Arbi- trary conversions or modifications are explicitly forbidden. The safety approval markings and safety tips on the device must also be observed. CE conformity The device fulfills the legal requirements of the applicable EC guide- lines. By affixing the CE marking, we confirm successful testing of the product. You can find the CE Certificate of Conformity in the download section of our homepage. 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfill this obligation by observing the environmental instructions in this manual: • Chapter "Packaging, transport and storage" • Chapter "Disposal" 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
Go to www.vega.com, "VEGA Tools" and "Instrument search". Enter the serial number. Alternatively, you can access the data via your smartphone: • Download the smartphone app "VEGA Tools" from the "Apple App Store" or the "Google Play Store" 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
Page 6
2 Product description • Scan the Data Matrix code on the type label of the instrument or • Enter the serial number manually in the app 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
Keep in mind that measurement all the way down to the tip of the probe may not be pos- sible. The exact value of the min. distance (lower dead band) is stated in chapter "Technical data". Fig. 2: Vessel with conical bottom 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
Page 8
Fig. 3: Installation in non-metallic vessel Flange Metal sheet Concrete vessel When installed in thick concrete ceilings, VEGAFLEX 82 should be mounted front flush to the lower edge. In concrete silos, the distance to the wall should be at least 500 mm (20 in). 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
Page 9
Check if this is relevant for your measurement. In such cases, always carry out a false signal suppression after instal- lation. You can find further information under "Setup procedure". _ < DN40 ... DN150 _ < > DN150 ... DN200 Fig. 5: Mounting socket 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
Page 10
3 Mounting When welding the socket, make sure that the socket is flush with the vessel top. Fig. 6: Socket must be installed flush Unfavourable installation 2 Socket flush - optimum installation 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
When the screwdriver is released, the terminal closes again. 6. Check the hold of the wires in the terminals by lightly pulling on them 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
Terminal Function Polarity Voltage supply Voltage supply 4 … 20 mA output (active) 4 … 20 mA output (passive) Mass - output Function ground with installa- tion according to CSA 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
Page 13
Terminal Function Polarity Voltage supply Voltage supply 4 … 20 mA output (active) 4 … 20 mA output (passive) Mass - output Function ground with installa- tion according to CSA 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
The display and adjustment module is powered by the sensor, an ad- ditional connection is not necessary. Fig. 10: Installing the display and adjustment module in the electronics compart- ment of the single chamber housing 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
If your instrument is only suitable for a certain medium, this menu item is not visible. Application In this menu item, you can select the application. You can choose between level measurement and interface measurement. You can 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
Page 16
They represent the correlation between the level percentage and vessel volume. The linearization applies for the measured value indication and the current output. By activating the suitable curve, the percentage vessel volume is displayed correctly. 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...
0.2 … 1.5 mm² (AWG 24 … 16) Voltage supply Operating voltage Ʋ Version for low voltage 9.6 … 48 V DC, 20 … 42 V AC, 50/60 Hz Ʋ Version for mains voltage 90 … 253 V AC, 50/60 Hz Interpolation protection Integrated Max. power consumption 4 VA; 2.1 W 927-0306 Rev A GWR-2000 4 - 20 mA/HART - four-wire...