Electrical Connections, Ecl Comfort 310 - Danfoss S 22 Instructions For Installation And Use Manual

Table of Contents

Advertisement

Instructions for installation and use
7.

Electrical connections, ECL Comfort 310

Electrical connection
The electrical connection of the unit must be performed by authorised
personnel. The unit is to be connected to a 230 V AC mains power supply.
The power supply/connection must be carried out in accordance with
the applicable regulations and instructions.
The unit must be connected to an external switch so that it can be
disconnected in connection with maintenance, cleaning and repairs
or in the event of an emergency.
As standard the S 22 is supplied with Danfoss ECL Comfort 310 with
Application 266. The control equipment includes actuators and sensors
installed in the unit and the controller, placed/mounted on the mount-
ing plate in top of the unit. The controller is electrically wired to sensors,
pump and actuators.
Outdoor sensor is supplied loose, and installation and connection of
this is carried out in accordance with below instructions.
Installation of outdoor sensor (ESMT)
The outdoor temperature sensor is supplied loose with the unit.
It is to be mounted on site as shown in the drawings to the right.
Always mount the sensor on the coldest side of the building (normally
the north side).
It must not be exposed to morning sunlight, and must not be po-
sitioned above windows, doors, ventilation ducts, balconies under
overhanging roof sections, or close to any other heat source.
Installation height: approx. 2.5 m above ground level.
Temperature range: -50 to 50° C.
Electrical connection
The cables can be connected to the sensor in any order.
Connection cable: 2 x 0.4 - 1.5 mm²
The cable ends are connected to the ECL 310 controller in common
ground terminal and in terminal 29.
S 22 med electronic control of both circuits (App. A266)
From factory the controller is electrically wired to sensors, pump and
actuators according to the diagram to the right.
Mounting of sensor for DHW (ESMU)
Sensor pocket and sensor are factory-mounted in the unit and elec-
trically wired to the controller in common ground terminal and in
terminal 26.
Other sensors
Other supply and return flow sensors are also mounted and electrically
wired to the controller from factory.
Mounting of pumps
The circulation pump P1 is electrically wired to the controller in
terminal N and terminal 11.
The P2 for the heating circuit is electrically wired to the controller
in terminal N and terminal 12.
Access to ECL base part
Access to the base part for connection of outdoor sensor or the like
is obtained by pulling the lock (pin) down with a screwdriver until a
yellow line is visible on the lock. Then, the front piece can easily be
removed. Locking is achieved by pressing the lock up.
8
DKDHR
Lock / pin
S 22
Controller ECL Comfort 310
Supply voltage:
Power consumption: 5 VA
Actuator AMV 10 / AMV 30 / AMV 150
Supply voltage:
Power consumption: 2 VA / 7 VS / 8 VA
Pumps Wilo Yonos PARA, Stratos PARA, Star-Z NOVA
(Alternatively: Grundfos Alpha2, Magna, Alpha2 L CIL2)
Supply voltage:
Power consumption:
Wilo, HE
Grundfos, HE
Wilo, DHW
Grundfos, DHW
230 V a.c. , A266.1 / A266.2 / A266.9
ESMU
ECL Comfort 310 base part
VI.IE.D1.02
230 V AC - 50 Hz
230 V AC - 50 Hz
230 V AC - 50/60 Hz
Max 45 Watt (Yonos) / 70 Watt (Stratos)
Max 25 Watt (Alpha2) / 185 Watt (Magna)
Max 4,5 Watt (Star-Z NOVA)
Max 22 Watt (Alpha2 L 15-40 CIL2 PPS)
Common ground
terminal
Danfoss District Energy