5.9

Combustion head adjustment

The air damper servomotor 4)(Fig. 4 on page 11) varies the air
output according to the output demand, while manually a lever-
age varies the combustion head adjustment.
The selection of the hole to be used is determined based on the
maximum output requested, as illustrated in Tab. I.
In the factory, the adjustment is adjusted for the minimum stroke
(hole 0, Fig. 14).
Leverage hole
RS 1000/EV FGR
0
1
2
3
4
5
6
7
8
9
10
The gas pipes leave the factory calibrated at
notch 1.
The adjustment shown in Fig. 15 allows the gas
WARNING
pipes to be positioned in the best way for the ap-
plication on which the burner is installed (e.g. boil-
ers with flame inversion chamber).
5.10

Ignition pilot burner

For correct functioning, adjust the gas pressure (measured on
the socket located on the valve) to between 30 ÷ 50 mbar.
Gas
G20
G31
Before starting the main burner, make sure that
the pilot flame is stable, checking the value of the
flame signal on the AZL display on the boiler's
main panel.
WARNING
Continue with the burner ignition procedure, checking that the pi-
lot has come on correctly.

5.10.1 Ignition pilot positioning

Position the electrode at a distance of 2 - 3 mm from the hole, as
shown in Fig. 16.
D3899
Output (kW)
RS 1200/EV FGR
1100
1500
2200
2500
3200
3700
4200
5000
5000
6000
6000
7000
7000
8000
8000
9000
8900
9800
9700
10800
10100
11100
mbar
Sm
1.5
12.3
1.4
3.2
Installation
20133583
20077710
Tab. I
3
/h
Tab. J
Fig. 16
19
GB
0
5
10
20134186
Fig. 14
Fig. 15
Fig. 17
20166543