Instructions for installation and use
5.

Installation instructions, GETTING STARTED

Connect the unit to the household piping in accordance with the
labelling at the bottom and/or in accordance with the instructions
in this manual.
Please also refer to page 7, top, Installation instructions, General.
Mount S 22 on a solid wall using expansion bolts or similar. Please
note that the unit weighs more than 60 kg!
See page 7 for more details.
GETTING STARTED is a quick guide and some details in connection
with installation and commissioning may require additional informa-
tion, which can be found elsewhere in this instruction manual.
1.
When the unit has been securely mounted, close all shut-off
valves on supply and return pipes before connecting the unit
to the household piping.
2.
Mount the district heating meter (if the unit includes built-in
fitting piece for heat meter - see page 7 in the instructions, if
necessary).
3.
IMPORTANT! Tighten all pipe connections, as they may
have loosened during transport and handling (do NOT
overtighten!) - check that the air valve in top of the unit is
closed.
4.
Establish a drain connection on the safety valves in compli-
ance with the aplicable legislation.
5.
Open the ball valves for HE supply and return and fill the
system with water by carefully opening the ball valve for the
district heating supply flow and at the same time venting the
system. Finally, open the ball valve for the district heating
return flow.
6.
Carefully open the ball valve for the DCW inlet.
7.
Check the unit and the household piping thoroughly for
leaks.
8.
Pressure test the entire system for leaks in accordance with
the applicable regulations.
9.
Connect the ECL automatics to the electricity supply, but do
not switch on the power.
10. Heat the system and vent the radiator circuit/heating side
thoroughly on the radiators and the air valve, see pages 11
and 13 "Venting of system" in the instruction manual
11. Now switch on the automatics at the mains.
12. Finish by adjusting the unit in accordance with the instruc-
tions and remember to fill-in the commissioning certificate
on page 18.
13. IMPORTANT! Heating and cooling of the system may cause
leaks. Therefore it may be necessary to retighten the connec-
tions in the period after commissioning.
6
DKDHR
S 22
District heating
supply return
Primary
VI.IE.D1.02
DCW
Circ.
DHW
HE
return
Domestic water
Secondary
Danfoss District Energy
HE
supply