The solar pump does not operate, despite the fact that the switch-on condi-
tions are satisfied:
Secondary symptoms
The pump symbol in the
display rotates.
The pump symbol in the
display does not rotate.
The pump symbol in the
display does not rotate.
The display illumination
is red.
A tool symbol flashes in
the display.
The pump symbol in the
display does not rotate.
The display illumination
flashes red.
EN
Possible cause
Pump power supply is
interrupted.
Pump has seized up.
The maximum storage
tank temperature has
been reached.
The maximum collector
temperature has been
reached.
In multi storage tank
systems: the system has
stopped due to a priority
test.
The minimum collector
temperature has not
been reached.
The maximum loading
temperature has been
reached.
Stagnation reduction
activated
Storage tank deactivated
The operating switch is set
to manual operation and
the pump output is set to
„off".
Short circuit or interruption
of a temperature sensor
730.137 | 08.37
Procedure
Check the pump power cable.
Check the fuse in the controller
(replacement fuse is located in the
case).
Get the pump working again, replace
if necessary.
No fault
Set the operating switch to auto-
matic operation.
On the controller, request the current
values from all connected tempera-
ture sensors.
Check all defective sensors and/or
sensor cable.