Guidelines When Installing The Ducting; Guidelines When Installing The Drain Piping - Daikin FXSN71A2VEB Installation And Operation Manual

Co2 conveni-pack: indoor unit
Hide thumbs Also See for FXSN71A2VEB:
Table of Contents

Advertisement

a
b
c
b
d
f
e:
630
a
Nut (field supply)
b
Washer (accessories)
c
Hanger bracket
d
Double nut (field supply)
e
Suspension bolt spacing
f
Suspension bolt
  11‒1 Suspension bolt spacing (A)
Class
50
71
112
▪ Level. Make sure the unit is level at all four corners using a level
or a water-filled vinyl tube.
b
a
a
Water level
b
Vinyl tube
NOTICE
Do NOT install the unit tilted. Possible consequence: If
the unit is tilted against the direction of the condensate flow
(the drain piping side is raised), the float switch might
malfunction and cause water to drip.
FXSN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P602815-1F – 2021.07
(mm)
A (mm)
738
1038
1438
11.2.2

Guidelines when installing the ducting

CAUTION
▪ Make sure the installation of the duct does NOT exceed
the setting range of the external static pressure for the
unit. Refer to the technical datasheet of your model for
the setting range.
▪ Make sure to install the canvas duct so vibrations are
NOT transmitted to the duct or ceiling. Use a sound-
absorbing material (insulation material) for the lining of
the duct and apply vibration insulation rubber to the
hanging bolts.
▪ When welding, make sure NOT to spatter onto the
drain pan or the air filter.
▪ If the metal duct passes through a metal lath, wire lath
or metal plate of the wooden structure, separate the
duct and wall electrically.
▪ Install the outlet grille in a position where the airflow will
not come into direct contact with people.
▪ Do NOT use booster fans in the duct. Use the function
to adjust the fan rate setting automatically (see
setting" [ 4  21]).
"15.1 Field
The ducting is to be field supplied.
1 Connect the canvas duct to the inside of the flange on both inlet
and outlet sides. Connect the canvas duct using the accessory
screws.
2 Connect the duct to the canvas duct.
a
b
d
e
f
a
Screws for duct flanges (accessory)
b
Flange (located on the unit)
c
Main unit
d
Insulation (field supply)
e
Canvas duct (field supply)
f
Aluminium tape (field supply)
▪ Fixing screws. When installing an air inlet duct, select fixing
screws that stick out 5  mm on the inside of the flange to protect
the air filter from damage during maintenance of the filter.
a
b
c
5 mm
a
Air inlet duct
b
Inside of the flange
c
Fixing screw
3 Wind aluminium tape around the flange and duct connection.
Make sure there are no air leaks at any other connection.
4 Insulate the duct to prevent condensation from forming. Use
glass wool or polyethylene foam 25 mm thick.
11.2.3
Guidelines when installing the drain
piping
Make sure condensation water can be evacuated properly. This
involves:
▪ General guidelines
11 Unit installation
c
b
a
f
e
d
Installation and operation manual
15