Mitsubishi Heavy Industries SRK06CJ Technical Manual & Parts List

Mitsubishi Heavy Industries SRK06CJ Technical Manual & Parts List

Residential air-conditioning wall mounted type (split system, air cooled cooling only type)
Hide thumbs Also See for SRK06CJ:
Table of Contents

Advertisement

Manual No.'11•SRK-T-114
RESIDENTIAL AIR-CONDITIONING
TECHNICAL MANUAL & PARTS LIST
WALL MOUNTED TYPE
RESIDENTIAL AIR-CONDITIONER
(Split system, air cooled cooling only type)
SRK06CJ, 09CJ, 12CJ
SRK06CJ-3, 09CJ-3, 12CJ-3
SRK10CJV-3, 13CJV-3
SRK10CJV-4, 13CJV-4
SRK19CK, 24CK
SRK19CK-3, 24CK-3
SRK19CKS-3, 25CKS-3
SRK19CKS-4, 25CKS-4

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SRK06CJ and is the answer not in the manual?

Questions and answers

Summary of Contents for Mitsubishi Heavy Industries SRK06CJ

  • Page 1 Manual No.'11•SRK-T-114 RESIDENTIAL AIR-CONDITIONING TECHNICAL MANUAL & PARTS LIST WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONER (Split system, air cooled cooling only type) SRK06CJ, 09CJ, 12CJ SRK06CJ-3, 09CJ-3, 12CJ-3 SRK10CJV-3, 13CJV-3 SRK10CJV-4, 13CJV-4 SRK19CK, 24CK SRK19CK-3, 24CK-3 SRK19CKS-3, 25CKS-3 SRK19CKS-4, 25CKS-4...
  • Page 2: Table Of Contents

    TECHNICAL MANUAL 1. SRK06CJ, 09CJ, 12CJ SRK06CJ-3, 09CJ-3, 12CJ-3 ........2 2. SRK10CJV-3, 13CJV-3 SRK10CJV-4, 13CJV-4 ..........31 3. SRK19CK, 24CK SRK19CK-3, 24CK-3 ..........63 4. SRK19CKS-3, 25CKS-3 SRK19CKS-4, 25CKS-4 ..........97...
  • Page 3: Srk06Cj, 09Cj, 12Cj Srk06Cj-3, 09Cj-3, 12Cj-3

    WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONER Split system, air cooled cooling only type 1. SRK06CJ, 09CJ, 12CJ SRK06CJ-3, 09CJ-3, 12CJ-3...
  • Page 4 '11 • SRK-T-114 CONTENTS 1.1 SPECIFICATIONS ..................1.2 EXTERIOR DIMENSIONS ................(1) Indoor units ..................(2) Outdoor units ..................(3) Wireless remote controller ..............1.3 ELECTRICAL WIRING ................. (1) Indoor units ..................(2) Outdoor units ..................10 1.4 PIPING SYSTEM ..................11 1.5 RANGE OF USAGE &...
  • Page 5 '11 • SRK-T-114 (7) Phenomenon observed after shortcircuit, wire breakage on sensor ..29 (8) Checking the indoor electrical equipment ........... 29 (9) How to make sure of wireless remote controller ........30 ■How to read the model name Example: SRK 06 C Series code Cooling only type Product capacity...
  • Page 6: Specifications

    1.1 SPECIFICATIONS SRK06CJ (-3) Model Item Indoor unit SRK06CJ (-3) Outdoor unit SRC06CJ (-3) 1500 Cooling capacity (1) BTU/h 5000 Power supply 1 Phase, 220 / 230V, 50Hz Power Cooling 0.385 consumption Running Operation Cooling current data (1) Inrush current Cooling 3.90...
  • Page 7 SRK09CJ (-3) Model Indoor unit SRK09CJ (-3) Outdoor unit SRC09CJ (-3) Item 2640 Cooling capacity (1) BTU/h 9000 Power supply 1 Phase, 220 / 230V, 50Hz Power Cooling 0.88 consumption Running Operation Cooling current data (1) Inrush current Cooling 3.00 Noise level Cooling Sound level dB(A)
  • Page 8 SRK12CJ (-3) Model Item Indoor unit SRK12CJ (-3) Outdoor unit SRC12CJ (-3) 3450 Cooling capacity (1) BTU/h 11800 Power supply 1 Phase, 220 / 230V, 50Hz Power Cooling 1.125 consumption Running Cooling Operation current data (1) Inrush current Cooling 3.07 Noise level Cooling Sound level dB(A)
  • Page 9: Exterior Dimensions

    Frequency of ON-OFF cycle Max. 3 minutes ON and OFF interval 1.2.3 Exterior dimensions 1.2 EXTERIOR DIMENSIONS (1) Indoor units Indoor unit Models SRK06CJ(-3), 09CJ(-3), 12CJ(-3) Models SRK06CJ, 09CJ, 12CJ Unit: mm Piping hole right (left) Terminal block 206.5 133.5 102.5...
  • Page 10: Outdoor Units

    Outdoor unit Unit: mm Model SRC06CJ(-3), 09CJ(-3) 192.5 Drain holes 372.5 82.5 82.5 2 - ø12 Terminal block 61.5 127.7 33.3 Service valve (Liquid) Flare connecting ø6.35 (1/4˝) 40˚ 40˚ Service valve (Gas) Flare connecting ø9.52 (3/8˝) Model SRC12CJ (-3) Unit: mm Anchor bolt hole Drain discharge holes...
  • Page 11: Wireless Remote Controller

    (3) Wireless remote controller Unit: mm 17.3...
  • Page 12: Electrical Wiring

    Power source 220/230/240V 50Hz OUTDOOR UNIT CONTROL BOX 52C-4 52C-3 t° 1~ 250V 3.15A t° Wireless R-Amp Display Back up Sw IC15 Printed circuit board Meaning of Marks Color symbol Symbol Parts name Symbol Parts name Black Capacitor for Room temp. thermistor Blue White Fuse...
  • Page 13 WHITE BLACK ORANGE BLACK BLACK INDOOR UNIT WHITE Power source 220-240V 50Hz WHITE BLACK BLACK WHITE Meaning of Marks ORANGE Symbol Parts name Capacitor for CM Capacitor for FMo CAPACITOR Compressor motor Fan motor Motor protector for CM Terminal block Connector...
  • Page 14: Indoor Units

    1.4 PIPING SYSTEM 1.4 PIPING SYSTEM Models SRK06CJ(-3), 09CJ(-3) Model SRK06CJ-3, 09CJ-3 Indoor unit Outdoor unit Cooling cycle Flare connecting Service valve (Gas) Piping Check joint (Gas) ø9.52 Accumulator Room temp. Heat Heat sensor exchanger exchanger sensor Heat Compressor exchanger...
  • Page 15: Range Of Usage & Limitations

    1.5 RANGE OF USAGE & LIMITATIONS Models All models Item Indoor return air temperature ( Upper, lower limits ) Refer to the selection chart Outdoor air temperature ( Upper, lower limits ) Refrigerant line ( one way ) length Max. 15m Max.
  • Page 16 (2) Correction of cooling capacity in relation to one way length of refrigerant piping Piping length [m] Cooling 0.99 0.975 How to obtain the cooling capacity SRK12CJ (-3) 3450W 0.975 3364 W (11800 BTU/h) (11500 BTU/h) Factor by air SRK12CJ (-3) Length 15m temperatures...
  • Page 17: Application Data

    1.6 APPLICATION DATA Safety precautions • Please read these “Safety Precautions” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two headings, WARNING and CAUTION , those points which are WARNING section. related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the CAUTION section as well.
  • Page 18 Standard accessories Necessary tools for the installation work (Installation kit) Q'ty Accessories for indoor unit Plus headed driver (Phillips screwdriver) Installation board Knife ① (Attached to the rear of the indoor unit) ② Wireless remote control Tape measure ③ Remote contorol holder Hammer Tapping screws ④...
  • Page 19 Limitations for one way piping length and vertical height difference One way piping length ( ) 15 m Outdoor unit is lower Vertical height Outdoor unit difference (h) is higher Installation of indoor unit Installation of installation board Look for the inside wall structures (Intersediate support or INSTALLATION SPACE (INDOOR UNIT) (FRONT VIEW) pillar and firaly install the unit after level surface has been...
  • Page 20 Preparation of indoor unit Terminal block ① Mounting of connecting wires ⓐ Remove the lid. ⓑ Remove the wiring clamp. ⓒ Connect the connecting wire securely to the terminal block. Use cable for interconnection wiring to avoid loosening of the wires.
  • Page 21 ⑤ Securing the indoor unit to the installation board Indoor unit Installing steps Installation board Latch (2 locations) 1.Hook the upper part of the indoor unit to the installation board. Installation board 2.The unit can be installed Wall simply by gently push- ing in the lower part.
  • Page 22 Installation of outdoor unit ① Make sure that the unit is stable in installation. Fix the unit to stable base. ② Perfrom wiring, making wire terminal numbers conform to terminal numbers of indoor unit terminal block. ③ Earth lead wire shall be longer than the other lead wires Terminal block for the electrical safety in case of the slipping out of the cord from the anchorage.
  • Page 23 ♦ Additional refrigerant charge When refrigerant piping exceeds 7.5m conduct additional refrigerant charge after refrigerant sweeping. 7.5m over 15m:Additional charge amount per meter = 10g/m [Example] How much amount of additional charge for 15m piping? (15 – 7.5)m × 10g/m=75g 75g for additional charge Insulation of connecting portion ①...
  • Page 24: Outline Of Operation Control By Microcomputer

