Technical Specifications - Siemens SIMATIC NET CP 442-1 RNA Equipment Manual

Industrial ethernet
Table of Contents

Advertisement

Technical specifications

Technical specifications
Attachment to Industrial Ethernet
Number
Design of the Ethernet interface
Design of the RNA interface
Electrical data
Power supply
Current consumption
Permitted ambient conditions
Ambient temperature
Relative humidity
Operating altitude
Contaminant concentration
Design, dimensions and weight
Module format
Degree of protection
Weight
Dimensions (W x H x D)
Installation options
Permitted cable lengths
0 ... 55 m
0 ... 85 m
0 ... 100 m
Product functions **
* For details, refer to the IK PI catalog, cabling technology
** You will find the product functions in the section Application and functions (Page 11).
CP 442-1 RNA
Equipment Manual, 03/2022, C79000-G8976-C318-05
1 x Ethernet interface
1 x RNA interface with 2 ports
Connector
Transmission speed
Connector
Transmission speed
via S7 backplane bus
From backplane bus
Power dissipation
During operation
During storage
During transportation
During operation
≤ 2,000 m above sea level
Acc. to ISA-S71.04 severity level G1, G2, G3
Compact module for S7-400, single width
IP20
Approx. 700 g
25 x 290 x 210 mm
Mounting in an S7-400 rack
(Alternative combinations per length range) *
Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
Max. 85 m IE FC TP Marine/Trailing/Flexible/FRNC/Festoon/Food Cable with
IE FC RJ45 Plug 180
Max. 75 m IE FC TP Marine/Trailing/Flexible/FRNC/Festoon/Food Cable + 10 m
TP Cord via IE FC RJ45 Outlet
Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
1 x RJ-45 jacks
10 / 100 Mbps half duplex or full duplex
2 x RJ-45 jacks
100 Mbps full duplex
5 V
2 A
10 W
0 °C to +60 °C
-40 °C to +70 °C
-40 °C to +70 °C
≤ 95 % at 25 °C, no condensation
8
61

Advertisement

Table of Contents
loading

Table of Contents