NOTE: The use of aluminum wire will void the warranty.
An individual ground circuit must be provided to each
pocket, do not daisy chain.
Component failure due to improper voltage application will
void the warranty.
The manufacturer reserves the right to make changes in
specifications at any time without notice or obligation.
IMPORTANT: A separate protected circuit must be
provided to each pocket.
It is necessary to have a power disconnect for each dryer.
These disconnects must be located within 30 feet (9
meters) of the dryer.
The dryer must be connected to the electric supply shown
on the data label.
Electrical Service Specifications
Gas Models Only
ELECTRICAL SERVICE SPECIFICATIONS (PER POCKET)
NOTES:
A.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY . Calculate/determine correct fuse
value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
B.
Circuit breakers are thermal-magnetic (industrial) motor curve type
ONLY . For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
SERVICE
WIRE
PHASE
VOLTAGE
SERVICE
120
2
Grounding
A ground (earth) connection must be provided and installed
in accordance with local, state, and national regulations or
codes of the country of destination. In the absence of these
codes, grounding must conform to applicable requirements
of the National Electrical Code ANSI/NFPA NO. 70-LATEST
EDITION, or in Canada, the installation must conform to
applicable Canada Standards: Canadian Electrical Codes
Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION. The
ground connection may be to a proven earth ground at the
location service panel.
Electrical Connections
A wiring diagram is located behind the control panel with
connection data.
If local codes permit, power to the dryer can be made by the
use of a flexible UL listed power cord/pigtail (wire size must
conform to rating of dryer), or the dryer can be hard wired
directly to the service breaker panel. In both cases, a strain
relief must be installed where the wiring enters the dryer.
113284 -1
APPROX.
CIRCUIT
AMP DRAW
BREAKER
60 Hz
50 Hz
14.6
15
10/26/12
Maytag Co.
WARNING
!
Fire Hazard
Use 12 gauge solid copper wire.
Use a UL listed strain relief.
Connect the white wire to the white wire from the
electric service; Connect the black wire to the
black wire from the electric service; Connect the
green wire to the green wire from the ground
connection.
Securely tighten all electrical connections.
Failure to do so can result in death, fire, or
electrical shock.
Single-Phase (1ø)
Wiring Connections / Hookup
The electrical input connections are made into the service
box located on the top toward the back of the dryer. The
ground connection is made to the copper lug, also provided
in this box. To gain access, the service box cover must be
removed.
Insert incoming white wire (neutral) for the top pocket into
the far right hand connection.
Insert incoming black wire (L1) for the top pocket into the
second from the right connection.
Insert incoming white wire (neutral) for the bottom pocket
into the third from the right connection.
Insert incoming black wire (L1) for the bottom pocket into the
far left hand connection.
Insert both incoming green wires (ground) into the copper
lug.
Tighten strain relief screws assuring to leave a 1/2" of slack
in the box.
Replace electrical box plate by inserting 3 screws previously
removed.
120 Application with Neutral