Four-Lead Reconnection; 100--120-Volt Configurations - Kohler 9EKOZD Installation Manual

Marine generator sets
Table of Contents

Advertisement

Voltage Reconnection Procedure
1. Stop the generator set.
2. Turn the controller pushbutton/rotary selector dial
until it stops at the Volt Select menu.
Figure 8-1.
Volt Select: ---->
###/### V # Ph
Figure 8-1 Volt Select Menu
46
Section 8 Reconnection
All manuals and user guides at all-guides.com
See
120/240 V 1 Ph
120/208 V 3 Ph
139/240 V 3 Ph
277/480 V 3 Ph
120/240 V 3 Ph
115/230 V 1 Ph
120 V 1 Ph
230 V 1 Ph
240 V 1 Ph
110/190 V 3 Ph
127/220 V 3 Ph
115/230 V 3 Ph
230/400 V 3 Ph
240/416 V 3 Ph
3. Press the selector dial and the voltage selection
option (second line on the display) will start to flash.
4. Turn
the
selector
counterclockwise
until
selection option appears.
5. Press the selector dial. The second line on the
display will stop flashing and the new voltage will
appear.
6. Disconnect the generator set engine starting
battery, negative (--) lead first. Disconnect power to
the battery charger (if equipped).
7. Use Figure 8-2, Figure 8-3, Figure 8-4, Figure 8-5,
or Figure 8-8 to determine the generator set
voltage configuration. Note the original voltage
and reconnect as needed.
8. Reconnect the battery, negative lead last.
9. Start the generator set. Check the digital display
for correct voltages using the section on Generator
Metering included in the Operation Manual.
10. Stop the generator set after completing the voltage
adjustments.

8.2 Four-Lead Reconnection

The following information illustrates the reconnection of
four-lead generator sets. In all cases, conform to the
National Electrical Code (NEC).
NOTICE
Voltage reconnection. Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.
8.2.1
100- -120-Volt Configurations
If the installation requires a factory two-pole circuit
breaker, do not connect the load-side terminals of the
circuit breaker together; see Figure 8-2.
installation requires a 100--120-volt, 2-wire system, use
a single-pole circuit breaker. See Figure 8-3. When
connecting stator phase leads together, size the output
lead (L1) to handle the amperage. Use a jumper lead on
the line side of the circuit breaker to balance the load of
the generator set.
dial
clockwise
or
the
desired
voltage
If the
TP-6773 5/12a