    1.7 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER (1) Operation control function by remote controller Remote controller S Operation section FAN SPEED button OPERATION MODE select button Each time the button is pushed, the Each time the button pushed, the indicator is switched over in turn. indicator is switched over in turn.
  • Page 25: Unit On/Off Button

    Unit indication section SRK10YJV-S RUN light (green) SRK13YJV-S Illuminates during operation and CLEAN operation. TIMER light (yellow) Illuminates during TIMER operation. (2) Unit ON/OFF button When the remote controller batteries become weak, or if the remote controller is lost or malfunctioning, this button may be used to turn the unit on and off.
  • Page 26: Flap Control

    '09•SRK-DB-087D (5) Flap control (a) Flap (Flap stopped) (Swing) Angle of Flap from Horizontal Remote controller display COOL , DRY, FAN Approx. 10° Approx. 20° Approx. 30° Approx. 45° Approx. 60° (b) Swing In COOL, DRY, FAN operation Approx. 10° Approx.
  • Page 27: Outline Of Cooling Operation

    (7) Outline of cooling operation (a) Operation of major functional components in Cooling mode Cooling Thermostat ON Thermostat OFF Failure Compressor Indoor fan motor Outdoor fan motor (few minutes ON) (few minutes ON) (b) Fan speed switching Model All models Fan speed Auto Auto fan control...
  • Page 28: Protective Control Function

    (9) Protective control function (a) Frost prevention for indoor heat exchanger (During cooling or dehumidifying) Operating conditions Indoor heat exchanger temperature (Th2) is lower than 2.5ºC. 3 minutes elapsed after the start of operation. Detail of frost prevention operation Compressor Indoor fan Protects the fan tap just before frost prevention control.
  • Page 29: Maintenance Data

    1.8 MAINTENANCE DATA (1) Cautions (a) If you are disassembling and checking an air conditioner, be sure to turn off the power before beginning. When working on indoor units, let the unit sit for about  minute after turning off the power before you begin work. When working on an outdoor unit, there may be an electrical charge applied to the main circuit (electrolytic condenser), so begin work only after discharg- ing this electrical charge (to DC 10 V or lower).
  • Page 30: Troubleshooting Procedure (If The Air Conditioner Runs)

    (4) Troubleshooting procedure (If the air conditioner runs) Confirm the contents of the customer complaint. The cause of the trouble can be specifically identified. Eliminate the cause of the trouble and perform an Check the self-diagnosis display. operation check. See below. Identify the faulty component by using the check procedure corresponding to the content of the trouble.
  • Page 31: Inspection Procedures Corresponding To Detail Of Trouble

    (6) Inspection procedures corresponding to detail of trouble Sensor error [Broken sensor wire, connector poor connection] Is connector connection good? Correct connection. Is sensor resistance value good? Replace sensor. Replace PCB. ◆ Sensor temperature characteristics (Room temp., indoor heat exchanger temp.) (Broken wire) (Short circuit) - 10...
  • Page 32 Trouble of outdoor unit [Compressor malfunction of insufficient gas (refrigerant)] Replace capacitor for compressor. Is capacitor for compressor normal? Does compressor operation? Is connector for compressor connection Correct connection good? Replace compressor. Is heat exchanger sensor resistance Replace heat exchanger sensor value good? Check if there are any places where Is refrigerant amount normal?
  • Page 33 (9) How to make sure of wireless remote controller Is remote Remote controller controller normal? defects Replace the display. Again pushing operating switch Is the unit operable with remote Normal controller? Abnormality is not Operating the unit? found. Defective remote controller Does unit ON/OFF button operates?
  • Page 34: Srk10Cjv-3, 13Cjv-3

    WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONER Split system, air cooled cooling only type 2. SRK10CJV-3, 13CJV-3 SRK10CJV-4, 13CJV-4...
  • Page 35 '10 • SRK-T-099 CONTENTS 2.1 SPECIFICATIONS ..................34 2.2 EXTERIOR DIMENSIONS ................36 (1) Indoor units ..................36 (2) Outdoor units ..................37 (3) Wireless remote controller ..............38 2.3 ELECTRICAL WIRING ................. 39 (1) Indoor units ..................39 (2) Outdoor units ..................
  • Page 36 (7) Phenomenon observed after shortcircuit, wire breakage on sensor ..61 (8) Checking the indoor electrical equipment ........... 61 (9) How to make sure of wireless remote controller ........62 ■How to read the model name Example: SRK 10 C JV-3 Series code Cooling only...
  • Page 37: Specifications

    2.1 SPECIFICATIONS SRK10CJV-3 (-4) Model Item Indoor unit SRK10CJV-3 (-4) Outdoor unit SRC10CJV-3 (-4) 2640 Cooling capacity (1) BTU/h 9000 Power supply 1Phase, 220 / 230V, 50Hz Power Cooling 0.73 consumption Running Operation Cooling current data (1) Inrush current Cooling 3.62 Noise level Cooling Sound level...
  • Page 38 SRK13CJV-3 (-4) Model Item Indoor unit SRK13CJV-3 (-4) Outdoor unit SRC13CJV-3 (-4) 3660 Cooling capacity (1) BTU/h 12500 Power supply 1Phase, 220 / 230V, 50Hz Power Cooling 1.065 consumption Running Cooling Operation current data (1) Inrush current Cooling 3.44 Noise level Cooling Sound level dB(A) Exterior dimensions (Height x Width x Depth)
  • Page 39: Exterior Dimensions

    2.2 EXTERIOR DIMENSIONS (1) Indoor units Models SRK10CJV-3(-4), 13CJV-3(-4) Unit: mm Piping hole right (left) Terminal block 206.5 133.5 102.5 102.5 17.5 Piping for Gas 53.5 53.5 10 :ø9.52 13 :ø12.7 380.6 Piping for Liquid 448.6 (ø6.35) VIEW A Drain hose 520 (ø16) Piping hole (ø65) Piping hole (ø65)
  • Page 40: Outdoor Units

    (2) Outdoor units Models SRC10CJV-3(-4), 13CJV-3(-4) Anchor bolt hole Drain discharge holes 50.6 Unit: mm 390.6 390.6 111.6 158.4 17.9 61.9 Terminal block Service valve (Liquid) Flare connection 138.4 33.5 ø6.35(1/4") Service valve (Gas) Flare connection 10: ø9.52 (3/8") 13: ø12.7 (1/2")
  • Page 41: Wireless Remote Controller

    (3) Wireless remote controller Unit: mm 17.3...
  • Page 42: Electrical Wiring

    Power source 220/230/240V 50Hz OUTDOOR UNIT CONTROL BOX 52C-4 52C-3 t° 1~ 250V 3.15A t° Wireless R-Amp Display IC15 Back up Sw Printed circuit board Meaning of Marks Color symbol Symbol Parts name Symbol Parts name Black Capacitor for Louver motor(RIGHT) Blue White Fuse...
  • Page 43 WHITE BLACK ORANGE BLACK BLACK INDOOR UNIT WHITE Power source 220-240V 50Hz WHITE BLACK BLACK WHITE Meaning of Marks ORANGE Symbol Parts name Capacitor for CM Capacitor for FMo CAPACITOR Compressor motor Fan motor Motor protector for CM Terminal block Connector...
  • Page 44: Indoor Units

    2.4 PIPING SYSTEM Model All models Indoor unit Outdoor unit Cooling cycle Flare connecting Service valve (Gas) Piping Check joint (Gas) 10 : ø9.52 13 : ø12.7 Accumulator Room temp. Heat Heat sensor exchanger exchanger sensor Heat Compressor exchanger Piping (Liquid) Service valve (Liquid) ø6.35...
  • Page 45: Range Of Usage & Limitations

    2.5 RANGE OF USAGE & LIMITATIONS Models All models Item Indoor return air temperature ( Upper, lower limits ) Refer to the selection chart Outdoor air temperature ( Upper, lower limits ) Refrigerant line ( one way ) length Max. 15m Max.
  • Page 46 (2) Correction of cooling capacity in relation to one way length of refrigerant piping Piping length [m] Cooling 0.99 0.975 How to obtain the cooling capacity SRK13CJV-3 3660W 0.975 3569 W (12500 BTU/h) (12187 BTU/h) Factor by air SRK13CJV-3 Length 15m temperatures...
  • Page 47: Application Data

