Code
Meaning
F.797
Sensor fault: Cooling flow temp.
F.798
Sensor fault: Well inlet temp.
F.799
Sensor fault: Well outlet temp.
F.1100
Heating rod: Safety cut-out open
F.1117
Compressor: Phase failure
F.1118
Compressor: Incorrect phase seq.
F.1119
Compressor: ICL fault
F.1120
Heating rod: Phase failure
0020213394_01 flexoTHERM exclusive Installation and maintenance instructions
Cause
Sensor not connected or sensor
input has short-circuited
Sensor not connected or sensor
input has short-circuited
Sensor not connected or sensor
input has short-circuited
The safety cut-out on the auxiliary elec-
tric heater is open due to:
Insufficient volume flow or air in the
building circuit
Heating rod operation when the
building circuit is not filled
Heating rod operation at flow tem-
peratures above 110 °C trips the
fuse of the safety cut-out and re-
quires that the fuse be replaced
Feeding of external heat into the
building circuit
In-rush current limiter defective or
incorrectly connected
Defective fuse
Poorly tightened electrical connec-
tions
Mains voltage too low
Compressor/low tariff power supply
not connected
Blocked by energy supply company
for over three hours
Incorrect order of phase connection
to the mains supply
In-rush current limiter defective or
incorrectly connected
In-rush current limiter defective or
incorrectly connected
Mains voltage too low
The circuit breaker in the electronics
box has been triggered
Auxiliary electric heater defective
Poorly tightened electrical connec-
tions
Mains voltage too low
Blocked by energy supply company
for over three hours
Appendix
Remedy
Check the sensor, and replace if
necessary
Replace the cable harness
Check the sensor, and replace if
necessary
Replace the cable harness
Check the sensor, and replace if
necessary
Replace the cable harness
Check the circulation in the building
circuit pump
If required, open the stop cock. The
safety cut-out is automatically reset
as soon as the temperature at the
fuse falls below 55 °C again.
Also press
.
reset
If the safety cut-out is still open at an
auxiliary electric heater temperature
below 55 °C, temperatures above
110 °C were reached and the fuse
tripped.
Replace the safety cut-out
Reduce or stop the external heat
that is entering
Check the fuse
Check the electrical connections
Measure voltage at the heat pump
electrical connection
Reduce energy supply company
anti-cycling time to under three hours
Change the phase order by switch-
ing over two phases at a time on the
mains supply
Check the in-rush current limiter
Check all plug contacts
Check the ICL compressor connec-
tion
Check the ICL controller PCB con-
nection
Replace the ICL
Check the auxiliary electric heater
and its power supply, and reset the
circuit breaker
Check the electrical connections
Measure the voltage at the electrical
connection for the auxiliary electric
heater
53