10 .4 .3 Testing
Make the safe- and hazardous-area connections shown in figure 10.7 and carry out the
following procedure:
76
a
Set the current source or sink to 12mA
b
Adjust each trip potentiometer until the associated LED just
extinguishes.
c
With sources of 11.5mA and 12.5mA carry out the following
checks:
Table 10 .5
Current
High alarm
LED
11 - 12
8 - 9
11.5mA
On
closed
12.5mA
Off
open
Figure 10.7: Test circuit for MTL5314
Low alarm
Relay
10 - 11
LED
11 - 12
7 - 8
open
Off
closed
On
closed
Relay
10 - 11
8 - 9
7 - 8
open
closed
open
INM 5500 Rev 11