Mitsubishi Electric FR-A802-E Instruction Manual page 56

Separated converter type
Table of Contents

Advertisement

(a) Remove the upper screws.
(b) Remove the lower screws.
(c) Pull the jumper toward you to remove.
(d) Connect the separate power supply cable for the control circuit to the upper terminals (R1/L11, S1/L21).
NOTE
• When using separate power supplies, always remove the jumpers connected to terminals R1/L11 and S1/L21. The inverter
may be damaged if the jumpers are not removed.
• When the control circuit power is supplied from other than the input line of the MC, the voltage of the separate power supply
must be the same as that of the main control circuit .
• When using a separate power supply connected to terminals R1/L11 and S1/L21, the necessary power capacity is 80 VA.
• If the main circuit power is switched OFF (for 0.1 second or more) then ON again, the inverter is reset and a fault output will
not be held.
(c)
Power supply terminal block
for the control circuit
Power supply terminal block
for the control circuit
R1/L11
S1/L21
(a)
(b)
(d)
2. INSTALLATION AND WIRING
2.6 Control circuit
1
2
3
4
5
6
7
8
9
10
55

Advertisement

Table of Contents
loading