ATT 2100 / ATT 2200 Smart Temperature Transmitter
Operation Manual
M2X00-E01H
AUTROL Series
Operation Manual : M2X00-E01H
ATT 2100/ATT 2200
Smart Temperature Transmitter
Operation Manual
www.autroltransmitter.com
Autrol Corporation of America
Information on this manual can be changed without an advance notice.
*

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ATT 2100 and is the answer not in the manual?

Questions and answers

Summary of Contents for Autrol ATT 2100

  • Page 1 ATT 2100 / ATT 2200 Smart Temperature Transmitter Operation Manual M2X00-E01H AUTROL Series Operation Manual : M2X00-E01H ATT 2100/ATT 2200 Smart Temperature Transmitter Operation Manual www.autroltransmitter.com Autrol Corporation of America Information on this manual can be changed without an advance notice.
  • Page 2 This manual is for general user to understand the installation and operatation of ATT 2100 / ATT2200 Smart Temperature Transmitter efficiently. Before handling Autrol series device, all users have to be fully understand to control or get some technical support.
  • Page 3: Table Of Contents

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Table of Contents 1. INTRODUCTION 1-1. USING THIS MANUAL 1-2. OVERVIEW OF TRANSMITTER 1-3. SOFTWARE COMPATIBILITY 1-4. TRANSMITTER COMPONENTS 2. HANDLING CAUTIONS 2-1. UNPACKING 2-2. MODEL AND SPECIFICATIONS CHECK 2-3. STORAGE 2-4. SELECTING THE INSTALLATION LOCATIONS 2-5.
  • Page 4 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 3-5. FAIL MODE ALARM 3-6. EEPROM-WRITE ENABLE/DISABLE MODE JUMPER 3-7. CONFIGURATION OF ALARM AND SECURITY JUMPER PROCEDURE 3-8. CONFIGURATION OF ZERO AND SPAN PROCEDURE 3-9. CONFIGURATION OF ZERO POINT ADJUSTMENT PROCEDURE 3-10. COMMISSIONING ON THE BENCH WITH HHT 3-11.
  • Page 5 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 4-15. ENVIRONMENTAL CONSIDERATIONS 5. ON-LINE OPERATION 5-1. OVERVIEW 5-2. SAFETY MESSAG 5-3. CHECK OUTPUT 5-4. BASIC SETUP 5-5. DETAILED SETUP 5-6. INFORMATION VARIABLE SETUP 5-7. DIAGNOSITICS AND SERVICES 5-8. CALIBRATION 6. MAINTENANCE 6-1. OVERVIEW 6-2.
  • Page 6: Introduction

    M2100-REV-G Chapter 1 Introduction The ATT 2100/ATT 2200, Smart Temperature Transmitter is correctly calibrated at the factory before shipment. To ensure correct and efficient use of the instrument, please read this manual thoroughly and fully understand how to operate the instrument before operating it ①...
  • Page 7: Overview Of Transmitter

    Thermocouple, RTD, mV, Resistance for temperature measurement. ATT 2100 has a true draft analog range from 0 to 20mA offering that features that a temperature range or after convert analog range to HART (Communication) digital signal transmit for control systems like DCS, PLC.
  • Page 8: Transmitter Components

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Transmitter Components The components and figure of Autrol Smart Temperature Transmitter ATT 2100 is as follow. Figure 1-1. Model ATT 2100 Transmitter Exploded View (Housing) Figure 1-2. TRANSMITTER COMPONENTS...
  • Page 9: Handling Cautions

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Sensor Element connection terminal Sensor Element connection terminal Chapter 2 Handling Cautions This chapter consists of cautions for transmitter handling and storage, selection of installation locations, insulation and explosion structure, etc. [Quick Reference Manual]...
  • Page 10: Storage

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Calibration on a a) Basic Configuration HHT, Calibration Room b) Input RTD &TC, TC Cold Juction Calibration, DAC Galvanometer Trim a) Where ambient temperature is not fluctuated InstallationLocation (Engineering) b) Where corrosion happens by chemical materials, etc.
  • Page 11: Selecting The Installation Locations

