15. Floor drying
• This function is available only for the header remote controller.
• This function is used for drying concrete etc.
• Service personnel must operate the unit after setting the related function code.
• Operation is not started unless All the related function codes are set.
• Refer to the following for the settings of the related items. Please setup on the responsibility for an installer. An
unsuitable setup may cause a crack of concrete etc.
• When the operation starts, the unit operates as follows.
1
Press the [
] button and the [
seconds or longer on the top screen to display the "FIELD SETTING
MENU".
2
Press the [
] / [
FIELD SETTING MENU, then press the [
longer.
FC:14 setting start and End temperature [20-55°C]
FC:15 setting Max temperature [20-55°C]
FC:16 continuation days for every step up to Max temperature [1-7 days]
FC:17 temperature difference for every step up to Max temperature [1-10 K]
FC:18 continuation days for every step down to End temperature [1-7 days]
FC:19 temperature difference for every step down to End temperature [1-10 K]
FC:1A Continuation days in Max temperature [1-30 days]
3
Press the [
] / [
the [
] / [
4
Press the [
] button. The set value is registered.
] button at same time for 4
] button to select "Floor drying" on the
setting temperature
] button to select FC number or Data, then press
] button to set the value.
] button for 4 seconds or
°C
50
49
48
47
46
45
FC:15
44
43
42
41
40
39
38
37
36
35
34
FC:17
33
32
FC:16
31
FC:14
30
29
28
27
26
25
24
:
:
1
0
0
1
2
3
4
5
6
7
162
FIELD SETTING MENU(1/2)
Test mode
Floor drying
Forced defrosting
Information input
Alarm history
FC:1A
FC:19
FC:18
8
9
10
11
12
13
14
15
16
17
lapsed days
total days
Floor drying
FC No.
FIX
SET
18
19
20
21
22 Day
Data