Part 2. Troubleshooting
7.
Megger the compressor using 500 or 1000 VDC, the insulation must be higher than 3 MΩ.
8.
Replace the compressor if the windings and/or insulation measurements fail (refer to
9.
Run the compressor and measure the current in each phase; the current for each phase should be identical (refer to
specific information" on page
compressor" on page
77).
15/11/18
|
Version 1.1
R32 Sky-Air RZAG-M
128). In that case it can be decided to preventively replace the compressor (refer to
2.4. Component checklist
"Replacing compressor" on page
"Replacing
77).