TABLE 15
LGH/LCH150S Fin/Tube Coil - TXV
CIRCUIT 1
Outdoor
Dis­
Coil
charge
Suction
Entering
+5 psig
+10 psig
Air Temp
655 F
275
755 F
312
855 F
354
955 F
398
1055 F
449
1155 F
500
TABLE 16
LGH/LCH150S Fin/Tube Coil Hot Gas Reheat - TXV
CIRCUIT 1
Outdoor
Dis­
Coil
Suction
charge
Entering
+10 psig
+5 psig
Air Temp
655 F
280
755 F
319
855 F
360
955 F
407
1055 F
455
1155 F
510
TABLE 17
LGH/LCH150H Fin/Tube - TXV
CIRCUIT 1
Outdoor
Dis­
Coil
Suction
charge
Entering
+10 psig
+5 psig
Air Temp
65°F
276
75°F
317
85°F
357
95°F
399
105°F
450
115°F
502
TABLE 18
LGH/LCH150H Fin/Tube Hot Gas Reheat - TXV
CIRCUIT 1
Outdoor
Dis­
Coil
Suction
charge
Entering
+5 psig
+10 psig
Air Temp
65° F
296
75° F
334
85° F
378
95° F
422
105° F
470
115° F
520
Charge Verification - Approach Method - AHRI Testing
(Fin/Tube Coil Continued)
1- Using the same thermometer, compare liquid tempera­
ture to outdoor ambient temperature.
Approach Temperature = Liquid temperature (at con­
denser outlet) minus ambient temperature.
2- Approach temperature should match values in table 19.
An approach temperature greater than value shown indi­
cates an undercharge. An approach temperature less
than value shown indicates an overcharge.
CIRCUIT 2
Dis­
charge
Suction
+5 psig
+10 psig
140
298
139
142
335
141
143
374
142
146
419
146
149
465
148
151
514
150
CIRCUIT 2
Dis­
Suction
charge
+10 psig
+5 psig
136
296
136
141
335
141
142
376
143
144
420
144
147
466
147
150
518
150
CIRCUIT 2
Dis­
Suction
charge
+10 psig
+5 psig
131
275
125
133
314
128
136
363
131
139
408
136
142
457
140
145
509
142
CIRCUIT 2
Dis­
Suction
charge
+5 psig
+10 psig
135
286
135
137
318
136
139
364
138
142
409
140
144
458
142
147
509
146
3- The approach method is not valid for grossly over or
undercharged systems. Use tables 9 through 18 as a
guide for typical operating pressures.
APPROACH TEMPERATURE - FIN/TUBE COIL - TXV
Unit
092
6°F + 1 (3.3°C + 0.5)
102
6°F + 1 (3.3°C + 0.5)
120 & 150S
6°F + 1 (3.3°C + 0.5)
150H
4°F + 1 (2.2°C + 0.5)
092, 120 & 150
6°F + 1 (3.3°C + 0.5)
Hot Gas Reheat
102
6°F + 1 (3.3°C + 0.5)
Hot Gas Reheat
F-Refrigerant Charge and Check - Fin/Tube Coil & RFC
WARNING-Do not exceed nameplate charge under any
condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant, re­
claim the charge, evacuate the system, and add required
nameplate charge.
NOTE - System charging is not recommended below 60_F
(15_C). In temperatures below 60_F (15_C), the charge
must be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in standard cooling mode.
1- Make sure outdoor coil is clean. Attach gauge manifolds
and operate unit at full CFM in cooling mode with econo­
mizer disabled until system stabilizes (approximately five
minutes). Make sure all outdoor air dampers are closed.
2- Check each system separately with all stages operat­
ing. Compare the normal operating pressures (see table
20) to the pressures obtained from the gauges. Check
unit components if there are significant differences.
3- Measure the outdoor ambient temperature and the suc­
tion pressure. Refer to the appropriate circuit charging
curve to determine a target liquid temperature.
Note - Pressures are listed for sea level applications.
4- Use the same thermometer to accurately measure the
liquid temperature (in the outdoor section).
D If measured liquid temperature is higher than the
target liquid temperature, add refrigerant to the
system.
D If measured liquid temperature is lower than the
target liquid temperature, recover some refrigerant
from the system.
5- Add or remove charge in increments. Allow the system
to stabilize each time refrigerant is added or removed.
6- Continue the process until measured liquid tempera­
ture agrees with the target liquid temperature. Do not
go below the target liquid temperature when adjusting
Page 52
TABLE 19
Liquid Temp. Minus Ambient Temp.
1st Stage
2nd Stage
7°F + 1 (3.9°C + 0.5)
9°F + 1 (5.0°C + 0.5)
10°F+1 (5.6°C + 0.5)
6°F+1 (3.3°C + 0.5)
8°F + 1
(4.4°C + 0.5)
9°F + 1
(5.0°C + 0.5)
LGH/LCH150S