Vaillant flexoTHERM exclusive VWF 117/4 Installation And Maintenance Instructions Manual page 50

Table of Contents

Advertisement

Appendix
Code
Meaning
F.715
Env. circuit: Fault contact: Pump
open
F.718
Fan unit 1: Fan blocked
F.719
Fan unit 1: Safety cut-out open
F.723
Building circuit: Pressure too low
F.724
Sensor fault: Fan unit 1 fan inlet
temp.
F.725
Sensor fault: Fan unit 1 brine flow
temp.
F.731
High pressure switch opened
F.732
Compressor outlet temperature
too high
50
Cause
The electronics system of the high-
efficiency pump has detected a
fault (e. g. dry running, blockage,
overvoltage, undervoltage) and
switched the pump off as a securing
measure.
There is no confirmation signal stat-
ing that the fan is rotating
The safety cut-out on the de-icer is
open due to insufficient volume flow
and/or brine temperatures above
65 °C
Operating the de-icer outside of the
permitted area of application
De-icer operation when the brine
circuit is not filled
During de-icer operation at brine
temperatures above 115 °C, the fuse
of the safety cut-out is tripped and
the fuse must be replaced.
Pressure loss in the building circuit
due to leaks or air pockets
Building circuit pressure sensor
defective
Sensor not connected or sensor
input has short-circuited
Sensor not connected or sensor
input has short-circuited
Coolant pressure too high. The
integrated high-pressure switch has
tripped at 46 bar (g) or 47 bar (abs)
Insufficient energy output via the
relevant condenser
The compressor outlet temperature is
above 130 °C:
Application limits exceeded
EEV does not work or does not open
correctly
Coolant volume too low
Installation and maintenance instructions flexoTHERM exclusive 0020213394_01
Remedy
Switch the heat pump off for at least
30 seconds (no current)
Check the quality of the plug contact
on the PCB
Check that the pump functions cor-
rectly
Purging the environment circuit
Check the air route and, if required,
remove any blockages
Check and, if required, replace the
F1 fuse on the PCB in the fan unit
(OMU)
Checking for circulation in the envir-
onment circuit pump
If required, open the stop cock. The
safety cut-out is automatically reset
as soon as the temperature at the
fuse falls below 30 °C again. If the
safety cut-out is still open at a de-
icer temperature below 65 °C (or
30 °C), temperatures above 115 °C
were reached and the fuse tripped.
Check and, if required, replace the
F1 fuse of the air/brine collector
Replace the safety cut-out
Check the building circuit for leaks
Top up with water, purge
Check the quality of the plug contact
on the PCB and on the cable har-
ness
Check that the pressure sensor is
working correctly
Replace the pressure sensor
Check the sensor in the fan unit, and
replace if necessary
Replace the cable harness in the fan
unit
Check the sensor in the fan unit, and
replace if necessary
Replace the cable harness in the fan
unit
Purging the building circuit
Insufficient volume flow as a result of
closing individual room controllers in
an underfloor heating system
Check that the dirt filter that is in
place is permeable
Refrigerant flow rate too low (e.g.
electronic expansion valve defective,
four-way valve mechanically blocked,
filter blocked). Inform Customer
Service.
VWL SA (cooling mode): Check the
fan unit for dirt
Check the low-pressure sensor,
compressor inlet sensor and outlet
sensor
Check the EEV (does the EEV
move to the limit stop? Use the
sensor/actuator test)
Check the refrigerant volume (see
Technical data)
Carry out a leak-tightness test