BINMASTER GWR-2000 Operating Instructions Manual

Tdr sensor for continuous level measurement of bulk solids
Hide thumbs Also See for GWR-2000:
Table of Contents

Advertisement

Quick Links

Operating Instructions
TDR sensor for continuous level
measurement of bulk solids
GWR-2000
4-20 mA/HART - two-wire
Rod and cable probe
Document ID: 41829
925-0345 Rev A

Advertisement

Table of Contents
loading

Summary of Contents for BINMASTER GWR-2000

  • Page 1 Operating Instructions TDR sensor for continuous level measurement of bulk solids GWR-2000 4-20 mA/HART - two-wire Rod and cable probe Document ID: 41829 925-0345 Rev A...
  • Page 2: Table Of Contents

    Set up with the quick setup ..................... 50 Saving the parameter adjustment data ................51 Set up with other systems DD adjustment programs ....................52 Field Communicator 375, 475 ..................52 Diagnostics and servicing GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 3 11.4 Trademark ........................84 Safety instructions for Ex areas Take note of the Ex specific safety instructions for Ex applications. These instructions are attached as documents to each instrument with Ex approval and are part of the operating instructions manual. Editing status: 2016-04-13 GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 4: About This Document

    This arrow indicates a single action. Sequence of actions Numbers set in front indicate successive steps in a procedure. Battery disposal This symbol indicates special information about the disposal of bat- teries and accumulators. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 5: For Your Safety

    Arbi- trary conversions or modifications are explicitly forbidden. The safety approval markings and safety tips on the device must also be observed. CE conformity The device fulfils the legal requirements of the applicable EC guide- lines. By affixing the CE marking, we confirm successful testing of the product. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 6: Namur Recommendations

    That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: • Chapter "Packaging, transport and storage" • Chapter "Disposal" GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 7: Product Description

    Go to www.vega.com "VEGA Tools" and "Instrument search". Enter the serial number. Alternatively, you can access the data via your smartphone: • Download the smartphone app "VEGA Tools" from the "Apple App Store" or the "Google Play Store" GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 8: Principle Of Operation

    The accuracy thus depends on the stability of the dielectric constant. If you measure a medium with a dielectric constant below 1.5, probe end tracking is always active. In this case, you have to enter the GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 9: Packaging, Transport And Storage

    The interface adapter VEGACONNECT enables the connection of communication-capable instruments to the USB interface of a PC. For parameter adjustment of these instruments, the adjustment software PACTware with VEGA-DTM is required. You can find further information in the operating instructions "Interface adapter VEGACONNECT" (Document-ID 32628). GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 10 You can use this display and adjustment module in an ambient tem- perature range of -40 … +70 °C. You can find further information in the operating instructions "Display and adjustment module with heating" (Document-ID 31708). GWR-2000 • 4-0 mA/HART - two-wire 925-0345 Rev A...
  • Page 11 If you mount the VEGAFLEX 82 in a bypass tube or standpipe, you Centering have to avoid contact to the bypass tube by using a spacer at the probe end. You can find additional information in the operating instructions manual "Centering". GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 12: Mounting

    These are mainly: • Active measuring component • Process fitting • Process seal Process conditions are particularly: • Process pressure • Process temperature • Chemical properties of the medium • Abrasion and mechanical influences GWR-2000 • 4-0 mA/HART - two-wire 925-0345 Rev A...
  • Page 13: Mounting Instructions

    The guided microwave principle requires a metallic surface on the process fitting. Therefore, in plastic vessels, etc., use an instru- ment version with flange (from DN 50) or place a metal sheet (ø > 200 mm/8 in) beneath the process fitting when screwing it in. Make sure that the plate has direct contact with the process fitting. When installing the probes without metal vessel wall, e.g. in plastic vessels, the measured value can be influenced by strong electromag- netic fields (emitted interference according to EN 61326: class A). Use a probe in coax version for applications in liquids. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 14 500 mm (20 in). ø >160 mm (ø >6.3") Fig. 4: Installation in concrete silo If possible, avoid sockets. Mount the sensor flush with the vessel top. Mounting socket If this is not possible, use short sockets with small diameter. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 15 2 Socket flush - optimum installation Welding work Before beginning the welding work, remove the electronics module from the sensor. By doing this, you avoid damage to the electronics through inductive coupling. Inflowing medium Do not mount the instruments in or above the filling stream. Make sure that you detect the product surface, not the inflowing product. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 16 If there is a danger of the rod probe touching the vessel wall, then the probe must be fastened at the bottom end. Keep in mind that below the fastening, a measurement is not possible. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 17 To compensate for the resulting changes in signal runtime, let the instrument determine the probe length automatically. You can find further information in the supplementary instructions of the rod and cable components. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 18: Connecting To Power Supply