    2.6 APPLICATION DATA Safety precautions • Please read these “Safety Precautions” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two headings, WARNING and CAUTION , those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the WARNING section.
  • Page 48 Standard accessories Necessary tools for the installation work (Installation kit) Q'ty Accessories for indoor unit Plus headed driver (Phillips screwdriver) Installation board Knife ① (Attached to the rear of the indoor unit) ② Wireless remote control Tape measure ③ Remote contorol holder Hammer Tapping screws ④...
  • Page 49 Limitations for one way piping length and vertical height difference One way piping length ( ) 15 m Outdoor unit is lower Vertical height Outdoor unit difference (h) is higher � Installation of indoor unit Installation of installation board INSTALLATION SPACE (INDOOR UNIT) (FRONT VIEW) Look for the inside wall structures (Intersediate support or pillar and firaly install the unit after level surface has been...
  • Page 50 Preparation of indoor unit Terminal block ① Mounting of connecting wires ⓐ Remove the lid. ⓑ Remove the wiring clamp. ⓒ Connect the connecting wire securely to the terminal block. Use cable for interconnection wiring to avoid loosening of the wires.
  • Page 51 ⑤ Securing the indoor unit to the installation board Indoor unit Installing steps Installation board Latch (2 locations) 1.Hook the upper part of the indoor unit to the installation board. Installation board 2.The unit can be installed Wall simply by gently push- ing in the lower part.
  • Page 52 Installation of outdoor unit ① Make sure that the unit is stable in installation. Fix the unit to stable base. ② Perfrom wiring, making wire terminal numbers conform Terminal block to terminal numbers of indoor unit terminal block. ③ Earth lead wire shall be longer than the other lead wires for the electrical safety in case of the slipping out of the cord from the anchorage.
  • Page 53 ♦ Additional refrigerant charge When refrigerant piping exceeds 7.5m conduct additional refrigerant charge after refrigerant sweeping. 7.5m over 15m:Additional charge amount per meter = 10g/m [Example] How much amount of additional charge for 15m piping? (15 – 7.5)m × 10g/m=75g 75g for additional charge Insulation of connecting portion ①...
  • Page 54: Outline Of Operation Control By Microcomputer

    2.7 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER (1) Operation control function by remote controller Remote controller S Operation section Unit display section...
  • Page 55: Unit On/Off Button

    Unit indication section SRK10YJV-S RUN light (green) SRK13YJV-S Illuminates during operation and CLEAN operation. TIMER light (yellow) Illuminates during TIMER operation. (2) Unit ON/OFF button When the remote controller batteries become weak, or if the remote controller is lost or malfunctioning, this button may be used to turn the unit on and off.
  • Page 56: Flap And Louver Control

    '09•SRK-DB-087D (5) Flap and louver control (a) Flap (Flap stopped) (Swing) Angle of Flap from Horizontal Remote controller display COOL , DRY, FAN Approx. 10° Approx. 20° Approx. 30° Approx. 45° Approx. 60° (b) Louver (Louver stopped) (Swing) (Spot) (Wide) Angle of Louver Remote controller display...
  • Page 57: Auto Operation

    (6) 3D auto operation Control the flap and louver by 3D AUTO button on the wireless remote controller. Fan speed and air flow direction are automatically controlled, allowing the entire room to efficiently conditioned. Detail of operation Perform STEP1 → STEP2 → STEP3 → STEP4 one time. After performing STEP4 in 1 ) above, the next steps to be carried out are determined by the difference between the room temperature and the setting temperature.
  • Page 58: Timer Operation

    '09•SRK-DB-087D (7) Timer operation (a) Comfortable timer setting (ON timer) (b) Sleep timer operation (c) OFF timer operation (8) Installation location setting (a) Setting If the air conditioning unit is running, press the ON/OFF button to stop. Press the AIR FLOW (UP/DOWN) button and the AIR FLOW (LEFT/RIGHT) button together for 5 seconds...
  • Page 59: Outline Of Cooling Operation

    (9) Outline of cooling operation (a) Operation of major functional components in Cooling mode Cooling Thermostat ON Thermostat OFF Failure Compressor Indoor fan motor Outdoor fan motor (few minutes ON) (few minutes ON) (b) Fan speed switching Model All models Fan speed Auto Auto fan control...
  • Page 60: Protective Control Function

    (11) Protective control function (a) Frost prevention for indoor heat exchanger (During cooling or dehumidifying) Operating conditions Indoor heat exchanger temperature (Th2) is lower than 2.5ºC. 3 minutes elapsed after the start of operation. Detail of frost prevention operation Compressor Indoor fan Protects the fan tap just before frost prevention control.
  • Page 61: Maintenance Data

    2.8 MAINTENANCE DATA (1) Cautions (a) If you are disassembling and checking an air conditioner, be sure to turn off the power before beginning. When working on indoor units, let the unit sit for about 1 minute after turning off the power before you begin work. When working on an outdoor unit, there may be an electrical charge applied to the main circuit (electrolytic condenser), so begin work only after discharg- ing this electrical charge (to DC 10 V or lower).
  • Page 62: Troubleshooting Procedure (If The Air Conditioner Runs)

    (4) Troubleshooting procedure (If the air conditioner runs) Confirm the contents of the customer complaint. The cause of the trouble can be specifically identified. Eliminate the cause of the trouble and perform an Check the self-diagnosis display. operation check. See below. Identify the faulty component by using the check procedure corresponding to the content of the trouble.
  • Page 63: Inspection Procedures Corresponding To Detail Of Trouble

    (6) Inspection procedures corresponding to detail of trouble Sensor error [Broken sensor wire, connector poor connection] Is connector connection good? Correct connection. Is sensor resistance value good? Replace sensor. Replace PCB. ◆ Sensor temperature characteristics (Room temp., indoor heat exchanger temp.) (Broken wire) (Short circuit) - 10...
  • Page 64 Trouble of outdoor unit [Compressor malfunction of insufficient gas (refrigerant)] Replace capacitor for compressor. Is capacitor for compressor normal? Does compressor operation? Is connector for compressor connection Correct connection good? Replace compressor. Is heat exchanger sensor resistance Replace heat exchanger sensor value good? Check if there are any places where Does trouble persist after charging gas?
  • Page 65 (9) How to make sure of wireless remote controller Is remote Remote controller controller normal? defects Replace the display. Again pushing operating switch Is the unit operable with remote Normal controller? Abnormality is not Operating the unit? found. Defective remote controller Does unit ON/OFF button operates?
  • Page 66: Srk19Ck, 24Ck Srk19Ck-3, 24Ck-3

    WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONER Split system, air cooled cooling only type 3. SRK19CK, 24CK SRK19CK-3, 24CK-3...
  • Page 67 CONTENTS 3.1 SPECIFICATIONS ..................66 3.2 EXTERIOR DIMENSIONS ................68 (1) Indoor units ..................68 (2) Outdoor units ..................69 (3) Wireless remote controller ..............70 3.3 ELECTRICAL WIRING ................. 71 (1) Indoor units ..................71 (2) Outdoor units ..................72 3.4 PIPING SYSTEM ..................
  • Page 68 '10 • SRK-T-099 (7) Phenomenon observed after shortcircuit, wire breakage on sensor ..94 ........... 95 (8) Checking the indoor electrical equipment (9) How to make sure of wireless remote controller ........96 ■How to read the model name Example: SRK 19 C K -3 For Indonesia Series code...
  • Page 69: Specifications

    3.1 SPECIFICATIONS SRK19CK (-3) Model Item Indoor unit SRK19CK (-3) Outdoor unit SRC19CK (-3) Cooling capacity (1) 5280 Power supply 1 Phase, 220/230/240V, 50Hz Power Cooling 1.59 consumption Running Cooling 7.4/7.1/6.8 current Operation data (1) Inrush current Cooling 3.32 Sound level dB(A) Hi : 44 Me : 41 Lo : 38 Noise...
  • Page 70: Exterior Dimensions

    SRK24CK (-3) Model Item Indoor unit SRK24CK (-3) Outdoor unit SRC24CK (-3) Cooling capacity (1) 6700 Power supply 1 Phase, 220/230/240V, 50Hz Power Cooling 2.28 consumption Running Cooling 10.5/10.0/9.6 current Operation data (1) Inrush current Cooling 2.94 Sound level dB(A) Hi : 50 Me : 46 Lo : 43 Noise Cooling...
  • Page 71: Indoor Units

    1090 Symbol Content 43.5 Gas piping ø 15.88 (5/8") (Flare) Liquid piping ø 6.35 (1 / 4") (Flare) Hole on wall for right rear piping ( ø 65) Hole on wall for left rear piping ( ø 65) Drain hose VP16 Outlet for wiring Outlet for piping(on both side)...
  • Page 72: Outdoor Units

