Eaton Crouse-Hinds MTL5500 Series Instruction Manual page 71

Isolating interface units
Hide thumbs Also See for Crouse-Hinds MTL5500 Series:
Table of Contents

Advertisement

8 .3 .3
Output Measurements
1.
2. The measured current imbalance (A2) over this range should not exceed ± 20mA
8 .3 .4
Output Measurements
1.
2. The measured current imbalance (A2) over this range should not exceed ± 20mA
63
Modules: MTL5541A & MTL5544A
RV1
10kW lin.
24V
+
250W
+
Figure 8 .7: AI test circuit #3 "active i/p"
Adjust RV1 to vary the current (A1) through the range 4 to 20mA.
Modules: MTL5541AS & MTL5544AS
RV1
10kW lin.
24V
+
250W
+
Figure 8 .8: AI test circuit #4 "active i/p - o/p sinking"
Adjust RV1 to vary the current (A1) through the range 4 to 20mA.
+
A1
I
I
A2
o
i
i/p
o/p
+
+
A1
I
I
A2
o
i
250W
+
i/p
o/p
24V
+
INM 5500 Rev 11