5.2.7 Contact/helpdesk number ........... 16 Daikin website (publicly accessible). Menu structure: Overview installer settings....... 17 ▪ The full set of latest technical data is available on the Daikin extranet (authentication required). 6 Commissioning Checklist before commissioning..........18 Checklist during commissioning ..........18 About the box 6.2.1...
See the installer reference guide for more information. (mm) (mm) Air outlet Minimum required flow rate Air inlet 05+07 models 12 l/min See the recommended procedure as described in "6.2 Checklist during commissioning" on page 18. Installation manual EBLQ+EDLQ05+07CAV3 Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
The maximum height of the upper protruding part of the Installation bolts is 15 mm. Opening the units 4.1.1 To open the outdoor unit DANGER: RISK OF ELECTROCUTION DANGER: RISK OF BURNING EBLQ+EDLQ05+07CAV3 Installation manual Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
It is possible to install the unit on brackets to the wall: 4.2.2 To install the outdoor unit CAUTION Do NOT remove the protective cardboard before the unit is installed properly. Installation manual EBLQ+EDLQ05+07CAV3 Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cables from scratching the paint (field supply). 4 Attach the ends of the cables and tighten them. Protective cardboard Instruction sheet EBLQ+EDLQ05+07CAV3 Installation manual Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
Install a manometer in the system. Propylene glycol, including the necessary inhibitors, classified as Category III according to EN1717. NOTICE Install air purge valves at all local high points. WARNING Ethylene glycol is toxic. Installation manual EBLQ+EDLQ05+07CAV3 Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
3 If an automatic air purge valve was installed, make sure it is open. 4 Fill the circuit with water until the manometer (field supply) indicates a pressure of ±2.0 bar. EBLQ+EDLQ05+07CAV3 Installation manual Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
Be careful NOT to pinch the wiring when attaching the frontplate to the unit. The main user interface is required for operation, but has to be ordered separately (mandatory option). 1 2 3 Installation manual EBLQ+EDLQ05+07CAV3 Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
If you do NOT configure the system correctly, it might NOT work as expected. The configuration influences the following: ▪ The calculations of the software EBLQ+EDLQ05+07CAV3 Installation manual Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
Result: The user permission level switches to End user. The user interface will return to the default home screen. To modify an overview setting Example: Modify [1‑01] from 15 to 20. Installation manual EBLQ+EDLQ05+07CAV3 Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
Page 15
[9-09] Heating: required temperature difference between entering and leaving water. In case a minimum temperature difference is required for the good operation of the heat emitters in heating mode. EBLQ+EDLQ05+07CAV3 Installation manual Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
▪ 1 (Reheat + sched.): Same as 2, but between the scheduled heatup cycles, reheat operation is allowed. ▪ 2 (Scheduled only): The domestic hot water tank can ONLY be heated according to a schedule. Installation manual EBLQ+EDLQ05+07CAV3 Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
Amp. limits for DI UFH screed dryout kW limits for DI Air purge Priority Actuator test run INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. EBLQ+EDLQ05+07CAV3 Installation manual Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
The correct pipe size is installed and the pipes are properly insulated. There are no water leaks inside the outdoor unit. The shut-off valves are properly installed and fully open. Installation manual EBLQ+EDLQ05+07CAV3 Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
▪ [4‑01]≠1 3 Go to [A.7.4]: > Installer settings > Commissioning > Actuator test run. 4 Select an actuator and press . Example: Pump. 5 Select OK and press EBLQ+EDLQ05+07CAV3 Installation manual Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
4 Select Lock or Unlock, and press To activate or deactivate button lock 1 Press to go to one of the home pages. 2 Press for more than 5 seconds. Installation manual EBLQ+EDLQ05+07CAV3 Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...
8 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin extranet (authentication required). Piping diagram: Outdoor unit...
Page 25
3 core Control box power supply: 230 V + earth X1M: L-N-PE X1M: L-N-PE 2 core 230 V External indoor thermistor X2M: 1a-2a Power supply signal Only for KRCS01-1 4D09752-1C EBLQ+EDLQ05+07CAV3 Installation manual Daikin Altherma low temperature monobloc 4P403578-1F – 2018.06...