    In the case of instrument housings with metric thread, the cable glands are screwed in at the factory. They are sealed with plastic plugs as transport protection. You have to remove these plugs before electrical connection. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 19: Connecting

    Connection procedure Proceed as follows: 1. Unscrew the housing lid 2. If a display and adjustment module is installed, remove it by turn- ing it slightly to the left. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 20 6. Insert the wire ends into the terminals according to the wiring plan Information: Solid cores as well as flexible cores with wire end sleeves are insert- ed directly into the terminal openings. In case of flexible cores without end sleeves, press the terminal from above with a small screwdriver, the terminal opening is then free. When the screwdriver is released, the terminal closes again. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 21: Wiring Plan, Single Chamber Housing

    For display and adjustment module or interface adapter For external display and adjustment unit 4 Ground terminal for connection of the cable screen Wiring plan, double chamber housing The following illustrations apply to the non-Ex as well as to the Ex-ia version. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 22 Parallel use of an external display and adjustment unit and a display and adjustment module in the terminal compartment is not supported. Terminal compartment - Radio module PLICS- MOBILE Status SIM-Card Test Fig. 14: Terminal compartment, radio module PLICSMOBILE Voltage supply GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 23: Wiring Plan, Ex-D-Ia Double Chamber Housing

    Internal connection to the plug connector for external display and adjust- ment unit (optional) Note: HART multidrop mode is not possible when using an Ex-d-ia instru- ment. Terminal compartment 4...20mA Fig. 16: Terminal compartment, double chamber housing Ex d ia Voltage supply, signal output 2 Ground terminal for connection of the cable screen GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 24 Pin 1 Pin 2 Pin 3 Pin 4 Contact pin Colour connection ca- Terminal, electronics ble in the sensor module Pin 1 Brown Pin 2 White Pin 3 Blue Pin 4 Black GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 25: Double Chamber Housing With Disadapt

    Pin 1 Pin 2 Pin 3 Pin 4 Contact pin Colour connection ca- Terminal, electronics ble in the sensor module Pin 1 Brown Pin 2 White Pin 3 Blue Pin 4 Black GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 26: Wiring Plan - Version Ip 66/Ip 68, 1 Bar

    2 Second current output (II) - Voltage supply and signal output (without HART) 3 Ground terminal for connection of the cable screen Supplementary elec- The radio module PLICSMOBILE is an external GSM/GPRS radio tronics - Radio module unit for transmission of measured values and for remote parameter PLICSMOBILE adjustment. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 27: Switch-On Phase

    As soon as a plausible measured value is found, the corresponding current is outputted to the signal cable. The value corresponds to the actual level as well as the settings already carried out, e.g. factory setting. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 28: Set Up With The Display And Adjustment Module

    The display and adjustment module is powered by the sensor, an ad- ditional connection is not necessary. Fig. 24: Installing the display and adjustment module in the electronics compart- ment of the single chamber housing GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 29: Adjustment System

    Adjustment system Fig. 26: Display and adjustment elements 1 LC display Adjustment keys • Key functions [OK] key: GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 30 In the second view, the selected measured value and a correspond- ing bar graph presentation are displayed. In the third view, the selected measured value as well as a second selectable value, e.g. the temperature, are displayed. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 31: Parameter Adjustment - Quick Setup