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G (a) It is not exposed to rain or water. (b) It suffers minimum vibration and shock. (c) If possible, it is preferable at normal temperature and humidity (approx. 25°C, 65% RH). However, it has an ambient temperature and relative humidity within the following ranges.
  • Page 12: Insulation Resistance Test And Dielectric Strength Test

    (e) After completing this test, slowly decrease the voltage to avoid any voltage surges. 2.8 Installation of Explosion Protected Type Transmitters 2.8.1 KOSHA Certification Caution for KOSHA Flameproof is following type. Model ATT 2100 diaphragm sealed for potentially explosive atmosphere: [Note1] Type of Protection and Marking Code: Ex d ⅡC T6 ...
  • Page 13 [Note5] Maintenance and Repair The instrument modification or parts replacement by other than authorized representative  of Autrol is prohibited and will void KOSHA Flameproof 2.8.2 KEMA / ATEX Certification ATEX Certification number : KEMA08ATEXxxxx CE 0344 II 2 G Note 1.
  • Page 14: Emc Conformity Standards

    EMS (Immunity): EN50082-2 Autrol recommends customer to apply the Meta l conduct Wiring or to upset he twisted pair Shield Cable for signal wiring to conform the requirement of EMC Regulation, when customer installs AUTROL Series Transmitters to the plant.
  • Page 15: Safety Message

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 3.2 Safety Message Procedures and instructions in this chapter may require special precautions to ensure the safety of the personal performing the operations. Information that raises potential safety issues is indicated by warning symbol(▲). Refer to the following safety messages before performing an operation preceded by this symbol.
  • Page 16 M2100-REV-G 3.4 Connection of Sensor ATT 2100 Temperature Transmitter can input sensors such as RTD, Thermocouple(TC) and Resistance. In case RTD, 2Wire/3Wire and 4Wire Sensor connection is applicable. Also, 2Wire TC(B, E, J, K, N, R, S, T) Sensor input is applicable. Below pictures are present sensor connections using RTD &...
  • Page 17: Fail Mode Alarm

    ATT2200 connector & HART communication. 3-5. Fail Mode Alarm AUTROL® Smart Temperature Transmitter automatically and continuously performs self-diagnostic routines. If the self-diagnostic routines detect a failure, the transmitter drives its output outside of the normal saturation values. The transmitter will drive its output low(down) or high(up) based on the position of the failure mode alarm jumper .
  • Page 18 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Table 3-2. Fail Mode Fail Mode and EEPROM Write Selection Switch on CPU Board EEPROM Writing [Down of Left] Alarm Down (4mA) [Down of Right] EEPROM Protect [Up of Left] Alarm Down (20mA) [Up of Right] Figure 3-1.
  • Page 19 2) EEPROM Write Selection Figure 3-3. CPU Module Fail Mode, EEPROM-Write Selection Jumper Switch There are two security methods in ATT 2100. Following this. (1) Security Jumper: protect to writing configuration parameters of transmitter. (2) Physical removing Zero and Span Magnetic Buttons of Transmitter: you are not able to regulate Zero and Span in Local.
  • Page 20: Configuration Of Alarm And Security Jumper Procedure

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 3.6.2 Zero and Span Magnetic Button To remove Magnetic Button, you can't configure Zero and Span in Local. 3.7 Configuration of Alarm and Security Jumper Procedures To change Jumper's position, follow this. (1) If install the transmitter, cutoff power.
  • Page 21: Configuration Of Zero Point Adjustment Procedure

    (Offset is variable. Therefore, PV value and Zero point can be configured by changing Offset value). There are two ways for Zero Point Adjuntment of ATT 2100 A. Using Zero/Span button attached on transmitter B. Using HART communicator, HHT, etc.
  • Page 22 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Zero button is pushed, and 0.01% increases whenever Span button is pushed. Pushing button continuously makes speed fast or slow. If you push Zero/Span button over 3 seconds or do not push any button over 30 seconds. “-Zo-“ message shows in LCD window. By this message, all procedures finish.
  • Page 23 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Menu Tree of ATT 2100 for external button function. NORMAL Zero Zero zero zero Span Span span span Menu 1 Trim span 11 Z-TRIM Zero Trim zero+span span 12 Z-ADJ Zero Adjustment span...
  • Page 24 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 3.10 Shop Commissioning using HHT Commissioning consists of testing the transmitter, testing the loop, and verifying transmitter configuration data. APT-3100 Pressure Transmitter may be commissioned using HHT of HART supported either before of after installation.
  • Page 25: Lcd Messages

