• No changes to any of the components that might impair their explosion protection are permitted. If any information provided here is not clear: Contact Eaton’s MTL product line or one of its representatives. NOTE Improper installation and operation of the module can result in the invalidation of the guarantee.
Spur Surge protection modules (part no. FS32). Surge protection of the OVERVIEW fieldbus trunk connection can be provided using protector type TP32-I-NDI; consult Eaton - MTL for pre-engineered enclosure systems containing appropriate electrical and mechanical hardware. This manual explains the installation and maintenance procedures for the...
MECHANICAL INSTALLATION Mounting considerations Trunk WARNING! from HOST Equipment must be mounted and connected in accordance with intrinsically the Conditions for Safe Use on the certificate. See section 7.2. safe See Figure 3.1 for the dimensions and fixing locations. When choosing an enclosure or mounting position for a Fieldbus Barrier module the following points should be taken into account.
The barrier module wiring should be installed in accordance with IEC/EN60079-14 and local installation standards but Eaton - MTL recommends that cable trunking be used inside the enclosure to assist in providing separation. Cable management may also be required for the spur cables, as deemed appropriate by local and site standards.
4.2.2 Cable shield grounding ELECTRICAL INSTALLATION The cable shield is normally electrically isolated from the protective earth ground, although the two may be deliberately interconnected in some WARNING! grounding arrangements, as described below. Before starting any electrical installation work, ensure that the The module can be configured by the user to either of two grounding methods incoming trunk connection is isolated from any source of power.
Currently, the recommended method of protection involves the use of a TP-32 surge protection module, available from Eaton - MTL, but a similar 4.3.1 Trunk Terminal wiring alternative may be chosen.
Final checks Before fitting/closing the lid on the barrier enclosure, check that: Spur wiring connections • all wire terminal connection screws are sufficiently tightened. • all enclosure cable glands and any blanking plugs are tightened to provide a good seal. •...
5.2.2 Adding a Spur Surge module TROUBLESHOOTING Use the following procedure and reference to Section 4.6 may help. a) Loosen the two screws securing the pluggable, spur-wiring connector to the barrier Each Fieldbus Barrier module is fitted with LED indicators to assist the user with and unplug it.
Spur LEDs ATEX INFORMATION The Essential Health and Safety Requirements (Annex II) of the EU Directive Colour State Description 2014/34/EU [the ATEX Directive - safety of apparatus] requires that the installation manual of all equipment used in hazardous areas shall contain certain information. Green Steady Channel powering spur, spur OK...
Notified Body Identification Number. This information applies to products manufactured during or after the year 2018. THIS PAGE IS LEFT INTENTIONALLY BLANK For full certification information visit Eaton - MTL products website at : www.mtl-inst.com/resources/datasheets Search on the product family name and type number to view datasheets and certificates.