    Display: Settings, e.g., for language, measured value display, lighting Diagnosis: Information, e.g. on instrument status, pointer, measure- ment certainty, simulation, echo curve Additional adjustments: Reset, date/time, reset, copy function GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 32 In this menu item you can enter the probe length or have the length determined automatically by the sensor system. When choosing "Yes", then the probe length will be determined automatically. When choosing "No", you can enter the probe length manually. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 33 Dusts, wood chips Wood chips, sawdust In this menu item, you can enter the max. adjustment for the level. Setup - Max. adjustment Level Adjust the requested percentage value with [+] and store with [OK]. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 34 If the volume should not be displayed in percent but e.g. in l or kg, a scaling can be also set in the menu item "Display". GWR-2000 • 4-0 mA/HART - two-wire 925-0345 Rev A...
  • Page 35 Fig. 27: Vessel height and socket correction value D Vessel height +h Positive socket correction value -h Negative socket correction value GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 36 This should be done with the lowest possible level so that all potential interfering reflections can be detected. Proceed as follows: Enter the actual distance from the sensor to the product surface. All interfering signals in this section are detected by the sensor and stored. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 37 In the main menu point "Display", the individual submenu points should be selected subsequently and provided with the correct parameters to ensure the optimum adjustment of the display options. The procedure is described in the following. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 38 The function depends on the strength of the supply voltage, see "Technical data". In delivery status, the lighting is switched on. In this menu item, the device status is displayed. Diagnostics - Device status GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 39 This menu item displays the peak values of the electronics tempera- ture as well as the dielectric constant. In another window you can carry out a reset of the two peak values separately. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 40 This is generally recommended; for using the Asset Management functions it is necessary. If possible, the curve should be saved with a low level in the vessel. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 41 Basic settings: Resetting of the parameter settings, incl. special parameters, to the default values of the respective instrument. Any stored false signal suppression or user programmable linearisation curve, as well as the measured value memory, is deleted. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 42 Probe length Scaling size - Level Volume in l Scaling unit - Level Litres Scaling format - Level Without decimal positions Scaling level - 100 % corresponds to Scaling level - 0 % corresponds to GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 43 Device memory - Echo curve memory Stopped Device memory - Measured value memory Started Device memory - Measured value memory - Distance level, percentage value Measured values level, reliability level, electronics temperature GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 44 When data are being written into the sensor, the display shows which instrument type the data originate from and which TAG-no. this sensor had. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 45 Additional adjustments - In this menu item you can select the type and size of your probe from Probe type a list of all possible probes. This is necessary to adapt the electronics optimally to the probe. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 46 PC. Info - Sensor character- In this menu item, the features of the sensor such as approval, pro- istics cess fitting, seal, measuring range, electronics, housing and others are displayed. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 47: Saving The Parameter Adjustment Data

    If it is necessary to exchange a sensor, the display and adjustment module is inserted into the replacement instrument and the data are likewise written into the sensor via the menu item "Copy sensor data". GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 48: Setup With Pactware

    5 Interface adapter, for example VEGACONNECT 4 Note: With power supply units with integrated HART resistance (internal resistance approx. 250 Ω), an additional external resistance is not necessary. This applies, e.g. to the VEGA instruments VEGATRENN 149A, VEGAMET 381, VEGAMET 391. Common Ex separators are GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 49: Parameter Adjustment With Pactware

    In the standard version, all functions for complete setup are already included. An assistant for simple project configuration simplifies the adjustment considerably. Saving/printing the project as well as import/export functions are also part of the standard version. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 50: Set Up With The Quick Setup

    If the function is inactive, then possibly no instrument is connected. Check the connection to the instrument. Extended adjustment With the extended adjustment, you carry out the parameter adjust- ment for the instrument via the clear menu structure in the DTM GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 51: Saving The Parameter Adjustment Data

    Click to the button "Quick setup", to start the assistant-driven adjust- ment for a simplified and reliable setup. Saving the parameter adjustment data We recommend documenting or saving the parameter adjustment data via PACTware. That way the data are available for multiple use or service purposes. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 52: Set Up With Other Systems

    This software is updated via the Internet and new EDDs are automatically taken over into the device catalogue of this software after they are released by the manufacturer. They can then be transferred to a Field Communicator. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 53: Diagnostics And Servicing

    Echo curve of the setup: This is used as reference echo curve for the measurement conditions during setup. Changes in the measure- ment conditions during operation or buildup on the sensor can thus be recognized. The echo curve of the setup is stored via: • PC with PACTware/DTM GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 54: Status Messages

    PACTware/DTM or EDD. Out of specification: The measured value is unstable because the instrument specification is exceeded (e.g. electronics temperature). This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD. Maintenance: Due to external influences, the instrument function is limited. The measurement is affected, but the measured value is GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 55 – Error in the calibration car- – Exchanging the electronics Bit 8 of Byte 0 … 5 ried out in the factory – Send instrument for repair Error in the – Error in the EEPROM calibration GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 56 Bit 9 of Byte 14 …24 range not available – 100 % adjustment: Increase Overfilling value – Check mounting socket – Remove possible interfering signals in the close range – Use coaxial probe GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 57 Bit 5 of Byte 14 … 24 echo during operation lation and/or parameter no measured adjustment value avail- able – Process component or – Clean or exchange process probe contaminated or component or probe defective GWR-2000 • 4-0 mA/HART - two-wire 925-0345 Rev A...
  • Page 58: Rectify Faults

