B-Refrigerant Charge and Check - Fin/Tube Coil - TXV
LGH/LCH092H, 102H, 120H, 150S, 150H
WARNING-Do not exceed nameplate charge under any
condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant, re­
claim the charge, evacuate the system, and add required
nameplate charge.
NOTE - System charging is not recommended below 60°F
(15°C). In temperatures below 60°F (15°C) , the charge
must be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in standard cooling mode.
1- Attach gauge manifolds and operate unit in cooling
mode with economizer disabled until system stabilizes
(approximately five minutes). Make sure outdoor air
dampers are closed.
2- Check each system separately with all stages operat­
ing.
3- Use a thermometer to accurately measure the outdoor
ambient temperature.
4- Apply the outdoor temperature to tables 9 through 18
to determine normal operating pressures. Pressures
are listed for sea level applications at 80
5
and 67
F wet bulb return air.
5- Compare the normal operating pressures to the pres­
sures obtained from the gauges. Minor variations in
these pressures may be expected due to differences in
installations. Significant differences could mean that
the system is not properly charged or that a problem
exists with some component in the system. Correct
any system problems before proceeding.
6- If discharge pressure is high, remove refrigerant from
the system. If discharge pressure is low, add refrigerant
to the system.
S Add or remove charge in increments.
S Allow the system to stabilize each time refrigerant
is added or removed.
7- Use the following approach method along with the nor­
mal operating pressures to confirm readings.
TABLE 9
LGH/LCH092H Fin/Tube Coil - TXV
CIRCUIT 1
Outdoor
Dis­
Coil
charge
Suction
Entering
+10 psig
Air Temp
o
65
F
235
o
75
F
272
o
85
F
312
o
95
F
357
o
105
F
407
o
115
F
460
5
F dry bulb
CIRCUIT 2
Dis­
charge
Suction
+5 psig
+5 psig
+10 psig
137
262
137
139
298
141
142
338
144
146
380
146
149
428
149
154
477
153
LGH/LCH092H Fin/Tube Coil Hot Gas Reheat - TXV
Outdoor
Dis­
Coil
charge
Entering
+10 psig
Air Temp
o
65
F
242
o
75
F
279
o
85
F
319
o
95
F
364
o
105
F
414
o
115
F
467
LGH/LCH102H Fin/Tube Coil - TXV
Outdoor
Dis­
Coil
charge
Entering
+10 psig
Air Temp
o
65
F
241
o
75
F
277
o
85
F
318
o
95
F
362
o
105
F
411
o
115
F
464
LGH/LCH102H Fin/Tube Coil Hot Gas Reheat - TXV
Outdoor
Dis­
Coil
charge
Entering
+10 psig
Air Temp
o
65
F
249
o
75
F
285
o
85
F
327
o
95
F
370
o
105
F
420
o
115
F
473
LGH/LCH120H Fin/Tube Coil - TXV
Outdoor
Dis­
Coil
charge
Entering
+10 psig
Air Temp
655 F
259
755 F
297
855 F
338
955 F
382
1055 F
431
1155 F
486
LGH/LCH120H Fin/Tube Coil Hot Gas Reheat - TXV
Outdoor
Dis­
Coil
charge
Entering
+10 psig
Air Temp
655 F
266
755 F
303
855 F
344
955 F
391
1055 F
443
1155 F
499
Page 51
TABLE 10
CIRCUIT 1
CIRCUIT 2
Dis­
Suction
charge
+5 psig
+10 psig
134
262
137
297
140
338
143
379
146
427
151
476
TABLE 11
CIRCUIT 1
CIRCUIT 2
Dis­
Suction
charge
+5 psig
+10 psig
139
273
141
307
143
348
145
389
148
437
150
486
TABLE 12
CIRCUIT 1
CIRCUIT 2
Dis­
Suction
charge
+5 psig
+10 psig
137
272
139
306
141
347
143
389
146
436
148
485
TABLE 13
CIRCUIT 1
CIRCUIT 2
Dis­
Suction
charge
+5 psig
+10 psig
137
283
140
321
143
360
146
406
149
453
151
505
TABLE 14
CIRCUIT 1
CIRCUIT 2
Dis­
Suction
charge
+5 psig
+10 psig
134
281
137
310
140
358
143
403
146
450
149
497
Suction
+5 psig
139
143
146
148
151
155
Suction
+5 psig
141
144
147
149
151
152
Suction
+5 psig
142
145
148
150
152
154
Suction
+5 psig
139
142
144
146
148
151
Suction
+5 psig
139
141
143
145
146
148