TABLE 29
MINIMUM AND MAXIMUM CFM
092H, 102H, 120H, 150H
Gas Heat Minimum CFM
Unit
Gas Heat Size
LGH092-150
LGH092-150
Electric Heat Minimum CFM
Unit
Heat Size (kW)
LCH092-102
LCH092-150
7.5, 15, 22.5, 30, 45
LCH120-150
Cooling Minimum CFM - 220* CFM/ton
Unit
Blower Speed
LGH/LCH092
LGH/LCH102
LGH/LCH120
LGH/LCH150
Cooling Minimum CFM - 280* CFM/ton
Unit
Blower Speed
LGH/LCH092
LGH/LCH102
LGH/LCH120
LGH/LCH150
Smoke and Ventilation Minimum CFM - 150 CFM/ton
Unit
Not Applicable
LGH/LCH092
LGH/LCH102
LGH/LCH120
LGH/LCH150
Heating and Cooling Maximum CFM - 480 CFM/ton
Unit
Blower Speed
LGH/LCH092
LGH/LCH102
LGH/LCH120
LGH/LCH150
*Refer to table 31 for ultra high efficiency unit minimum
CFM / ton. Ultra high efficiency units are equipped with tan­
dem compressors which allow lower minimum airflow.
Airflow CFM
Std. , Med.
2225
High
2550
Airflow CFM
0
2800
2800
0, 60
4000
Airflow CFM
Low
1650
Low
1870
Low
2200
Low
2750
Airflow CFM
High
2100
High
2380
High
2800
High
3500
Airflow CFM
NA
1125
NA
1275
NA
1500
NA
1875
Airflow CFM
High
3600
High
4080
High
4800
High
6000