Appendix
Code
Meaning
F.782
Connection error: Fan unit 2
F.783
Connection error: Terminal block
(TMB)
F.784
Connection error: ICL
F.785
Fan unit 2: Fan blocked
F.786
Fan unit 2: Safety cut-out open
F.787
Environment circuit: Pressure
mon. open
F.788
Building circuit: Pump fault
F.789
Sensor fault: Fan unit 2 fan inlet
temp.
F.790
Sensor fault: Fan unit 2 brine flow
temp.
F.792
Sensor fault: VI inlet temp.
F.793
Sensor fault: EEV-VI outlet temp.
52
Cause
No electrical connection
No eBUS connection
Cable not connected or connected incor-
rectly
Cable not connected or connected incor-
rectly
There is no confirmation signal stat-
ing that the fan is rotating
The safety cut-out on the de-icer is
open due to insufficient volume flow
and/or brine temperatures above
65 °C
Operating the de-icer outside of the
permitted area of application
De-icer operation when the brine
circuit is not filled
During de-icer operation at brine
temperatures above 115 °C, the fuse
of the safety cut-out is tripped and
the fuse must be replaced.
Pressure loss in the environment
circuit due to leaks or air pockets
Environment circuit pressure monitor
defective
The electronics system of the high-
efficiency pump has detected a
fault (e. g. dry running, blockage,
overvoltage, undervoltage) and
switched the pump off as a securing
measure.
Sensor not connected or sensor
input has short-circuited
Sensor not connected or sensor
input has short-circuited
Sensor not connected or sensor
input has short-circuited
Sensor not connected or sensor
input has short-circuited
Installation and maintenance instructions flexoTHERM exclusive 0020213394_01
Remedy
Check the electrical connection to
fan unit 2 (check the line connection;
contact fault? Has the circuit breaker
tripped in the connection box?)
Check the eBUS connection to fan
unit 2
Check the address switch position
on the PCB of fan unit 2. Required
switch position: 2
Check the connection line between the
mains connection PCB and the controller
PCB
Check the connection line between the
mains connection PCB and the in-rush
current limiter PCB
Check the air route and, if required,
remove any blockages
Check and, if required, replace the
F1 fuse on the PCB in the fan unit
(OMU)
Checking for circulation in the envir-
onment circuit pump
If required, open the stop cock. The
safety cut-out is automatically reset
as soon as the temperature at the
fuse falls below 30 °C again. If the
safety cut-out is still open at a de-
icer temperature below 65 °C (or
30 °C), temperatures above 115 °C
were reached and the fuse tripped.
Check and, if required, replace the
F1 fuse of the air/brine collector
Replace the safety cut-out
Check the environment circuit for
leaks
Top up the medium (brine/water),
purge
Check the screwed contact on the
PCB
Check that the pressure monitor
works correctly
Replace the pressure monitor
Switch the heat pump off for at least
30 seconds (no current)
Check the quality of the plug contact
on the PCB
Check that the pump functions cor-
rectly
Purging the building circuit
Check the sensor in the fan unit, and
replace if necessary
Replace the cable harness in the fan
unit
Check the sensor in the fan unit, and
replace if necessary
Replace the cable harness in the fan
unit
Check the sensor, and replace if
necessary
Replace the cable harness
Check the sensor, and replace if
necessary
Replace the cable harness