3.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE 3 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
3
Calibration (Serial or Ethernet connection): Allows retrieving the unit calibration settings and storing them in a file (with
extension *.cal). For reading or storing the calibration settings in the relay go to "Communications>Calibration>Get
or Set calibration settings" and select the intended calibration file. The calibration retrieval process is necessary to
be performed before updating the unit operative system, when the operating system is updated all the data in the relay
is deleted, including the factory calibration settings. When only the firmware is updated (for versions higher than 1.50),
the calibration settings are automatically saved in the relay.
Upgrade firmware version (Ethernet connection): Go to "Communications>Upgrade firmware version", this menu
allows the user to update the firmware version of the relay through Ethernet communication. Firmware is related to the
relay internal program, designed by GE Multilin, which performs the protection and control functions, and which is run
by the relay main microprocessor.
Upgrade operating system (Serial and Ethernet connection): Go to "Communications>Upgrade operating system".
This option allows the user to update the relay operative system. The operative system or OS is the program that
supports the firmware and provides auxiliary services for access to electronic devices included in the relay.
IMPORTANT NOTE:
3-28
Figure 3–12: COMMUNICATION TROUBLESHOOTING SCREEN
READ CAREFULLY THE FLASH MEMORY UPDATE PROCEDURE DESCRIBED IN
SECTION 5 AND CLOSE ALL THE RUNNING APPLICATIONS BEFORE
PERFORMING FIRMWARE AND OPERATIVE SYSTEM UPDATING PROCESS
Before updating firmware check that the firmware version that is going to be updated
match the operative system version of the relay. Otherwise it is necessary to update the
operative system before proceeding to update the firmware. Other combinations of
firmware and operative system different from the listed in section 5 will not be operative
The operative system version is available in the logotype main screen in HMI; it is the
number between brackets in the first line, e.g. F650 1.70 (2.35). The operative system
version is 2.35