6 COMMISSIONING

6.16 RECLOSER (79)

Set protection element 79 as follows:
Set the relay to trip by 50PH, and configure the signals necessary to test the 79 element:
Configure one output as AR RECLOSE
Configure the AR INITIATE signal with the 50PH trip
Configure the AR LEVEL BLOCK signal with a digital input
Configure the AR CONDS INPUT with the digital signal desired
Connect a latching relay simulating the breaker managed by the F650 unit.
Once the relay is set, close the breaker and wait for 5 seconds.
After this time, the recloser is ready to initiate the reclosing cycle.
Command a 50PH trip and verify that the breaker opens and the relay recloses in 2.1 seconds.
Command a 50PH trip and verify that the breaker opens and the relay recloses in 4.1 seconds.
Command a 50PH trip and verify that the breaker opens and the relay recloses in 6.1 seconds.
Command a 50PH trip and verify that the breaker opens and the relay recloses in 8.1 seconds.
Command a 50PH trip and verify that the breaker opens and the recloser passes to Lockout.
Verify the correct operation of programmed outputs
Tripping times must be within the following values:
GEK-113000T
RECLOSER
Function
Max Number Shots
Dead Time 1
Dead Time 2
Dead Time 3
Dead Time 4
Reclaim Time
Cond. Permission
Hold Time
Reset Time
50PH SETTINGS
Function
Input
Pickup Level
Trip Delay
Reset Delay

RECLOSING CYCLE

Nº shot
Expected time
1
2.1 sec
2
4.1 sec
3
6.1 sec
4
8.1 sec
F650 Digital Bay Controller
ENABLED
4
2.10 sec
4.10 sec
6.10 sec
8.10 sec
3.00 sec
ENABLED
7.00 sec
5.00 sec
ENABLED
RMS
3 A
0.00 s
0.00 s
Admissible time
[1.8 – 2.3]
[3.8 – 4.3]
[5.8 – 6.3]
[7.8 – 8.3]