    (2) Outdoor unit Model SRC19CK(-3) 286.4 Drain holes Unit: mm 203.1 136.9 Elogated hole (2-12 x16) Terminal block 34.6 Ground terminal Service valve (Liquid) ø6.35 (1/4'') Service valve (Gas) ø15.88 (5/8'') Model SRC24CK(-3) Unit: mm Drain holes 2-ø15 25.8 29.8 87.9 Terminal block Service valve (Liquid)
  • Page 73: Wireless Remote Controller

    (3) Wireless remote controller Unit: mm 17.3...
  • Page 74: Electrical Wiring

    3.3 ELECTRICAL WIRING (1) Indoor units Models SRK19CK(-3), 24CK(-3) DISPLAY WIRELESS RECEIVER BACK-UP SW PRINTED CIRCUIT BOARD FLAP ROOM TEMP. MOTOR SENSOR CNX2 HEAT EXCHANGER SENSOR 1 VARISTOR WHITE BLACK FUSE 52C-3 BLUE WHITE 250V YELLOW 3.15A BLUE BLACK 52C-4 FAN MOTOR HEAT TERMINAL...
  • Page 75: Outdoor Units

    (2) Outdoor units Model SRC19CK(-3) MEANING OF MARK SYMBOL PARTS NAME COMPRESSOR MOTOR FAN MOTOR RUNNING CAPACITOR FOR COMPRESSOR RUNNING CAPACITOR FOR FAN MOTOR MOTOR PROTECTOR CONNECTOR TERMINAL BLOCK MARK COLOR BLACK BLUE ORANGE WHITE INDOOR UNIT POWER SOURCE 220-240V 50Hz...
  • Page 76 Model SRC24CK(-3) MEANING OF MARK SYMBOL PARTS NAME COMPRESSOR MOTOR FAN MOTOR RUNNING CAPACITOR FOR COMPRESSOR RUNNING CAPACITOR FOR FAN MOTOR CONNECTOR TERMINAL BLOCK MARK COLOR BLACK BLUE ORANGE WHITE INDOOR UNIT POWER SOURCE 220-240V 50Hz...
  • Page 77: Piping System

    3.4 PIPING SYSTEM Model SRK19CK(-3) Indoor unit Outdoor unit Flare connecting Service valve (Gas) Piping (Gas) Check joint ø 15.88 Room temp. Heat Heat sensor exchanger exchanger sensor Heat Accumulator Compressor exchanger Piping (Liquid) Service valve (Liquid) ø6.35 Capillary tube Strainer Strainer Flare connecting...
  • Page 78: Range Of Usage & Limitations

    3.5 RANGE OF USAGE & LIMITATIONS Models All models Item Indoor return air temperature ( Upper, lower limits ) Refer to the selection chart Outdoor air temperature ( Upper, lower limits ) Refrigerant line ( one way ) length Max. 15m Max.
  • Page 79 (2) Correction of cooling capacity in relation to one way length of refrigerant piping Piping length [m] Cooling 0.99 0.975 How to obtain the cooling capacity SRK24CK(-3) 6700 6533 SRK24CK(-3)
  • Page 80: Application Data

    3.6 APPLICATION DATA Safety precautions When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces. We recommend you to read this “SAFETY PRECAUTIONS”...
  • Page 81 CAUTION Use the circuit breaker with sufficient breaking capacity. Take care when carrying the unit by hand. If the breaker does not have sufficient breaking capacity, it can cause the unit If the unit weights more than 20kg, it must be carried by two or more per- malfunction and fire.
  • Page 82 Standard accessories Necessary tools for the installation work (Installation kit) Q'ty Accessories for indoor unit Plus headed driver (Phillips screwdriver) Installation board Knife ① (Attached to the rear of the indoor unit) ② Wireless remote control Tape measure ③ Remote contorol holder Hammer Tapping screws ④...
  • Page 83 Limitations for one way piping length and vertical height difference Total one way piping length ( ) Max. 15 m Vertical height difference (h) Max. 10 m Installation of indoor unit Installation of installation board INSTALLATOIN SPACE (INDOOR UNIT) (FRONT VIEW) Look for the inside wall structures (Intersediate support or pillar and firaly install the unit after level surface has been checked.)
  • Page 84 Preparation of indoor unit ① Mounting of connecting wires ⓐ Open the air inlet panel. ⓑ Remove the lid. ⓒ Remove the wiring clamp. ⓓ Connect the connecting wire securely to the terminal block. Use cable for interconnection wiring to avoid loosening of the wires.
  • Page 85 ⑤ Securing the indoor unit to the installation board Latch (2 locations) Installing steps Indoor unit 1.Hook the upper part of the indoor unit to the installation board. Installation board Installation board 2.The unit can be installed simply by gently push- Wall ing in the lower part.
  • Page 86 Installation of outdoor unit ① Make sure that the unit is stable in installation. Fix the Outdoor unit unit to stable base. When installing the unit at a higher place or where it ② could be toppled by strong winds, secure the unit firmly with foundation bolts, wire, etc.
  • Page 87 Air purge Compound pressure gauge Operation valve ① Tighten all flare nuts in the pipings both Pressure gauge indoor and outside wall so as not to Operation valve Gauge manifold cause leak. (two-way valve) -0.1MPa (Designed specifically for R22) (-76cmHg) ②...
  • Page 88 Installation of remote control switch Mounting method of battery Fixing to pillar or wall Uncover the remote control switch, and mount the bat- Conventionally, operate the wireless remote control teries [R03(AAA, Micro) 2 pieces] in the body regu- by holding in your hand. larly.
  • Page 89: Outline Of Operation Control By Microcomputer

    3.7 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER (1) Operation control function by remote controller Remote controller ◆ Operation section FAN SPEED button OPERATION MODE select button Each time the button is pushed, the Each time the button pushed, the indicator is switched over in turn. indicator is switched over in turn.
  • Page 90: Unit On/Off Button

    '09•SRK-DB-087D (2) Unit ON/OFF button (a) Operation (b) Details of operation Function Indoor temperature Fan speed Flap/Louver Timer Switch setting operation mode Cooling Thermal dry Unit ON/OFF button (3) Auto restart function Jumper wire (J170) (J170) Jumper wire (J171) (4) Custom cord switching procedure (a) Modifying the indoor printed circuit board (J171) (b) Modifying the wireless remote controller...
  • Page 91: Flap Control

    '09•SRK-DB-087D (5) Flap control (a) Flap (Flap stopped) (Swing) Angle of Flap from Horizontal Remote controller display COOL , DRY, FAN Approx. 10° Approx. 20° Approx. 30° Approx. 45° Approx. 60° (b) Swing In COOL, DRY, FAN operation Approx. 10° Approx.
  • Page 92: Outline Of Cooling Operation

    (7) Outline of cooling operation (a) Operation of major functional components in Cooling mode Cooling Thermostat ON Thermostat OFF Failure Compressor Indoor fan motor Outdoor fan motor (few minutes ON) (few minutes ON) (b) Fan speed switching Model SRK19CK(-3) SRK24CK(-3) Fan speed Auto Auto fan control...
  • Page 93: Protective Control Function

    (9) Protective control function (a) Frost prevention for indoor heat exchanger (During cooling or dehumidifying) Operating conditions Indoor heat exchanger temperature (Th2) is lower than 2.5ºC. 3 minutes elapsed after the start of operation. Detail of frost prevention operation Compressor Indoor fan Protects the fan tap just before frost prevention control.
  • Page 94: Maintenance Data

    3.8 MAINTENANCE DATA (1) Cautions (a) If you are disassembling and checking an air conditioner, be sure to turn off the power before beginning. When working on indoor units, let the unit sit for about 1 minute after turning off the power before you begin work. When working on an outdoor unit, there may be an electrical charge applied to the main circuit (electrolytic condenser), so begin work only after discharg- ing this electrical charge (to DC 10 V or lower).
  • Page 95: Troubleshooting Procedure (If The Air Conditioner Runs)

    (4) Troubleshooting procedure (If the air conditioner runs) below '09•SRK-DB-087D (5) Self-diagnosis table Outdoor Indoor unit display panel Description main PCB Cause Display (flashing) condition TIMER of trouble Red LED light light • Broken heat exchanger sensor When a heat exchanger sensor 1 wire disconnection is detected while operation is 1 time Stays Heat exchanger...
  • Page 96: Inspection Procedures Corresponding To Detail Of Trouble

