ESIE17-08
|
Part 3. Repair
3
2
1
1. Screw ground wire
2. Screw
Finally, strip the Main PCB assembly (rear)
19. Unplug the connector (2).
20. Unplug the terminal wires (1).
21. Remove the wiring from the cable clamps (6) if necessary.
22. Unlock the 4 standoffs (5) that fix the electrical noise PCB (4).
23. Remove the electrical noise filter PCB (4) from the main PCB assembly.
15/11/18
|
Version 1.1
R32 Sky-Air RZAG-M
Figure 3-29: Stripping the main PCB assembly 3-phase (front)
3.3. Unit specific repair procedures
3. Terminal connectors