Mounting The Indoor Unit; Guidelines When Installing The Indoor Unit - Daikin FXSN71A2VEB Installation And Operation Manual

Co2 conveni-pack: indoor unit
Hide thumbs Also See for FXSN71A2VEB:
Table of Contents

Advertisement

11 Unit installation
Example: Total refrigerant charge in the system is 45 kg and room
3
volume is 300  m
. 45/300=0.15, which is >QLMV (0.074) and
<QLAV (0.18), therefore install at least 1 appropriate measure in the
room.
QLAV
70
65
a
60
55
50
45
40
35
30
25
20
15
10
5
0
0
50
100 150
200 250 300 350
400
450
  11‒2 Example graph for calculation
A
Refrigerant charge
B
Room volume
a
2 appropriate measures required
b
1 appropriate measure required
c
No measure required
For occupancies on the lowest underground floor of the
building
If the total refrigerant charge
(kg) divided by the room
(a)
3
volume
(m
) is...
<RCL
>RCL and ≤QLMV
>QLMV and <QLAV
>QLAV
(a)
For occupied spaces with a floor area exceeding 250 m
2
250 m
as the floor area for determination of the room volume
(Example: even if the room area is 300 m
is 2.5 m, calculate the room volume as 250 m
Example: Total refrigerant change in the system is 45 kg and room
3
volume is 300 m
. 45/300=0.15, which is >RCL (0.072) and <QLAV
(0.18), therefore install at least 2 appropriate measures in the room.
QLAV
70
65
a
60
55
50
45
40
35
30
25
20
15
10
5
0
0
50
100 150
200 250 300 350
400
450
  11‒3 Example graph for calculation
A
Refrigerant charge limit
B
Room volume
a
Installation is not allowed
b
2 appropriate measures required
c
1 appropriate measure required
d
No measure required
Installation and operation manual
14
QLMV
b
c
500
550
600 650 700 750 800 850 900 950 1000
B (m³)
...the number of appropriate
measures must be at least...
0
1
2
Value CANNOT be exceeded!
2
, use
2
and the room height
2
3
×2.5 m=625 m
)
QLMV
RCL
b
c
d
500
550
600 650 700 750 800 850 900 950 1000
B (m³)
INFORMATION
Even if there is no refrigerating system on the lowest floor,
where the largest system charge (kg) in the building
divided by total volume of the lowest floor (m
value for QLMV, provide a mechanical ventilation in
accordance with EN 378-3:2016.
11.2

Mounting the indoor unit

11.2.1

Guidelines when installing the indoor unit

INFORMATION
Optional equipment. When installing optional equipment,
also read the installation manual of the optional equipment.
Depending on the field conditions, it might be easier to
install the optional equipment first.
Installation options
INFORMATION
The unit can be used with bottom suction by replacing the
interchangeable plate by the air filter holding plate.
a
Air filter holding plate with air filter(s)
b
Interchangeable plate
▪ Ceiling strength. Check whether the ceiling is strong enough to
support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.
▪ For existing ceilings, use anchors.
▪ For new ceilings, use sunken inserts, sunken anchors or other
field supplied parts.
b
a
c
d
e
a
Anchor
b
Ceiling slab
c
Long nut or turn-buckle
d
Suspension bolt
e
Indoor unit
▪ Suspension bolts. Use M10 suspension bolts for installation.
Attach the hanger bracket to the suspension bolt. Fix it securely
using a nut and washer from the upper and lower sides of the
hanger bracket.
3
) exceed the
a
b
a
FXSN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P602815-1F – 2021.07