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 3-11. Description of LCD Messages ATT-2100 Transmitter inform any cautions and failures to user through LCD during operation. Measured Value(Temperature, Resistance, Voltage, etc) and Unit(℃, ℉, R, T, mV, ohm, etc) will be shown on LCD during normal working.
  • Page 26 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G condition when the failures are removed. This message present for failures of the sensors such as short circuit, breaking down of wire, abnormal wiring, and back to normal condition when the failures are removed.
  • Page 27 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Below messages present for setting Zero / Span using the buttons on the top of transmitter. First two messages are normal setting conditions and following two messages are abnormal setting conditions. Shown when normally set Zero the current value..
  • Page 28: Installation

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Chapter 4 Installation 4.1 Overview The information in this chapter 4 covers installation considerations. Dimensional drawings for Model ATT- 2100 variation and mounting configuration are included in this chapter. 4.2 Safety Message Procedures and instructions in this chapter may require special precautions ensure the safety of the personnel performing the operation.
  • Page 29: Commissioning On The Bench With Hand-Held Terminal

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Commissioning on the bench with Hand-Held Terminal After and before installation, You can handle upon commissioning. However, for correctly handling and knowing the function, before installation you have to handle upon commissioning on the bench with Hand-Held Terminal.
  • Page 30: General Considerations

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 4.5 General Considerations This transmitter uses temperature sensors. It transfer electrical signal minutely to 4~20mA analog signal. Thus mount the transmitter close to the process and use a minimum of sensor length to achieve best accuracy.
  • Page 31 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 4.8.2 Selecting the Wiring Materials (1) Use over 600V PVC shielded wire or standard lead line of same class or cable. (In order to ensure proper communication use 24 AWG or lager wire, and do not exceed 1500 meters.) (2) Use the shielded wire in electrical noise effected area.
  • Page 32: Wiring

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G ■ Wiring Figure 4-3. Picture of Terminal Board of Transmitter ▲ Warning Explosion can result in death or serious injury: ◈ Do not remove the transmitter covers in explosion environments when the circuit is alive.
  • Page 33 Operation Manual M2100-REV-G 4.9 Loop Configuration AUTROL Series Transmitters use a two-wire system for power supply, 4~20mA analog signal transmission and HART digital transmission. DC Power Supply is required for the transmitter loop. The Transmitter and distributor are connected as shown below.
  • Page 34: Wiring Installation

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G (3) Intrinsical Safety Type (Saftey Barrier must be connected to inner Loop) Hazardous Location <-------------> Nonhazardous Location Transmitter terminal box Distirbutor Receive (Power supply unit) Instrument Safety barrier 4.10 Wiring Installation 1) General-use Type and intrinsically Safe Type make cable wiring using metallic conduct or...
  • Page 35 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G (2) KOSHA Flameproof Type Wire cables through a flameproof packing adapter, or using a flameproof metal conduct. (a) Wiring cable through flameproof packing adapter for KOSHA flameproof type (see Figure 4-4b) (b) Use only flameproof packing adapter by KOSHA.
  • Page 36 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G (b) Flameproof metal conduct wiring (c) A seal fitting must be installed near the terminal box connections port for a sealed construction. (d) Apply a non-hardening sealant to the threads of the terminal box connection box, flexible metal conduct and deal fitting for waterproofing.
  • Page 37: Grounding

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 4.11 Grounding (a) Grounding should satisfy KS requirements (grounding resistance, 10 Ohm or less). Grounding is required below 10 Ohm for explosionproof and intrinsic safety. [Note] In case of with Built-in Lightening Protector, Grounding should satisfy Special KS requirements (grounding resistance, 10 Ohm or less) (b) There are ground terminal on the inside and outside of the terminal box.
  • Page 38: Power Supply Voltage And Load Resistance

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 4.12 Power Supply Voltage and Load Resistance When configuring the loop, make sure that the external load resistance is within the range in the figure below. Since the voltage of transmitter terminal input is same as follows.
  • Page 39: Temperature Sensor Installation