    (6) Inspection procedures corresponding to detail of trouble Sensor error [Broken sensor wire, connector poor connection] Is connector connection good? Correct connection. Is sensor resistance value good? Replace sensor. Replace PCB. ◆ Sensor temperature characteristics (Room temp., indoor heat exchanger temp.,) (Broken wire) (Short circuit)
  • Page 97 '09•SRK-DB-087D Trouble of outdoor unit Insufficient refregerant amount, Broken compressor wire Service valve close . (7) Phenomenon observed after shortcircuit, wire breakage on sensor (a) Indoor unit Phenomenon Operation Sensor mode Shortcircuit Disconnected wire Room temperature Cooling sensor Heat exchanger Cooling sensor...
  • Page 98 '09•SRK-SM-087D (8) Checking the indoor electrical equipment (a) Indoor PCB check procedure Is there voltage between terminal Inspect power source blocks ① and ② ? (AC 220/230/240V) for outdoor unit. Replace fuse. Is the fuse burnt out? (3.15 A) Is the voltage between terminal Replace indoor PCB.
  • Page 99 '09•SRK-DB-087D (9) How to make sure of wireless remote controller The figare below shows the SRK series.
  • Page 100: Srk19Cks-3, 25Cks-3

    WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONER Split system, air cooled cooling only type 4. SRK19CKS-3, 25CKS-3 SRK19CKS-4, 25CKS-4...
  • Page 101 CONTENTS 4.1 SPECIFICATIONS .................. 4.2 EXTERIOR DIMENSIONS ..............(1) Indoor units ..................(2) Outdoor units ..................(3) Wireless remote controller ..............4.3 ELECTRICAL WIRING ................(1) Indoor units ..................(2) Outdoor units ..................4.4 PIPING SYSTEM ..................108 4.5 RANGE OF USAGE & LIMITATIONS ............
  • Page 102: Srk-T

    '10 • SRK-T-099 (7) Phenomenon observed after shortcircuit, wire breakage on sensor ..134 (8) Checking the indoor electrical equipment .......... 135 (9) How to make sure of wireless remote controller ......... 136 ■How to read the model name Example: SRK 19 C KS-3 Series code Cooling only type...
  • Page 103: Specifications

    4.1 SPECIFICATIONS SRK19CKS-3 (-4) Model Item Indoor unit SRK19CKS-3 (-4) Outdoor unit SRC19CKS-3 (-4) Cooling capacity (1) 5300 Power supply 1 Phase, 220/230V, 50Hz Power Cooling 1.45 consumption Running Cooling 6.8/6.5 current Operation data (1) Inrush current Cooling 3.66 Sound level dB(A) Hi : 47 Me : 42 Lo : 39 Noise...
  • Page 104 SRK25CKS-3 (-4) Model Indoor unit SRK25CKS-3 (-4) Outdoor unit SRC25CKS-3 (-4) Item Cooling capacity (1) 7210 Power supply 1 Phase, 220/230V, 50Hz Power Cooling 2.10 consumption Running Cooling 9.7/9.3 current Operation data (1) Inrush current Cooling 3.43 Sound level dB(A) Hi : 50 Me : 46 Lo : 43 Noise Cooling...
  • Page 105: Indoor Units

    1090 Symbol Content 43.5 Gas piping ø 15.88 (5/8") (Flare) Liquid piping ø 6.35 (1 / 4") (Flare) Hole on wall for right rear piping ( ø 65) Hole on wall for left rear piping ( ø 65) Drain hose VP16 Outlet for wiring Outlet for piping(on both side)...
  • Page 106: Outdoor Units

    (2) Outdoor unit Model SRC19CKS-3(-4) 286.4 Drain holes Unit: mm 203.1 136.9 Elogated hole (2-12 x16) Terminal block 34.6 Ground terminal Service valve (Liquid) ø6.35 (1/4'') Service valve (Gas) ø15.88 (5/8'') Model SRC25CKS-3(-4) Unit: mm Drain holes 2-ø15 25.8 29.8 87.9 Terminal block Service valve (Liquid)
  • Page 107: Wireless Remote Controller

    (3) Wireless remote controller Unit: mm 17.3...
  • Page 108: Electrical Wiring

    4.3 ELECTRICAL WIRING (1) Indoor units Models SRK19CKS-3(-4), 25CKS-3(-4) FLAP LOUVER LOUVER MOTOR MOTOR MOTOR 1 MOTOR 2 HEAT EXCHANGER 4 5 6 CONTROL S/N WHITE VARISTOR R/L BLACK FUSE 250V 3.15A YELLOW/GREEN PRINTED CIRCUIT BOARD 2/N DISPLAY WIRELESS TERMINAL BLOCK R-AMP TO OUTDOOR UNIT...
  • Page 109: Outdoor Units

    (2) Outdoor units Model SRC19CKS-3(-4) 52X1 52X4 52X3 FUSE 250V 3.15A Y/GN PRINTED CIRCUIT VARISTOR BOARD Y/GN COMPRESSOR MOTOR MARK COLOR MARK COLOR FAN MOTOR BLACK WHITE ELECTRIC EXPANSION VALVE(COIL) BLUE YELLOW HEAT EXCHANGER SENSOR ORANGE Y/GN YELLOW /GREEN OUTDOOR AIR TEMP. SENSOR DISCHARGE PIPE TEMP.
  • Page 110 Model SRC25CKS-3(-4) 11 9 52X1 52X4 52X5 52X3 FUSE 250V 3.15A Y/GN PRINTED CIRCUIT VARISTOR BOARD Y/GN COMPRESSOR MOTOR MARK COLOR MARK COLOR FAN MOTOR BLACK WHITE ELECTRIC EXPANSION VALVE(COIL) BLUE YELLOW HEAT EXCHANGER SENSOR ORANGE Y/GN YELLOW /GREEN OUTDOOR AIR TEMP. SENSOR DISCHARGE PIPE TEMP.
  • Page 111: Piping System

    4.4 PIPING SYSTEM Model SRK19CKS-3(-4) Indoor unit Outdoor unit Outdoor air Flare connecting Service valve temp. sensor (Gas) Piping (Gas) Check joint ø 15.88 Humidity sensor Room temp. Heat Discharge pipe Heat sensor exchanger temp. sensor exchanger sensor Heat Accumulator Compressor exchanger Heat exchanger...
  • Page 112: Range Of Usage & Limitations

    4.5 RANGE OF USAGE & LIMITATIONS Models All models Item Indoor return air temperature ( Upper, lower limits ) Refer to the selection chart Outdoor air temperature ( Upper, lower limits ) Refrigerant line ( one way ) length Max. 25m Max.
  • Page 113 (2) Correction of cooling capacity in relation to one way length of refrigerant piping Piping length [m] Cooling 0.99 0.975 0.965 0.95 How to obtain the cooling capacity SRK25CKS-3 7210 7030 SRK25CKS-3...
  • Page 114: Application Data

    4.6 APPLICATION DATA Safety precautions When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces. We recommend you to read this “SAFETY PRECAUTIONS”...
  • Page 115 CAUTION Use the circuit breaker with sufficient breaking capacity. Take care when carrying the unit by hand. If the breaker does not have sufficient breaking capacity, it can cause the unit If the unit weights more than 20kg, it must be carried by two or more per- malfunction and fire.
  • Page 116 Standard accessories Necessary tools for the installation work (Installation kit) Q'ty Accessories for indoor unit Plus headed driver (Phillips screwdriver) Installation board Knife ① (Attached to the rear of the indoor unit) ② Wireless remote control Tape measure ③ Remote contorol holder Hammer Tapping screws ④...
  • Page 117 Limitations for one way piping length and vertical height difference Total one way piping length ( ) Max. 25 m Vertical height difference (h) Max. 15 m Installation of indoor unit Installation of installation board INSTALLATOIN SPACE (INDOOR UNIT) (FRONT VIEW) Look for the inside wall structures (Intersediate support or pillar and firaly install the unit after level surface has been checked.)
  • Page 118 Preparation of indoor unit ① Mounting of connecting wires ⓐ Open the air inlet panel. ⓑ Remove the lid. ⓒ Remove the wiring clamp. ⓓ Connect the connecting wire securely to the terminal block. Use cable for interconnection wiring to avoid loosening of the wires.
  • Page 119 ⑤ Securing the indoor unit to the installation board Latch (2 locations) Installing steps Indoor unit 1.Hook the upper part of the indoor unit to the installation board. Installation board Installation board 2.The unit can be installed simply by gently push- Wall ing in the lower part.
  • Page 120 Installation of outdoor unit ① Make sure that the unit is stable in installation. Fix the Outdoor unit unit to stable base. When installing the unit at a higher place or where it ② could be toppled by strong winds, secure the unit firmly with foundation bolts, wire, etc.
  • Page 121 Air purge Compound pressure gauge Operation valve ① Tighten all flare nuts in the pipings both Pressure gauge indoor and outside wall so as not to Operation valve Gauge manifold cause leak. (two-way valve) -0.1MPa (Designed specifically for R22) (-76cmHg) ②...
  • Page 122 Installation of remote control switch Mounting method of battery Fixing to pillar or wall Uncover the remote control switch, and mount the bat- Conventionally, operate the wireless remote control teries [R03(AAA, Micro) 2 pieces] in the body regu- by holding in your hand. larly.
  • Page 123: Outline Of Operation Control By Microcomputer