    22 mA or less than 3.6 mA the sensor defective The below tables show typical examples for application-relevant Treatment of measure- ment errors measurement errors. There are two measurement errors: • Constant level • Filling • Emptying GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 59 4. Measured value re- – Turbulence on the product – Check parameters, change if mains momentarily surface, quick filling necessary, e.g. in dosing ves- unchanged during fill- sel, reactor ing and then jumps to time the correct level GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 60: Exchanging The Electronics Module

    In Ex applications, only instruments and electronics modules with ap- propriate Ex approval may be used. If there is no electronics module available on site, the electronics module can be ordered through the agency serving you. The electron- GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 61: Exchange Or Shorten Cable/Rod

    4. Screw the new rod and the new cable manually to the thread on the process fitting. 5. Exert counterforce with the second fork spanner and tighten the measuring rod or cable on the flat surfaces with a torque of 20 Nm (15 lbf ft). GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 62 5. Shorten the cable/rod with a cut-off wheel or metal saw at the marking. Take note of the specifications in the following illustration when shortening the cable. 6. Cable: shift the cable into the gravity weight (according to the drawing) Plastic coated cable: remove coating according drawing to 70 mm (2.76 in). GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 63: Software Update

    You can find the current instrument software as well as detailed information on the procedure in the download area of our homepage: www.vega.com. Caution: Instruments with approvals can be bound to certain software versions. Therefore make sure that the approval is still effective after a software update is carried out. You can find detailed information in the download area at www.vega.com. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 64: How To Proceed If A Repair Is Necessary

    Attach the completed form and, if need be, also a safety data sheet outside on the packaging • Please contact the agency serving you to get the address for the return shipment. You can find the agency on our home page www.vega.com. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 65: Dismount

    Pass the instrument directly on to a spe- cialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 66: Supplement

    Ʋ Supporting material 316L Ʋ Glass potting Borosilicate glass GPC 540 Ʋ Contacts Alloy C22 Ʋ Helium leak rate < 10 mbar l/s Only with Ex d version Only with Ex d version GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 67 30 KN (6744 lbf) Ʋ Cable: ø 11 mm (0.433 in) - PA coated 30 KN (6744 lbf) The tensile force of solids are subject of a normal fluctuation range. For this reason, the determined diagram value of the following diagrams must be multiplied with safety factor 2. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 68 Vessel diameter 3 m (9.843 ft) Fig. 45: Max. tensile load with sand and cement - Cable: ø 4 mm (0.157 in) Sand Cement Tensile force in kN (the determined value must be multiplied with safety factor 2) Cable length in m Vessel diameter 12 m (39.37 ft) Vessel diameter 9 m (29.53 ft) Vessel diameter 6 m (19.69 ft) Vessel diameter 3 m (9.843 ft) GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 69 Vessel diameter 6 m (19.69 ft) Vessel diameter 3 m (9.843 ft) Thread in gravity weight, e.g. for eye-bolt M 12 (cable version) Torque for exchangeable cable or rod probe (in the process fitting) Ʋ Cable: ø 4 mm (0.157 in) 8 Nm (5.9 lbf ft) GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 70 3.8 … 20.5 mA (default setting) Signal resolution 0.3 µA Failure signal current output (adjustable) Last valid measured value, ≥ 21 mA, ≤ 3.6 mA Max. output current 21.5 mA The output values can be assigned individually The indication values can be assigned individually GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 71 Bulk solids - cereals, flour, cement (dielectric con- stant ~2.0) Ʋ Installation Probe end does not touch the vessel bottom Sensor parameter adjustment No gating out of false signals carried out The indication values can be assigned individually GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 72 ") -10 mm (-0.394 ") 0,08 m 0,3 m 0,02 m (3.15 (11.811 " " (0.787 ") Fig. 49: Deviation VEGAFLEX 82 in rod version Dead band - no measurement possible in this area Probe length Depending on the installation conditions, deviations can occur which can be rectified by adapting the adjust- ment or changing the measured value offset in the DTM service mode GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 73 0.22 % 1.2 % 200 °C (392 °F) -0.01 % 0.13 % 0.74 % 400 °C (752 °F) -0.02 % 0.08 % 0.52 % Also for the additional current output (optional) GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 74 -20 … +200 °C (-4 … +392 °F) ture adapter Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2). GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 75 392°F -40°C / -40°F Fig. 52: Ambient temperature - process temperature, version with temperature adapter Ambient temperature Process temperature (depending on the seal material) Aluminium housing Plastic housing Stainless steel housing, precision casting Stainless steel housing, electropolished GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 76 Ʋ Number of digits Ʋ Size of digits W x H = 7 x 13 mm Adjustment elements 4 keys Protection rating Ʋ unassembled IP 20 Ʋ mounted in the housing without lid IP 40 GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 77 Ʋ for 18 V< U < 36 V ≤ 1 V (16 … 400 Hz) Load resistor Ʋ Calculation )/0.022 A Ʋ Example - Non-Ex instrument with (24 V - 9.6 V)/0.022 A = 655 Ω = 24 V DC Electrical protective measures Protection rating GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 78: Dimensions

