Declaration of Conformity A printed version of the Declaration of Conformity has been provided separately within the original shipment of goods. However, you can find a copy of the latest version at http://www.mtl-inst.com/certificates INM9189 Rev 4...
Page 4
No changes to any of the components that might impair their explosion protection are permitted. If any information provided here is not clear: Contact Eaton’s MTL product line or one of its representatives. Note: Improper installation and operation of the assembly can result in the invalidation of the guarantee.
9189 - Redundant Fieldbus Power Supply 8-segment Power A 919x-FP input power supply module F809F-Plus 9181 -CA -P* diagnostic carrier module Segment outputs 1 - 4 Segment Diagnostic outputs 5 - 8 segment terminals Figure 1 .1 - 9189 showing some key components OVERVIEW This manual explains the installation and maintenance procedures for the 9189 Redundant Fieldbus Power Supplies and must be read in association with the...
DESCRIPTION The system provides segment current capacity in 250mA increments, up to 500mA, and then offers redundancy with the provision of an additional 250mA module, which is connected in a load-sharing manner, to achieve an N+1 type of configuration. Each 919x-FP module will support 4 segments, so two “groups” of modules are required to support 8-segments.
Page 7
Plus * This dimension applies if the F809F-Plus diagnostic module is not used. Figure 2 .2 - Dimension drawing with all modules fitted INM9189 Rev 4...
Power A – Power B – Figure 2 .3 - Power distribution to modules 2 .3 Alarms Each 919x-FP module monitors the output of the four fieldbus segments and indicates an alarm (by means of a built-in, normally-closed relay) if any of the segments is shorted, or its output falls below the ‘minimum output voltage threshold’.
The input power, field segment and alarm wiring connections are available with the option of either pluggable screw terminals (9189-CA-PS) or pluggable spring-clamp terminals (9189-CA-PC). The pluggable connections are screw-retained providing a reliable connection in an industrial environment. SYSTEMS AND COMPONENTS The system and component part numbers and their descriptions are given here.
MECHANICAL 4 .1 Mounting Orientation The optimum orientation for the 9189-CA-P* carrier is mounted on a vertical surface using a horizontally aligned DIN-rail, or surface mounted in the same orientation - see Figure 4.1. This method of mounting ensures optimum heat dissipation from the 919x- FP Power Supply Modules, and an operating temperature range of –20°C to +60°C.
4 .3 DIN-rail mounting option The carrier is designed for mounting on 35mm x 7 .5mm T-section “top hat” DIN rail to EN50022 and uses four built-in DIN clamp tabs to hold it on the rail. 4 .3 .1 To mount on DIN rail The power modules at each end of the carrier must be removed to obtain access to the DIN-rail clamp screws.
Page 12
NOTE The carrier hangs on the fixings and so there must be a minimum of 10mm top clearance above the carrier to enable it to be located over the screw heads before it is lowered onto the M4 fixings. 43.4 200 TYP.(H) TOP clearance when mounted Horizontally.
ELECTRICAL CONNECTIONS The DC power, Host and Field Segment connectors are pluggable and available in a screw terminal version (-PS) or a spring-clamp version (-PC). See Figures 5.1 & 5.2 for details. The terminals can accept the following conductor sizes: Type Conductor size Screw terminals...
5 .3 Host connections There are eight Host segment connectors, each providing (+), (–) and cable screen (S) connections. See section 5.5 for information on cable screen grounding. Connection Pin No . Connection Pin No . Segment 1 (+) Segment 5 (+) Segment 1 (S) Segment 5 (S) Segment 1 (–)
Figure 5 .3a Figure 5 .3b 5 .6 Power Modules WARNING ! The 919x-FP Power Module can be “hot-swapped” without the risk of damaging it, but a gas clearance certificate is required to carry out this action in a Zone 2 hazardous area or Division 2.
ALARM Seg 1 - 4 Seg 5 - 8 Figure 5 .5 - Carrier alarm “circuit” If a 919x-FP power module is removed or omitted, its position on the carrier should be filled with a blanking module (part number: 9197-BLK). This will maintain continuity of the “alarm circuit”...
TESTING 6 .1 919x-FP Status and Alarm LEDs Each Power Module is fitted with five LEDs, four green ones to indicate the status of individual segments and one red one to signify a Fault/Alarm condition. FAULT Segment Module Alarm System status LED(s) location contacts...
ATEX INFORMATION The Essential Health and Safety Requirements (Annex II) of the EU Directive 2014/34/ EU [the ATEX Directive - safety of apparatus] requires that the installation manual of all equipment used in hazardous areas shall contain certain information. This annex is included to ensure that this requirement is met.
8 .5 Marking Each certified component is marked in compliance with the Directive and CE marked with the Notified Body Identification Number. This information applies to products manufactured during or after the year 2011. For full certification information visit www.mtl-inst.com/support/certificates/ Product labels (showing certification information) INM9189 Rev 4...