Pre-Installation; Receiving; Receiving Checklist; Responsibilities - Trane Technologies IntelliPak Signature SCWF Installation, Operation And Maintenance Manual

Commercial self-contained
Table of Contents

Advertisement

Pre-Installation

Receiving

Receiving Checklist

Complete the following checklist immediately after
receiving unit shipment to detect possible shipping
damage:
Inspect individual cartons before accepting. Check for
rattles, bent carton corners, or other visible indications
of shipping damage.
If a unit appears damaged, inspect it immediately
before accepting the shipment. Make specific notations
concerning the damage on the freight bill. Do not refuse
delivery.
Inspect the unit for concealed damage before it is
stored and as soon as possible after delivery. Report
concealed damage to the freight line within the allotted
time after delivery. Check with the carrier for their
allotted time to submit a claim.
Do not move damaged material from the receiving
location. It is the receiver's responsibility to provide
reasonable evidence that concealed damage did not
occur after delivery.
Do not continue unpacking the shipment if it appears
damaged. Retain all internal packing, cartons, and
crate. Take photos of damaged material if possible.
Notify the carrier of the damage immediately by phone
and mail. Request an immediate joint inspection of the
damage by the carrier and consignee.
Note: Notify your Trane representative of the damage and
arrange for repair. Have the carrier inspect the
damage before making any repairs to the unit.
Ship-Separate Accessories
Field-installed sensors ship separately inside main control
panel of the unit. Extra filters, sheaves, and belts ship in
the fan motor section of the unit. Condenser plugs, spring
isolators, and Iso-pads ship stored in the bottom left side of
the unit.
Contractor Installation Responsibilities
Complete the following checklist before beginning final unit
installation:
Verify the unit size and tagging with the unit nameplate.
Make certain the floor or foundation is level, solid, and
sufficient to support the unit and accessory weights.
Level or repair the floor before positioning the unit if
necessary.
Allow minimum recommended clearances for routine
maintenance and service. Allow space at end of the
unit for shaft removal and servicing. Refer to the unit
submittals for dimensions. See also the "Service
Clearances" section in the Dimensional Data chapter.
18
Allow three fan diameters above the unit for the
discharge ductwork. Return air enters the rear of the
unit and conditioned supply air discharges through the
top.
Electrical connection knockouts are on the top, left side
of the unit.
Allow adequate space for piping access and panel
removal. Condenser water piping, refrigerant piping,
and condensate drain connections are on the lower left
end panel.
Note: Unit height and connection locations will change
if using vibration isolators. The unit height may
increase up to 5-7/8" with spring type isolators.
Electrical supply power must meet specific balance and
voltage requirements as described in chapter
"Electrical Installation".
The installer is responsible for providing a condenser
main, standby water pump, cooling tower, pressure
gauges, strainers, and all components for waterside
piping. See
"Water Piping," p. 34
recommendations.

Unit Inspection

To protect against loss due to damage incurred in transit,
perform inspection immediately upon receipt of the unit.
Exterior Inspection
If the job site inspection reveals damage or material
shortages, file a claim with the carrier immediately. Specify
the type and extent of the damage on the bill of lading
before signing. Notify the appropriate sales representative.
Important: Do not proceed with installation of a damaged
unit without sales representative's approval.
Visually inspect the complete exterior for signs of
shipping damages to unit or packing material.
Verify that the nameplate data matches the sales order
and bill of lading.
Verify that the unit is properly equipped and there are
no material shortages.
Verify that the power supply complies with the unit
nameplate specifications.
Inspection for Concealed Damage
Visually inspect the components for concealed damage as
soon as possible after delivery and before it is stored.
If concealed damage is discovered:
Notify the carrier's terminal of the damage immediately
by phone and by mail.
Concealed damage must be reported within 15 days.
Request an immediate, joint inspection of the damage
with the carrier and consignee.
Stop unpacking the unit.
for general waterside
SCXF-SVX01T-EN

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IntelliPak Signature SCWF and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Intellipak signature siwf

Table of Contents