6-2.Outdoor Unit - Toshiba HWS-P805XWHM3-E(TR) Service Manual

Air to water heat pump
Table of Contents

Advertisement

6-2. Outdoor unit
HWS-P805HR-E, P1105HR-E
No.
Component name
Compressor
1
2
Outdoor fan motor (x2)
Reactor (x2)
3
4-way valve coil
4
5
Pulse motor valve (PMV) coil
Compressor case thermostat
6
7
PC board
8
High pressure sensor
2-way valve coil
9
10
High pressure switch
HWS-P805H8R-E, P1105H8R-E, P1405H8R-E
No.
Component name
Compressor
1
Outdoor fan motor (x2)
2
3
Reactor
Reactor
4
5
4-way valve coil
Pulse motor valve (PMV) coil
6
PC board (Compressor)
7
8
PC board (Fan motor drive)
PC board (Control)
9
PC board (Noise filter)
10
11
High pressure switch
Compressor case thermostat
12
Relay
13
14
2-way valve coil
Type name
DA422A3F-26M
ICF-280-A100-1
Output 100 W
CH-44
1.4 mH, 25 A
STF-H01AP1874A1
AC220 - 230 V full-wave rectifier input, alive time 10 sec or less
UKV-A038
DC12 V
US-622KXTMQO-SS
OFF = 125 ± 4 °C, ON = 90 ± 5 °C
MCC-1571
Input 1Ø, AC220 - 230 V ± 10%, 50/60 Hz
NSK-BH042D-430
0 ~ 4.15 MPa
VPV-MOAJ510B0
AC220 - 240 V
ACB-4UB154W
OFF = 4.15 + 0, -0.15 MPa
Type name
DA422A3F-27M
ICF-280-A100-1
Output 100 W
CH-78
4.2 mH, 16 A
CH-68
18 mH, 5 A
STF-H01AJ1736A1
AC220 - 230 V
UKV-A038
DC12 V
MCC-1698
MCC-1597
MCC-1675
MCC-1600
ACB-4UB154W
OFF = 4.15 +0, - 0.15 MPa
US-622
OFF = 125 ± 4 °C, ON = 90 ± 5 °C
EL200/240 A2-F()
Contact = AC480V, 20 A
TEV-SMOAJ2170A1
AC220 - 240 V
28
Rating
Rating

Advertisement

Table of Contents
loading