10 .4 .2 Trip calibration
Switches and multiturn potentiometers for setting the trip points are located on top of the unit
(see figure 10.7). For each of channels A and B:
Figure 10 .7:
Top label
for MTL5314
75
Terminal
Function
1
Current input
2
Transmitter supply +ve
3
Common
7
Trip B (NC)
8
Trip B (COM)
9
Trip B (NO)
10
Trip A (NC)
11
Trip A (COM
12
Trip A (NO)
13
Supply –ve
14
Supply +ve
i
Set trip switch to H (high) or L (low) as required (see table 10.4
for relay operation).
ii
Set input current to the required value for trip-point.
iii
Adjust SET A/SET B until LED A/B is on: then slowly adjust until
LED goes out.
iv Relays are energised in normal operation and de-energised when
tripped. A lit LED shows the safe condition (not tripped).
Table 10 .4
Trip
Operation
switch
A or B
H (high)
Input > trip setting
H (high)
Input < trip setting
L (low)
Input > trip setting
L (low)
Input < trip setting
-
-
PWR
A or
Relay contacts
LED
B
11 - 12
10 - 11
LED
8 - 9
7 - 8
•
open
closed
closed
open
closed
open
•
open
closed
•
•
open
closed
INM 5500 Rev 11