    4.7 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER (1) Operation control function by remote controller Remote controller ◆ Operation section Unit display section TIMER HI POWER 3D AUTO ON/OFF RUN light (green) 3D AUTO light (green) Illuminates during 3D AUTO operation. Illuminates during operation.
  • Page 124: Unit On/Off Button

    '09•SRK-DB-087D (2) Unit ON/OFF button (a) Operation (b) Details of operation Function Indoor temperature Fan speed Flap/Louver Timer Switch setting operation mode Cooling Thermal dry Unit ON/OFF button (3) Auto restart function Jumper wire (J170) (J170) Jumper wire (J171) (4) Custom cord switching procedure (a) Modifying the indoor printed circuit board (J171) (b) Modifying the wireless remote controller...
  • Page 125: Flap And Louver Control

    '09•SRK-DB-087D (5) Flap and louver control (a) Flap (Flap stopped) (Swing) Angle of Flap from Horizontal Remote controller display Approx. 10° Approx. 20° Approx. 30° Approx. 45° Approx. 60° COOL , DRY, FAN (b) Louver (Louver stopped) (Swing) (Spot) (Wide) Angle of Louver Remote controller display...
  • Page 126: Auto Operation

    '09•SRK-DB-087D (6) 3D auto operation Air flow selection Operation mode AUTO < = Indoor temp. – Setting temp. >5°C Indoor temp. – Setting temp. 5°C At cooling HIGH POWER AUTO Cooling Flap Up/down Swing Louver Wide (Fixed) Cooling Flap Horizontal blowing (Fixed) Louver Left/right Swing Cooling...
  • Page 127: Installation Location Setting

    '09•SRK-DB-087D (7) Timer operation (a) Comfortable timer setting (ON timer) (b) Sleep timer operation (c) OFF timer operation (8) Installation location setting (a) Setting If the air conditioning unit is running, press the ON/OFF button to stop. Press the AIR FLOW (UP/DOWN) button and the AIR FLOW (LEFT/RIGHT) button together for 5 seconds...
  • Page 128: Outline Of Automatic Operation

    (9) Outline of cooling operation (a) Operation of major functional components in Cooling mode Cooling Thermostat ON Thermostat OFF Failure Compressor Indoor fan motor Outdoor fan motor (few minutes ON) (few minutes ON) (b) Fan speed switching Model SRK19CKS SRK25CKS Fan speed Auto Auto fan control...
  • Page 129: Protective Control Function

    (11) Protective control function (a) Frost prevention for indoor heat exchanger (During cooling or dehumidifying) Operating conditions Indoor heat exchanger temperature (Th2) is lower than 2.5ºC. 3 minutes elapsed after the start of operation. Detail of frost prevention operation Compressor Indoor fan Protects the fan tap just before frost prevention control.
  • Page 130 Compressor overheat protection If the discharge pipe temperature (sensed by Th6) exceeds the set temperature value, the compressor stops. If the temperature is 95ºC or lower after a 3-minute delay, it starts again, but if this function is reactivated again within 60 minutes, it results in an abnormal stop. (RUN light : ON, TIMER light : 5 time flash) Operation possible Abnormal stop...
  • Page 131: Maintenance Data

    4.8 MAINTENANCE DATA (1) Cautions (a) If you are disassembling and checking an air conditioner, be sure to turn off the power before beginning. When working on indoor units, let the unit sit for about 1 minute after turning off the power before you begin work. When working on an outdoor unit, there may be an electrical charge applied to the main circuit (electrolytic condenser), so begin work only after discharg- ing this electrical charge (to DC 10 V or lower).
  • Page 132 (4) Troubleshooting procedure (If the air conditioner runs) 130.
  • Page 133 '09•SRK-DB-087D (5) Self-diagnosis table Indoor unit display panel Description Cause Display (flashing) condition TIMER of trouble light light • Broken heat exchanger sensor When a heat exchanger sensor 1 wire disconnection is detected while 1 time operation is stopped. (If a temperature of –28ºC or lower is detected for Heat exchanger 1 wire, poor connector sensor 1 error...
  • Page 134: Inspection Procedures Corresponding To Detail Of Trouble