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 4.13 Temperature Sensor Installation NOTE 1. Install per local installation codes. Qualified cable entry or stopping box required. (For Using ATEX explosion proof certificate, Must be use ATEX approved cable entry) 2. Temperature sensor assembly must be qualified for appropriate area classification.
  • Page 40: Mechanical Considerations

    Operation Manual M2100-REV-G 4.14 Mechanical Considerations Figure 4-6 is transmitter dimensional drawings of ATT 2100. Figure 4-6 ATT 2100 Outline Dimension Drawing 4.14.1 Mounting To use the cadence carrier from the environment where the vibration is heavy and must install the transmitter.
  • Page 41: Environmental Considerations

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 4.15 Environmental Considerations 4.15.1 Effect of Ambient Temperature You have to install at -40℃~85℃, operating ambient temperature range. If predicted heat seems to exceed or equivalent to ambient temperature range limit, you have to consider additional method to cutoff the process heat.
  • Page 42: On-Line Operation

    Chapter 5 On-line Operation 5.1 Overview This chapter describes to configure function of ATT 2100 SMART Temperature Transmitter. Transmitter can be configured to On-Line or Off-Line mode. In On-Line Configuration Mode, you must connect configuration such as HHT (Hand Held Terminal), etc. Configuration data inputs in Working Register of HHT and this data is sent to corresponding transmitter.
  • Page 43: Check Output

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 5.4 Check Output Before other handle transmitter to on-line, you must examine and confirm whether transmitter currently operate and suitably configure progress variable. 5.4.1 Process Variable We use two progress variable in ATT-2100 SMART Pressure Transmitter pressure value is Primary Variable and temperature value of pressure value configure SV(Secondary Variable) with fixed value.
  • Page 44 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Meaning Damping time is to reach 63.2% of target value 5.7 Configuration of Information Variable 5.7.1 Set Tag Tag variable is better easy method to classify to transmitter in multi transmitter install environment.
  • Page 45: Calibration

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 5.9 Calibration Scaled system implements by calibrating the transmitter. Trim function have several function for the calibration. Smart transmitters operate differently than analog transmitter. A Smart transmitter uses a microprocessor that contains information about the sensor's specific characteristics in response to pressure and temperature inputs for calculating Process Variable.
  • Page 46: Maintenance

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Chapter 6 Maintenance Overview This chapter describes breakdown diagnostic and maintenance. Safety Message When operation, it requires specially notice for the safety of operator. Information that raises potential safety issues is indicated by a warning symbol(▲). Refer to the following safety messages before performing an operation proceeded by this symbol.
  • Page 47: Hardware Diagnostics

    ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 6.3 Hardware Diagnostics If you suspect a malfunction despite the absence of any diagnostic messages on the HHT follow Table 6- 1 described here to verify that transmitter hardware and process connections are in good working order.
  • Page 48: Hardware Maintenance

    M2100-REV-G 6.4 Hardware Maintenance Autrol ATT 2100 Smart Transmitters have no moving parts and require a minimum of scheduled maintenance. Both transmitters feature a modular design for easy maintenance. If you suspect a malfunction, check for an external cause before performing the diagnostics as discussed later in this section.
  • Page 49 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 6.4.2 Disassembling the Electronics Housing The transmitter is designed with dual-compartment housing; one contains the electronics module, and the other contains all wiring terminals and the communication receptacles. Figure 6.2 Structure of Housing 6.4.2.1...
  • Page 50 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G [Note2] The transmitter EEP-Write Jumpers and failure mode are located on the front of the electronics module. When it will be replaced for a new one, make a same jumper location. Figure 6-3 Structure of Electronics Module inner Transmitter 6.4.2.2 Fail Mode and Jumper Switch of EEPROM-write...
  • Page 51 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G 2) Connections of Sensors Connections with Sensors(Thermocouple, RTD) are as follows.
  • Page 52 ATT 2100 TEMPERATURE TRANSMITTER Operation Manual M2100-REV-G Message Description Remarks ADRE ADC Initial Error 2-tr Zero trim Button Pressed 2ero Zero Button Pressed span span Button Pressed ber1 Button Input Sequence Error 2ter Zero offset value over -tr- Trim Done...