    ~ 69 mm ~ 84 mm (2.72") (3.31") ø 79 mm ø 79 mm (3.11") (3.11") M16x1,5 M20x1,5/ ½ NPT M20x1,5/ ½ NPT Fig. 53: Housing versions with protection rating IP 66/IP 67 - with integrated display and adjustment module the housing is 9 mm/0.35 in higher Single chamber version Double chamber version GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 79 Aluminium housing with protection rating IP 66/IP 68 (1 bar) ~ 105 mm ~ 150 mm (4.13") (5.91") ø 86 mm ø 86 mm (3.39") (3.39") M16x1,5 M20x1,5 M20x1,5 M20x1,5/ ½ NPT Fig. 55: Housing version with protection rating IP 66/IP 68 (1 bar) - with integrated display and adjustment module the housing is 9 mm/0.35 in higher Single chamber version Double chamber version GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 80 ø 80 mm ø 79 mm (3.39") (3.15") (3.11") M16x1,5 M20x1,5 M20x1,5/ ½ NPT M20x1,5/ ½ NPT Fig. 57: Housing version with protection rating IP 66/IP 68 (1 bar) - with integrated display and adjustment module the housing is 9 mm/0.35 in higher Single chamber version, electropolished Single chamber version, precision casting Double chamber version, precision casting GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 81 VEGAFLEX 82, cable version ø 4 mm (0.157 in)/ø 6 mm (0.236 in) - PA coated SW 36 mm (1.42") G ¾ ø 4 mm ø 6 mm (0.24") (0.16") ø 20 mm (0.79") Fig. 58: VEGAFLEX 82, cable ø 4 mm (0.157 in)/ø 6 mm (0.236 in) threaded version with gravity weight (all gravity weights with thread M12 for eye-bolt) Sensor length, see chapter "Technical data" Cable ø 4 mm (0.157 in) Cable ø 6 mm (0.236 in) - PA coated Joint - cable GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 82 VEGAFLEX 82, cable version ø 6 mm (0.236 in)/ø 11 mm (0.433 in) - PA coated SW 55 mm (2.17") G1½ ø 6 mm ø 11 mm (0.24") (0.43") ø 30 mm (1.18") Fig. 59: VEGAFLEX 82, cable ø 6 mm (0.236 in)/ø 11 mm (0.433 in) threaded version with gravity weight (all grav- ity weights with thread M12 for eye-bolt) Sensor length, see chapter "Technical data" Cable ø 6 mm (0.236 in) Cable ø 11 mm (0.433 in) - PA coated Joint - cable GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 83 11 Supplement VEGAFLEX 82, rod version ø 16 mm (0.63 in) SW 55 mm (2.17") G1½ ø 16 mm (0.63") Fig. 60: VEGAFLEX 82, rod ø 16 mm (0.63 in), threaded version Sensor length, see chapter "Technical data" Joint - rod GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 84: Industrial Property Rights

    Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную собственность. Дальнейшую информацию смотрите на сайте www.vega.com. VEGA系列产品在全球享有知识产权保护。 进一步信息请参见网站<www.vega.com。 11.4 Trademark All the brands as well as trade and company names used are property of their lawful proprietor/ originator. GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 85 – Display and adjustment module with Factory calibration date 46 False signal suppression 36 heating 10 – Electronics module 10 Fault rectification 58 – Rod components 11 Functional principle 8 – Spacer 11 Reset 41 Grounding 19 GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 86 INDEX Scaling measured value 45 Sensor characteristics 46 Sensor status 38 Service hotline 60 Simulation 40 Special parameters 46 Type label 7 Type of medium 33 Units 32 GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...
  • Page 87 Notes GWR-2000 • 4-20 mA/HART - two-wire 925-0345 Rev A...