    (6) Inspection procedures corresponding to detail of trouble Sensor error [Broken sensor wire, connector poor connection] Is connector connection good? Correct connection. Is sensor resistance value good? Replace sensor. Replace PCB. ◆ Sensor temperature characteristics ◆ Discharge pipe sensor temperature characteristics (Room temp., indoor heat exchanger temp., outdoor heat exchanger temp., outdoor air temp.)
  • Page 135 '09•SRK-DB-087D Over heat of compressor Gas shortage, defective discharge pipe sensor 131) main Error of signal transmission Wiring error including power cable, defective indoor/ outdoor PCB ② ③ indoor ② ③ 220/230V indoor ① ② outdoor sub...
  • Page 136 '09•SRK-DB-087D Trouble of outdoor unit Insufficient refregerant amount, Faulty power transistor, Broken compressor wire Service valve close, Defective EEV, Defective outdoor PCB ◆ main   main ....
  • Page 137 See pages 53. (7) Phenomenon observed after shortcircuit, wire breakage on sensor (a) Indoor unit Phenomenon Operation Sensor mode Shortcircuit Disconnected wire Room temperature Cooling sensor Heat exchanger Cooling sensor Humidity sensor Cooling ■ Humidity sensor operation Failure mode Control input circuit resding Air conditioning system operation ①...
  • Page 138 Heat exchanger Cooling sensor Ourdoor air Cooling temperature sensor Discharge pipe All modes sensor (8) Checking the indoor electrical equipment (a) Indoor PCB check procedure Is there voltage between terminal Inspect power source blocks ① and ② ? (AC 220/230V ) for outdoor unit.
  • Page 139 Operation SW ON Measure in this section (9) How to make sure of wireless remote controller The figare below shows the SRK series.
  • Page 140 PARTS LIST INDOOR UNIT SRK06CJ , SRK09CJ , SRK12CJ SRK06CJ-3 , SRK09CJ-3 , SRK12CJ-3 SRK10CJV-3 , SRK13CJV-3 SRK10CJV-4 , SRK13CJV-4 SRK19CK , SRK24CK SRK19CK-3 , SRK24CK-3 SRK19CKS-3 , SRK25CKS-3 SRK19CKS-4 , SRK25CKS-4 OUTDOOR UNIT SRC06CJ , SRC09CJ , SRC12CJ SRC06CJ-3 , SRC09CJ-3 , SRC12CJ-3...
  • Page 141 CRAE0210...
  • Page 142 SRK06CJ / SRK06CJ-3 RWA002F062W / RWA002F062AA END ITEM NO. : Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-5 RMA102A100A PANEL ASSY,FRONT 1 RKX122A300L PANEL,FRONT 2 RMA435A100 PANEL, AIR INLET 5 RKX133A300 PLATE,ORNAMENT 6-19 RKX435A302A GRILLE ASSY,AIR OUT...
  • Page 143 CRAE0228...
  • Page 144 SRK06CJ / SRK06CJ-3 RWA002F062W / RWA002F062AA END ITEM NO. : Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-6 RKX301A017 HEAT EXCH ASSY (AIR) 2 RKX129A016 BRACKET ASSY (L) 6 RKX141A001 PLATE ASSY, BAFFLE 7 RKX142A001...
  • Page 145 CRAE0210...
  • Page 146 SRK09CJ / SRK09CJ-3 END ITEM NO. : RWA002F062Y / RWA002F062AB Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-5 RMA102A100A PANEL ASSY,FRONT 1 RKX122A300L PANEL,FRONT 2 RMA435A100 PANEL, AIR INLET 5 RKX133A300 PLATE,ORNAMENT 6-19 RKX435A302A GRILLE ASSY,AIR OUT 6 RKX435A303 GRILLE,AIR OUTLET 9-10 RKX436A006...
  • Page 147 CRAE0228...
  • Page 148 SRK09CJ / SRK09CJ-3 RWA002F062Y / RWA002F062AB END ITEM NO. : Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-6 RKX301A015 HEAT EXCH ASSY (AIR) 2 RKX129A016 BRACKET ASSY (L) 6 RKX141A001 PLATE ASSY, BAFFLE 7 RKX142A001 BOX, CONTROL 10 SSA564A132 FUSE (CURRENT)
  • Page 149 CRAE0210...
  • Page 150 SRK12CJ / SRK12CJ-3 END ITEM NO. : RWA002F062Z / RWA002F062AC Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-5 RMA102A100A PANEL ASSY,FRONT 1 RKX122A300L PANEL,FRONT 2 RMA435A100 PANEL, AIR INLET 5 RKX133A300 PLATE,ORNAMENT 6-19 RKX435A302A GRILLE ASSY,AIR OUT 6 RKX435A303 GRILLE,AIR OUTLET 9-10 RKX436A006...
  • Page 151 CRAE0227...
  • Page 152 SRK12CJ / SRK12CJ-3 END ITEM NO. : RWA002F062Z / RWA002F062AC Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-8 RKX301A007J HEAT EXCH ASSY (AIR) 2 RKX315D005 HEADER ASSY 3 RKX129A016 BRACKET ASSY(L) 4 RKX315A004 DISTRIBUTOR ASSY 8 RKX129A001B PLATE ASSY, BAFFLE 9 RKX142A001...
  • Page 153 24 15 CRAE0213...
  • Page 154 SRK10CJV-3 / SRK10CJV-4 END ITEM NO. : RWA002F065G / RWA002F065D Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-6 RMA102A100B PANEL ASSY,FRONT 1 RKX122A300M PANEL,FRONT 2 RMA435A100A PANEL, AIR INLET 5 RKX129A014 HOLDER,FILTER 6 RKX133A300 PLATE,ORNAMENT 7-27 RKX435A302 GRILLE ASSY,AIR OUT 7 RKX435A303...
  • Page 155 CRAE0214...
  • Page 156 SRK10CJV-3 / SRK10CJV-4 END ITEM NO. : RWA002F065G / RWA002F065D Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-4 RKX301A007K HEAT EXCH ASSY (AIR) 2 RKX315D005 HEADER ASSY 3 RKX129A016 BRACKET ASSY (L) 4 RKX315A004 DISTRIBUTOR ASSY 8 RKX129A001B PLATE ASSY, BAFFLE 9 RKX142A001...
  • Page 157 24 15 CRAE0213...
  • Page 158 SRK13CJV-3 / SRK13CJV-4 END ITEM NO. : RWA002F065H / RWA002F065F Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-6 RMA102A100B PANEL ASSY,FRONT 1 RKX122A300M PANEL,FRONT 2 RMA435A100A PANEL, AIR INLET 5 RKX129A014 HOLDER,FILTER 6 RKX133A300 PLATE,ORNAMENT 7-27 RKX435A302C GRILLE ASSY,AIR OUT 7 RKX435A303...
  • Page 159 CRAE0214...
  • Page 160 SRK13CJV-3 / SRK13CJV-4 END ITEM NO. : RWA002F065H / RWA002F065F Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-4 RKX301A007L HEAT EXCH ASSY (AIR) 2 RKX315D005 HEADER ASSY 3 RKX129A016 BRACKET ASSY (L) 4 RKX315A004 DISTRIBUTOR ASSY 8 RKX129A001B PLATE ASSY, BAFFLE 9 RKX142A001...
  • Page 161 CRAE0242...
  • Page 162 SRK19CK / SRK19CK-3 END ITEM NO. : RMA002F018 / RMA002F018B Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 1-6 RKW102A400C PANEL ASSY,FRONT 1 RKW122A400B PANEL,FRONT 2 RKW435A401B PANEL ASSY AIR IN 5 RKW133A400B PLATE,ORNAMENT 6 RKW011G400B LABEL,WIRING 7-22 RKW435A202H GRILLE ASSY,AIR OUT 7 RKW435A203B GRILLE,AIR OUTLET...
  • Page 163 CRAE0243...
  • Page 164 SRK19CK / SRK19CK-3 END ITEM NO. : RMA002F018 / RMA002F018B Recommendable Purchased Q'ty Part No. Note 1000 1-7 RMA301A003A HEAT EXCH ASSY(AIR) 1 RMA301A004A HEAT EXCH ASSY(AIR) 2 RMA315D004 HEADER ASSY 3 RKW129A409 BRACKET ASSY(L) 4 RMA315A004 DISTRIBUTOR ASSY q i l 8 RKW129A411 HOLDER ASSY,FILTER 9 RKW142A401...
  • Page 165 CRAE0242...
  • Page 166 SRK24CK / SRK24CK-3 END ITEM NO. : RMA002F018A / RMA002F018C Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 1-6 RKW102A400C PANEL ASSY,FRONT 1 RKW122A400B PANEL,FRONT 2 RKW435A401B PANEL ASSY AIR IN 5 RKW133A400B PLATE,ORNAMENT 6 RKW011G400B LABEL,WIRING 7-22 RKW435A202H GRILLE ASSY,AIR OUT 7 RKW435A203B GRILLE,AIR OUTLET...
  • Page 167 CRAE0243...
  • Page 168 SRK24CK / SRK24CK-3 END ITEM NO. : RMA002F018A / RMA002F018C Recommendable Purchased Q'ty Part No. Note 1000 1-7 RMA301A003A HEAT EXCH ASSY(AIR) 1 RMA301A004A HEAT EXCH ASSY(AIR) 2 RMA315D004 HEADER ASSY 3 RKW129A409 BRACKET ASSY(L) 4 RMA315A004 DISTRIBUTOR ASSY q i l 8 RKW129A411 HOLDER ASSY,FILTER 9 RKW142A401...
  • Page 169 CRAE0240...
  • Page 170 SRK19CKS-3 / SRK19CKS-4 END ITEM NO. : RMA002F018L / RMA002F018N Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 1-6 RKW102A400D PANEL ASSY,FRONT 1 RKW122A400C PANEL,FRONT 2 RKW435A401C PANEL ASSY AIR IN 5 RKW133A401 PLATE,ORNAMENT 6 RKW011G400C LABEL,WIRING 7-31 RKW435A202G GRILLE ASSY,AIR OUT 7 RKW435A203B GRILLE,AIR OUTLET...
  • Page 171 SRK19CKS-3 / SRK19CKS-4 END ITEM NO. : RMA002F018L / RMA002F018N Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 39 PHA129A302A COVER ASSY (PIPE) 42-43 RKW132A403 LID ASSY (TERMINAL) 43 RSA011H027 LABEL, NOTICE 44 RKW129A405 COVER PIPE 45 RKW129A213 HOLDER, FILTER...
  • Page 172 MEMO...
  • Page 173 CRAE0244...
