4 INSTALLATION
I
1eff
MIG/MAG
TIG
MMA
Fuse
anti-surge
type C MCB
Recommended fuse sizes and minimum cable area Warrior 500i CC/CV
Mains voltage
Mains cable area
Maximal current
rating I
max
I
1eff
MIG/MAG
TIG
MMA
Fuse
anti-surge
type C MCB
NOTE!
The mains cable areas and fuse sizes as shown above are in accordance with
Swedish regulations. Use the power source in accordance with the relevant national
regulations.
Supply from power generators
The power source can be supplied from different types of generators. However, some
generators may not provide sufficient power for the welding power source to operate
correctly. Generators with Automatic Voltage Regulation (AVR) or with equivalent or better
type of regulation, with rated power ≥40 kW, are recommended.
Connection instruction
The power source is factory set to 400 V AC (415 V AC for 0465 350 885 and 0465 350 886).
If another mains voltage setting is required, the cable on the printed circuit board has to be
moved and put in the correct position. Also the label, at the rear of the power source, marked
with the mains voltage setting must be updated. This operation must be done by a person
who has the appropriate electrical knowledge.
0463 362 201
Warrior 400i CC/CV
20 A
16 A
21 A
25 A
25 A
Warrior 500i CC/CV
380 V 3~ 50/60 Hz
4 × 6 mm²
38 A
28 A
23 A
29 A
35 A
32 A
- 13 -
19 A
16 A
20 A
25 A
25 A
400 V 3~ 50/60 Hz
4 × 6 mm²
36 A
27 A
22 A
28 A
35 A
32 A
18 A
14 A
19 A
20 A
20 A
415 V 3~ 50/60 Hz
4 × 6 mm²
35 A
26 A
26 A
26 A
35 A
32 A