Lennox LGH094U Unit Information page 42

Table of Contents

Advertisement

D-GAS HEAT COMPONENTS
See unit nameplate for all -1 model unit Btuh capacities.
See SPECIFICATIONS tables or unit nameplate for
Btuh capacities in -2 model units. Flexible pipe will feed
supply gas to both sections. If for service the flexible
connection must broken, hand tighten then turn addi­
tional 1/4" with a wrench for metal to metal seal (do not
overtighten).
NOTE - Do not use thread sealing compound on flex pipe
flare connections.
1-Control Box Components A3, A55, T3, K13
WARNING
Shock hazard. Spark related compo­
nents contain high voltage which can
cause personal injury or death. Discon­
nect power before servicing. Control is
not field repairable. Unsafe operation
will result. If control is inoperable, sim­
ply replace the entire control.
É É É
ON / CLOSED
É É É
OFF / OPEN
THERMOSTAT DEMAND
COMBUSTION AIR BLOWER
COMBUSTION AIR PROVE SWITCH
IGNITION SPARK
IGNITION TRIAL
É É É
ON
SECONDS 0
OFF
THERMOSTAT DEMAND
COMBUSTION AIR BLOWER
COMBUSTION AIR PROVE SWITCH
GAS VALVE
IGNITION SPARK
IGNITION TRIAL
É É É
ON
É É É
OFF
THERMOSTAT DEMAND
COMBUSTION AIR BLOWER
NORMAL IGNITION SEQUENCE - TIMINGS NOMINAL
SECONDS 0
5
30
É É É É É É É É É É É É É
É É É É É É É É É É É É É
É É É É É É É É É É É É É
É É É É É É É É É É É É É
É É
É É É É É É É É É
GAS VALVE
É É É É É É É É É É É É
BLOWER
RETRIALS - IGNITION ATTEMPT SEQUENCE - TIMINGS NOMINAL
5
30 35
É É É É É É É É É É É É É É É É É É É É
É É É É É É É É É É É É É É É É É É É É
É É É É É É É É É É É É É É É É É É É É
É É É É É É É É É É É É É É É É É É É É
É É É É É É É É É É É É É É É É É É É
É É
É É É É
É É
BLOWER
IGNITION CONTROL TIMING
SECONDS 0
30
É É É É É É É É É É É É É É
É É É É É É É É É É É É É É
É É É É
É É
GAS VALVE
IGNITION SPARK
É É
BLOWER
IGNITION TRIAL
Burner Ignition Control A3
The ignition control is located in the heat section and is manu­
factured by Johnson Controls. See table 3 for LED codes.
Manufacturer
Johnson
The ignition control provides three main functions: gas
valve control, ignition and flame sensing. The unit will usu­
ally ignite on the first attempt; however, the ignition attempt
sequence provides three trials for ignition before locking
out. The lockout time for the Johnson control is 5 minutes.
After lockout, the ignition control automatically resets and
provides three more attempts at ignition. Manual reset after
lockout requires breaking and remaking power to the igni­
tion control. See figure 22 for a normal ignition sequence
and figure 23 for the ignition attempt sequence with retrials
(nominal timings given for simplicity). Specific timings for
the ignition controls are shown in figure 24.
35
70
END OF
DEMAND
1
É É É É É É É É É É
FIGURE 22
65
70
100 105
É É
É É
É É
É É
É É É É
É É
É É
LOCKOUT
FIGURE 23
6 (+3.4, -2.0) SEC.
30
30
É É É É
É É É É É É
É É
É É
1
2
3
42 SEC.
FIGURE 24
Page 42
TABLE 3
LED Code
Description
Steady "ON"
.5 sec on / 2.5 sec off
"OFF"
No Power or Detected Failure
0
5
110
WATCHGUARD
END OF
THERMOSTAT
DEMAND
HEATING
CYCLE
É É É
É É
É É É
É É
122 SEC.
Normal
Reset Mode