X-Staged Supply Air Operation - Lennox LGH094U Unit Information

Table of Contents

Advertisement

TABLE 31
MINIMUM AND MAXIMUM CFM
094U4E, 122U4E, 152U4E
Gas Heat Minimum CFM
Unit
Gas Heat Size
LGH094-152
LGH094-152
Electric Heat Minimum CFM
Unit
Heat Size (kW)
LCH094
LCH094
0, 15, 22.5, 30, 45
LCH122, 152
15, 22.5, 30, 45
LCH122, 152
Cooling Low Minimum CFM - 160 CFM/ton
Unit
Blower Speed
LGH/LCH094
LGH/LCH122
LGH/LCH152
Cooling High Minimum CFM - 220 CFM/ton
Unit
Blower Speed
LGH/LCH094
LGH/LCH122
LGH/LCH152
Smoke and Ventilation Minimum CFM - 150 CFM/ton
Unit
Not Applicable
LGH/LCH094
LGH/LCH122
LGH/LCH152
Heating and Cooling Maximum CFM - 480 CFM/ton
Unit
Blower Speed
LGH/LCH094
LGH/LCH122
LGH/LCH152
*Rounded to nearest 25 CFM.
Airflow CFM*
Std. , Med.
2225
High
2550
Airflow CFM
7.5
1750
2750
2750
0, 60
3500
Airflow CFM
Low
1200
Low
1600
Low
2000
Airflow CFM
High
1650
High
2200
High
2750
Airflow CFM
NA
1125
NA
1500
NA
1875
Airflow CFM
High
3600
High
4800
High
6000

X-Staged Supply Air Operation

This is a summary of cooling operation for both belt and di­
rect drive blowers.
Note - During a dehumidification demand the blower oper­
ates at the highest speed. Free cooling is locked-out during
reheat operation. Refer to Hot Gas Reheat start-up and op­
eration section for details.
A-Two-Stage Thermostat
1-Economizer With Outdoor Air Suitable
Y1 Demand -
Compressors Off
Blower Cooling Low
Dampers modulate
Y2 Demand -
Compressors Off
Blower Cooling High
Dampers Modulate
Note - If dampers are at maximum open for three minutes,
compressor 1 is energized and blower stays on cooling
high.
2-No Economizer or Outdoor Air Not Suitable
Y1 Demand -
Compressor 1 On (on ultra high efficiency units,
Blower Cooling Low
Dampers Minimum Position
Y2 Demand -
Compressor 1 and 2 On
Blower Cooling High
Dampers Minimum Position
B-Three-Stage Thermostat OR Zone Sensor
1-Economizer With Outdoor Air Suitable
Y1 Demand -
Compressors Off
Blower Cooling Low
Dampers modulate
Y2 Demand -
Compressors Off
Blower Cooling High
Dampers Modulate
Note - If dampers are at maximum open for three minutes,
compressor 1 is energized and blower stays on cooling high.
Y3 Demand -
Compressors 1 and 2 On
Blower Cooling High
Dampers Maximum Open
Page 71
one compressor will operate)