4.4 LCD Settings
There are four buttons on the LCD. Step for settings by
the display:
Step1: After touch Enter button for about 2 seconds ,
the unit will enter setting mode.The setting
icon and index will flashing.
Step2:Touch UP or Down button to select setting
index from 1 to 19.
Step3: Then touch Enter button to set this item.
Step4: Touch UP or Down button to change the settings.
Step5: Touch Enter to confirm the setting or Return the
setting list is as below.
Description
Index
1
Date& time
PV input mode
2
23
Setting Option
Setting Year/Month/day
Setting hour/minute/second
Default: S
S: two independent
Strings input
P:Same string input
for 2 MPPTs
dc: DC source input
Run with No Battery:
Step1:Choose battery type first, when no flashing,
select Enter to choose Run with No battery
For Lead Acid:
Step1:Choose battery type first, when Lead-Acid
flashing, select Enter to choose Lead-acid battery
Step2:Then choose battery capacity
Battery
3
For Lithium battery
Step1:Choose battery type first, when Li-ion
flashing, select Enter to choose Li-ion battery
Step2:Choose battery brand
0- > Standard Battery
6->Luxpower protocol Battery
UPS Output voltage
4
and frequency
5
Buzzer enable
Ic:Maximum charge
6
current
2->Pylon Battery
8->Dyness Battery
AC Output voltage
200Vac/208Vac/220Vac/
230Vac(Default)/240Vac
AC Output frequency
50Hz (Default)/60Hz
Buzzer enable(Default)
Buzzer Disable
Totoal charge current
(Iac+Ipv)setting
Setting range :0A~140A
Default: 110A
AC charge current setting:
Setting range :0A~140A
Default: 30A
Generator charge current
setting:
Setting range :0A~60A
Default: 30A
24
Need help?
Do you have a question about the SNA6000WPV and is the answer not in the manual?