4.4.4 Bracket Mounting Procedure

If you are using an optional bracket, start with Step 1. For an existing bracket, start with Step 2.
1. Refer to
Figure
(60.4mm) actual OD) for a horizontal or vertical pipe, and install a "U" bolt around the pipe
and through the holes in the bracket. Secure the bracket with the nuts and lock washers
provided.
Figure 6 – ST 700 Standard Transmitter - Angle Mounting Bracket
2. Align the appropriate mounting holes in the transmitter with the holes in the bracket. Use the
bolts and washers provided to secure the transmitter to the bracket; see the following
variations.

Table 5 - ST 700 Standard Transmitter - Mounting Bracket procedure

DP with double-ended process heads and/or
remote seals
ST 700 standard transmitter models only.
In-line GP: STG7x0 and STG7xL
AP models: STA7xL and STA72x, STA740
Dual-head GP and AP
Example: Inline model mounted to an optional angle bracket. See
Revision 13
6. Position the bracket on a 2-inch (50.8mm nominal diameter, 2.38"
Secured to a Horizontal or Vertical Pipe
Transmitter Type
ST 700 SmartLine Pressure Transmitters User's Manual
Use Hardware
Alternate mounting holes in the ends of the
heads
The smaller "U" bolt provided to attach the
meter body to the bracket. See the
following example.
Mounting holes in the end of the process
head.
Figure
7.
Page 17