Toshiba HWS-P805XWHM3-E(TR) Service Manual page 154

Air to water heat pump
Table of Contents

Advertisement

<How to set Frost protection operation end time>
• This function is available only for the header remote controller.
1
Press the [
] / [
MENU screen.
2
Press the [
] button for 4 seconds or longer to enter the setting mode. The function code setting
screen appears.
FC No. 12: End days (Range: 0~20, Default: 0)
13: End times (Range: 0~23, Default: 0)
ex)
Code No. 12: 05
13: 13 = 5 days 13 hours
3
Press the [
] / [
to set the value.
4
Press the [
] button. The set value is registered.
] button to select "Frost protection" on the
] button to select FC number or Data, then press the [
153
MENU(2/2)
Anti bacteria
Frost protection
Setting
Information
SET
] / [
] button
Frost protection
FC No.
Data
FIX