Eaton Crouse-Hinds MTL5500 Series Instruction Manual page 72

Isolating interface units
Hide thumbs Also See for Crouse-Hinds MTL5500 Series:
Table of Contents

Advertisement

8 .3 .5
Output Measurements
1.
2. With the LINK disconnected and Safety Drive ON, V2 should drive to >+50mV with the
8 .3 .6
Output Measurements
1.
2. The green PWR LED should go to a steady state after initially flashing. If the flashing does not
3. Vary the resistance box setting between 10 and 400Ω and confirm the output voltage varies.
4. Short circuit the input and check that the output voltage is ≤ 51.6mV after 5 seconds.
5. Open circuit the input and check that the output voltage is ≤ 2.071V after 5 seconds and that
6. Set the input resistance to 200Ω and check that the output voltage settles to 1.0V ± 32mV
64
Module: MTL5581
LINK
RV1
100W
39kW
Figure 8 .9: AI test circuit #5 "mV input"
Note: V1 should be capable of measurement to within 1mV.
With the LINK connected, vary output V2 between 0 and 50mV using RV1. V1 should show
<50mV variation. (Note: Safety Drive can be ON or OFF )
switch set to '+', or <–50mV with the switch set to '–'.
Module: MTL5582/5582B
Resistance
box
0 - 400Ω min.
Figure 8 .10: AI test circuit #5 "Resistance input"
Set Sw1 & Sw2 to ON for 3-wire operation. Set the resistance box to any value between 10
and 400W and switch on power supply.
stop after 5 seconds then either the setup wiring is faulty or the unit is faulty.
the green PWR LED is flashing.
V1
i/p
o/p
+
4-wire
5
3-wire
4
9
2-wire
i/p
3
+
10
11
1
o/p
12
V2
+
+
V
47mV - 2.100V
+
5.0mA ± 150µA
+
INM 5500 Rev 11