Installation Sequence - Assa Abloy Norton LEO 5700 Series Installation And Instruction Manual

Power operator
Hide thumbs Also See for Norton LEO 5700 Series:
Table of Contents

Advertisement

1/2
(13)
1-1/8
(29)
3
(76)
C L Hinge
2" (51mm)
Min. Frame
Face
1-3/4" (44mm) Min.
Door Thickness
2-1/4" (57mm) Max.
Step 1: Determine hand of door from illustration on upper right of this
page.
Step 2: Using template above locate and prepare holes in the frame &
door:
Frame
A. Prepare six (6) holes for 1/4-20 machine screws or
No. 14 x 2-3/4" (70mm) wood screws. Blind rivet nuts (by others)
are suggested for unreinforced hollow metal frames or for
aluminum frames.
B. Concealed Wired Units Only: Two (2) 7/8" (22mm) diameter
holes for conduit, for power input and for switch/sensor wires.
NOTE: On new construction these holes will generally be drilled
by the frame supplier at their shop or at the time the frame is
installed in the wall.
Norton® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2015 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
1. Hinge (Pull) Side Mounting Instructions
A
14-3/16
(360)
13-13/16
(350)
12-15/16
(329)
11-11/16
(297)
1-1/4
(32)
7/8 (23) Dia.
1-7/16
(2 Places)
(37)
11
(279)
Door Opening
Dim "A"
Angle
Up to 110°
15-1/2 (394)
111° to 180°
13-1/4 (337)
6" (152mm)
Min. Ceiling
1A. Installation Sequence
Right Hand Door
opening to 110° shown.
7-9/16
(192)
Please verify desired mounting
requires Hinge (Pull) Side
application as shown on this
template.
22
(559)
Clearance
Frame Reveal
Door
C. Prepare three (3) holes for 3/8" diameter sex nuts. Standard units
are supplied with sex nuts and screws for 1-3/4" (44mm) thick door.
Sex nuts and screws for other door thicknesses are available to
order.
Step 3: Remove cover from the unit and set cover & cover screws aside.
Step 4: Mount unit to door frame. Select A or B below.
A. Concealed Wired Units Only:
backplate. Fasten unit to door frame (seven screws).
B. Surface Wired Units Only:
screws). Mount conduit bracket (found in screw pack) to unit's
backplate with two screws provided. Connect wiring conduit to
bracket.
(Continue to next page.)
Page 4
13-13/16
(351)
13-7/16
(341)
1/4-20 Machine Screws
or No. 14 Wood Screws
(6 Places)
1-1/8"
(29)
Notes:
• All dimensions are given in inches (mm).
• Thickness recommended for reinforcements in hollow
metal doors and frames is charted on Page 2.
• Do not scale drawing.
• Right hand door shown.
• This template information based upon use of 5"
(127mm) maximum width butt hinges. A separate
template is required for other conditions.
• Maximum frame reveal is 6-7/8" (175mm) for this
application.
• Conduit hole nearest the hinge is suggested for 120
VAC power input.
Note: Door must be visible by person
operating activation switch(es)
Connect conduit to frame side of
Fasten unit to door frame (seven
ASSA ABLOY
6"
(152mm)
Min.
Clearance
2" (51mm)
Min.
Frame Face
5/8
Stop
(15.9)
Frame
Rabbet
Frame
3/8 Dia.
Stop/Soffit
Sex Nuts
(3 Places)
80-9357-0008-020 (Rev 3)