WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
13.1
Specifications of standard wiring
components
Component
(a)
Power
MCA
1.4 A
supply cable
Voltage
Phase
Frequency
Wire sizes
Transmission wiring
User interface cable
indoor↔outdoor - maximum 1000 m (total
indoor↔user interface - maximum 500 m
Recommended field fuse
Residual current circuit
Must comply with applicable legislation
breaker
(a)
MCA=Minimum circuit ampacity. Stated values are maximum
values (see electrical data of combination with indoor units for
exact values).
13.2
To connect the electrical wiring to
the indoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ For instructions on how to connect the optional
equipment, see the installation manual delivered with
the optional equipment.
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
It is important to keep the power supply and the transmission wiring
separated from each other. In order to avoid any electrical
interference the distance between both wirings should ALWAYS be
at least 50 mm.
NOTICE
Be sure to keep the power line and transmission line apart
from each other. Transmission wiring and power supply
wiring may cross, but may NOT run parallel.
1 Remove the service cover.
2 User interface cable: Route the cable through the frame,
connect the cable to the terminal block (symbols P1, P2) and fix
the cable with a tie wrap.
3 Transmission cable: Route the cable through the frame,
connect the cable to the terminal block (make sure the symbols
F1, F2 match with the symbols on the outdoor unit), and fix the
cable with a tie wrap.
4 Appropriate measures (field supply): If installation is required
in
accordance
with
"11.1.2  Additional
refrigerant"  [ 4   13], connect them to the
requirements for CO₂
terminal block (symbols T1, T2). See
appropriate measures for appliances filled with
FXSN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P602815-1F – 2021.07
Class
50
71
112
2.0 A
2.9 A
220~240 V
1~
50/60 Hz
2
2.5 mm
(3‑core wire)
H07RN-F (60245 IEC 66)
0.75 to 1.25 mm² (2‑core wire)
H05RN-F (60245 IEC 57)
wiring length 2000 m)
16 A
installation
"13.3  To connect
CO₂" [ 4  20].
5 Power supply cable: Route the cable through the frame and
connect the cable to the terminal block (L, N, earth).
L N
a
a
Power supply and earth wiring
b
Service cover with wiring diagram
c
Transmission and user interface wiring
6 Fix the cables with a tie wrap.
7 Plastic clamp for tie wrap: Pass tie wraps through the plastic
clamps and fasten to fix the cables.
A-A'
a b
c
c
a
Small sealing (accessory)
b
Wiring
c
Plastic clamp for tie wrap
8 Divide the small sealing (accessory) and wrap it around the
cables to prevent water from entering the unit. Seal all gaps to
prevent small animals from entering the system.
9 Reattach the service cover.
Complete system example
▪ Example: 1 user interface controls 1 indoor unit.
a
Control box
IN/D OUT/D
F
F
F
F
1
2
1
2
L
N
L N
P
P
F
F
T
T
1
2
1
2
1
2
b
P
P
1
2
c
a
Outdoor unit
b
Indoor unit
c
User interface
d
Most downstream indoor unit
▪ Example: Group control or use with 2 user interfaces.
site
13 Electrical installation
P1P2 F1 F2 T1 T2
b
c
A
A
A'
A'
A
A
A'
A'
L
N
L
N
L N
L N
P
P
F
F
T
T
P
P
F
F
T
T
1
2
1
2
1
2
1
2
1
2
1
2
P
P
P
P
1
2
1
2
Installation and operation manual
L
N
d
L N
P
P
F
F
T
T
1
2
1
2
1
2
P
P
1
2
19