  • Page 174 SRK19CKS-3 / SRK19CKS-4 END ITEM NO. : RMA002F018L / RMA002F018N Recommendable Purchased Q'ty Part No. Note 1000 1-8 RMA301A003A HEAT EXCH ASSY(AIR) 1 RMA301A004A HEAT EXCH ASSY(AIR) 3 RKW129A410 BRACKET ASSY(L) 4 RMA315A004 DISTRIBUTOR ASSY q i l 8 RKW129A411 HOLDER ASSY,FILTER 9 RKW142A401 BOX ASSY,CONTROL(L)
  • Page 175 CRAE0240...
  • Page 176 SRK25CKS-3 / SRK25CKS-4 END ITEM NO. : RMA002F018M / RMA002F018P Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 1-6 RKW102A400D PANEL ASSY,FRONT 1 RKW122A400C PANEL,FRONT 2 RKW435A401C PANEL ASSY AIR IN 5 RKW133A401 PLATE,ORNAMENT 6 RKW011G400C LABEL,WIRING 7-31 RKW435A202G GRILLE ASSY,AIR OUT 7 RKW435A203B GRILLE,AIR OUTLET...
  • Page 177 SRK25CKS-3 / SRK25CKS-4 END ITEM NO. : RMA002F018M / RMA002F018P Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 39 PHA129A302A COVER ASSY (PIPE) 42-43 RKW132A403 LID ASSY (TERMINAL) 43 RSA011H027 LABEL, NOTICE 44 RKW129A405 COVER PIPE 45 RKW129A213 HOLDER, FILTER...
  • Page 178 MEMO...
  • Page 179 CRAE0244...
  • Page 180 SRK25CKS-3 / SRK25CKS-4 END ITEM NO. : RMA002F018M / RMA002F018P Recommendable Purchased Q'ty Part No. Note 1000 1-8 RMA301A001A HEAT EXCH ASSY(AIR) 1 RMA301A002A HEAT EXCH ASSY(AIR) 3 RKW129A410 BRACKET ASSY(L) 4 RKW315A400 DISTRIBUTOR ASSY q i l 8 RKW129A411 HOLDER ASSY,FILTER 9 RKW142A401 BOX ASSY,CONTROL(L)
  • Page 181 CRBE0161...
  • Page 182 SRC06CJ / SRC06CJ-3 END ITEM NO. : RWC003F073D / RWC003F073G Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1 RCK122A502B PANEL,FRONT 2 RCK123A500A PANEL ASSY,SIDE(R) 3 RMC123A001 PANEL ASSY,SIDE(L) 4 RCK132A501 PANEL,SERVICE 5 RCK435A501B GRILLE,AIR OUTLET 9 RCK141A506 PLATE, BAFFLE 10 SSA431B168...
  • Page 183 CRBE0279...
  • Page 184 SRC06CJ / SRC06CJ-3 END ITEM NO. : RWC003F073D / RWC003F073G Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-3 RMC301A002 HEAT EXCH ASSY(AIR) 4-5 RCK304A508 PIPING ASSY 4 RCK315B511 CAPILLARY 5 RCK315B510 CAPILLARY ,SUB 6 RCK116A002 BRACKET (VALVE) 7 RCK381A501 VALVE,SERVICE(1/4")
  • Page 185 CRBE0161...
  • Page 186 SRC09CJ / SRC09CJ-3 END ITEM NO. : RWC003F073F / RWC003F073H Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1 RCK122A502B PANEL,FRONT 2 RCK123A500A PANEL ASSY,SIDE(R) 3 RMC123A001 PANEL ASSY,SIDE(L) 4 RCK132A501 PANEL,SERVICE 5 RCK435A501B GRILLE,AIR OUTLET 9 RCK141A506 PLATE, BAFFLE 10 SSA431B168...
  • Page 187 CRBE0279...
  • Page 188 SRC09CJ / SRC09CJ-3 END ITEM NO. : RWC003F073F / RWC003F073H Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-3 RMC301A002 HEAT EXCH ASSY(AIR) 4-5 RCK304A507 PIPING ASSY 4 RCK315B509 CAPILLARY 5 RCK315B510 CAPILLARY ,SUB 6 RCK116A002 BRACKET(VALVE) 7 RCK381A501 VALVE,SERVICE(1/4")
  • Page 189 CRBE0290...
  • Page 190 SRC12CJ / SRC12CJ-3 END ITEM NO. : RWC003F077G / RWC003F077K Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1 RCV122A001 PANEL, FRONT 2 RCV123A001 PANEL,SIDE(R) 3 RCV124A500A PANEL ASSY, TOP 4 RCV132A003 COVER ASSY,SERVICE 5 RCV435A001A GRILL,AIR OUTLET 7 SSA913A034F SCREW, TAP...
  • Page 191 CRBE0288...
  • Page 192 SRC12CJ / SRC12CJ-3 END ITEM NO. : RWC003F077G / RWC003F077K Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-3 RMC301A004 HEAT EXCH ASSY (AIR) 4-5 RMC304A015 PIPING ASSY(CAPI) 6 RCS116A004 BRACKET(VALVE) 7 RCS381A001 VALVE,SERVICE(1/4" ) 8 RCS381A003 VALVE,SERVICE(1/2"...
  • Page 193 CRBE0290...
  • Page 194 SRC10CJV-3 / SRC10CJV-4 END ITEM NO. : RWC003F077H / RWC003F077D Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1 RCV122A001 PANEL FRONT 2 RCV123A001 PANEL SIDE(R) 3 RCV124A500A PANEL ASSY, TOP 4 RCV132A003 COVER ASSY SERVICE 5 RCV435A001A GRILLE, AIR OUTLET 7 SSA913A034F...
  • Page 195 CRBE0288...
  • Page 196 SRC10CJV-3 / SRC10CJV-4 END ITEM NO. : RWC003F077H / RWC003F077D Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-3 RMC301A004 HEAT EXCH ASSY (AIR) 4-5 RMC304A016 PIPING ASSY 5 RMC315B011 CAPILLARY,SUB 6 RCS116A004 BRACKET(VALVE) 7 RCS381A001 VALVE,SERVICE(1/4"...
  • Page 197 CRBE0290...
  • Page 198 SRC13CJV-3 / SRC13CJV-4 END ITEM NO. : RWC003F077J / RWC003F077F Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1 RCV122A001 PANEL, FRONT 2 RCV123A001 PANEL, SIDE(R) 3 RCV124A500A PANEL ASSY,TOP 4 RCV132A003 COVER ASSY, SERVICE 5 RCV435A001A GRILLE, AIR OUTLET 7 SSA913A034F SCREW, TAP...
  • Page 199 CRBE0287...
  • Page 200 SRC13CJV-3 / SRC13CJV-4 END ITEM NO. : RWC003F077J / RWC003F077F Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 100 500 1000 1-5 RMC301A006 HEAT EXCH ASSY (AIR) 6-7 RMC304A014 PIPING ASSY 8 RCS116A004 BRACKET(VALVE) 9 RCS381A001 VALVE,SERVICE(1/4" ) 2 LIQ. 10 RCS381A003 VALVE,SERVICE(1/2"...
  • Page 201 CRBE0313...
  • Page 202 SRC19CK / SRC19CK-3 END ITEM NO. : RWC003F052K / RWC003F052L Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 1 RWC122A004 PANEL ASSY,FRONT 2 RWC123A005J PANEL ASSY,SIDE(R) 3 RWC123A008 PANEL SIDE(L) 4 RWC124A004F PANEL,ASSY TOP 5 RWC132A007 PANEL ASSY SERVICE 6 RWC435A002 GRILLE ASSY,AIR OUTLET 8 RWC116A041...
  • Page 203 CRBE0312...
  • Page 204 SRC19CK / SRC19CK-3 END ITEM NO. : RWC003F052K / RWC003F052L Recommendable Purchased Q'ty Part No. Part Name Note 1000 1-3 RMC301A018 HEAT EXCH ASSY(AIR) 1 RMC311A005 HEAT EXCH(AIR) 4 RCK116A002 BRACKET(VALVE) 5 RWC381A018A VALVE,SERVICE(1/4" ) 2 LIQ. 6 RWC381A017A VALVE,SERVICE(5/8") 2 GAS 7 RMC304A021 PIPING ASSY (EXPAN)
  • Page 205 CRBE0314...
  • Page 206 SRC24CK / SRC24CK-3 END ITEM NO. : RWC003F050H / RWC003F050J Recommendable Purchased Q'ty Part NO. Part Name RE.Q Note 1000 1 RCR122A001 PANEL ASSY,FRONT 2 RCR125A002G PANEL ASSY,REAR 4 RCR124A002J PANEL,ASSY TOP 5 RCR122A004A PANEL ASSY SERVICE 7 RCR115A002A SUPPORT,CORNER 8 RMC435A001 GRILLE ASSY,AIR OUT 9 RCR132A004B...
  • Page 207 CRBE0312...
  • Page 208 SRC24CK / SRC24CK-3 END ITEM NO. : RWC003F050H / RWC003F050J Recommendable Purchased Q'ty Part No. Part Name Note 1000 1-3 RMC301A020 HEAT EXCH ASSY(AIR) 1 RMC311A006 HEAT EXCH(AIR) 4 RCR116A003 BRACKET(VALVE) 5 RCR381A003A VALVE,SERVICE(1/4" ) 2 LIQ. 6 RCR381A004A VALVE,SERVICE(5/8") 2 GAS 7 RMC304A022 PIPING ASSY (EXPAN)
  • Page 209 CRBE0221...
  • Page 210 SRC19CKS-3 / SRC19CKS-4 END ITEM NO. : RWC003F070D / RWC003F070F Recommendable Purchased Q'ty Part NO. Part Name RE.Q Note 1000 1 RWC122A004 PANEL ASSY,FRONT 2 RWC123A005F PANEL ASSY,SIDE(R) 3 RWC123A008 PANEL SIDE(L) 4 RWC124A004 PANEL,ASSY TOP 5 RWC132A007 PANEL ASSY SERVICE 6 RWC435A002 GRILLE ASSY,AIR OUTLET 8 RWC131A004...
  • Page 211 21 28 21 27 18 19 20 CRBE0263...
  • Page 212 SRC19CKS-3 / SRC19CKS-4 END ITEM NO. : RWC003F070D / RWC003F070F Recommendable Purchased Q'ty Part NO. Part Name RE.Q Note 1000 1-3 RWC301A024 HEAT EXCH ASSY(AIR) 1 RWC311A011 HEAT EXCH(AIR) 4 RCK116A002 BRACKET(VALVE) 5 RWC381A018A VALVE,SERVICE(1/4" ) 2 LIQ. 6 RWC381A017A VALVE,SERVICE(5/8") 2 GAS 7-9 RWC304A137 PIPING ASSY (EXPAN)
  • Page 213 CRBE0256...
  • Page 214 SRC25CKS-3 / SRC25CKS-4 END ITEM NO. : RWC003F071C / RWC003F071D Recommendable Purchased Q'ty Part NO. Part Name RE.Q Note 1000 1 RCR122A001 PANEL ASSY, FRONT 2 RCR125A002C PANEL ASSY, REAR 4 RCR124A002A PANEL,ASSY TOP 5 RCR122A004A PANEL ASSY,SERVICE 7 RCR115A001 SUPPORT,CORNER 8 RCR435A001 GRILLE,AIR OUTLET...
  • Page 215 22 29 22 28 19 20 21 CRBE0264...
  • Page 216 SRC25CKS-3 / SRC25CKS-4 END ITEM NO. : RWC003F071C / RWC003F071D Recommendable Purchased Q'ty Part NO. Part Name RE.Q Note 1000 1-3 RCR301A002-SP HEAT EXCH ASSY(AIR) 1 RCR311A002 HEAT EXCH(AIR) 4 RCR116A003 BRACKET(VALVE) 5 RCR381A003A VALVE,SERVICE(1/4" ) 2 LIQ. 6 RCR381A004A VALVE,SERVICE(5/8") 2 GAS 7-9 RCR304A011A...
  • Page 217 RESIDENTIAL AIR-CONDITIONING TECHNICAL MANUAL & PARTS LIST...