10 .2 .3 Testing
Make the safe- and hazardous-area connections shown in figure 10.2, and check the status
of the output contacts for each channel in turn (with a 22kΩ resistor connected to the other
channel) as shown in the table 10.1.
Table 10 .1
Phase
reverse
switch
Normal
Reverse
Reverse
Normal
Normal
Normal
Normal
70
Figure 10 .2: Test circuit for MTL5018AC
Line
Input
fault
switch
detection
(SW)
Off
a
= 7 _ 9mA
Off
I
SC
Off
Open
= 7.5 _ 9.5V
On
V
OC
On
a
On
b
On
c
Output
Output
relay
relay
(11-12, 8-9)
(10-11, 7-8)
Closed
Open
Open
Closed
Closed
Open
Open
Closed
Open
Closed
Open
Closed
Closed
Open
Channel
Line fault
status LED
LED
(yellow)
(red)
On
Off
Off
Off
Off
Off
Off
On
Off
On
Off
Off
On
Off
INM 5500 Rev 11