Lennox LGH094U Unit Information page 10

Table of Contents

Advertisement

SPECIFICATIONS - GAS HEAT - 092H, 102H, 120H, 150H
Number of Gas Heat Stages
Gas Heating
Input - Btuh
Performance
Output - Btuh
Temperature Rise Range - °F
Gas Supply Connections
Recommended Gas Supply
Pressure - in. w.g.
HIGH ALTITUDE DERATE - 092H, 102H, 120H, 150H
Units may be installed at altitudes up to 2000 feet above sea level without any modification.
At altitudes above 2000 feet, units must be derated to match gas manifold pressures shown in table below.
At altitudes above 4500 feet unit must be derated 2% for each 1000 feet above sea level.
NOTE − This is the only permissible derate for these units.
Gas Heat
Altitude
Type
Feet
Standard
2001-4500
Medium
2001-4500
High
2001-4500
Heat Input Type
First Stage
Second Stage
Second Stage
Thermal Efficiency
Natural
LPG/Propane
Gas Manifold Pressure
in. w.g.
Natural Gas
3.4
3.4
3.4
Standard
2
84,500
130,000
104,000
15 - 45
80%
3/4 in. npt
7 in. w.c.
11 in. w.c.
LPG/Propane Gas
9.6
9.6
9.6
Page 10
Medium
2
117,000
180,000
144,000
30 - 60
80%
3/4 in. npt
7 in. w.c.
11 in. w.c.
Input Rate - Btuh
(Natural Gas or LPG/Propane)
First Stage
Second Stage
84,500
117,000
156,000
High
2
156,000
240,000
192,000
40 - 70
80%
3/4 in. npt.
7 in. w.c.
11 in. w.c.
124,000
172,000
230,000

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents