Page 1
® Operation Manual: 150414-2100-OM01V7.X AUTROL Series ATT2100 AUTROL® ATT Series Operation Manual : 150414-2100-OM01V7.X ATT2100 Smart Temperature Transmitter Operation Manual AUTROL CORPORATION OF AMERICA www.autroltransmitters.com...
Page 2
ATT2100 Smart Temperature Transmitter This manual is made available to assist general users with instructions for proper installation and operation of an Autrol® ATT2100 Smart Temperature Transmitter. Before handling the ATT2100 transmitter, all users should read this manual to familiarize with recommended practices.
Page 3
® Operation Manual: 150414-2100-OM01V7.X AUTROL Series ATT2100 Table of Contents Chapter 1. Introduction 1.1 Using this manual 1.2 Overview of the transmitter 1.3 Software Compatibility 1.4 Transmitter Components Chapter 2. Handling 2.1 Unpacking and specifications Check 2.2 Models and specifications Check 2.3 Storage...
Autrol® ATT series Smart Temperature Transmitters. Chapter 5 On-line Operation Chapter 5 describes the configuration process and how to use basic and advanced Autrol® ATT series Smart Temperature Transmitter software functions during configuration. Included in these sections are details on using: ①Sensor Zero Adjustment...
(digital signal superimposed over the analog output) communication that allows transmitting additional digital parameters/diagnostic information for advanced control systems like DCS, PLC, SCADA, RTU, etc. All ATT series transmitters have an explosion proof rated housing (standard cast aluminum, copper free epoxy coated or optional SUS316) protected for outdoor NEMA 4X and classified hazardous areas Class I, Div.
1.3 Software Compatibility This manual is current for firmware revision 7.x. Autrol® Smart Temperature Transmitters are shipped from the factory with the most up to date firmware. However, as product developments and new features are released a firmware update becomes necessary to incorporate these new changes. As such, transmitters with older firmware may restrict certain functions when communicating with an external HHT(Model 275 /375 or 465 HART®...
Autrol® Series 1.4 Transmitter Components The various components of an Autrol® ATT Series Smart Temperature Transmitter are included in Figure 1-1 Exploded View. Figure 1-2 below is the list of parts referenced in Figure 1-1. Figure 1-3 has outlline dimensions in millimeters: for inches divide by 25.45.
250 – 550 Ohm. - For mounting transmitter, an appropriate bracket Mounting and (Mounting Operat ion Manual:111508-2100-OM01V7.X (Autrol BA or BF type) should be used. Installation Installation) ® AUTROL Series - Transmitter should be fixed firmly to its bracket.
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series 2.2 Models and Specifications Check The model name and specifications are indicated on the top nameplate fixed to the transmitter. Please check your specification and model supplied for your installation. Please ensure that LRL(Lower Range Limit)/URL(Upper Range Limit), min/max span specifications and sensor type are in line with your application requirements.
Page 11
AUTROL Series done, Autrol has provided this capability using the Zero and Span buttons. Short description: adjust the accurate temperature source (example, a temperature bath) to the zero point, example 0 deg. F., push the Zero button (5 seconds), wait for display to show ZERO, then push Zero button again: display is “ZR”...
Thereafter, always use the transceiver outside the area affected by noise. 2.9 Insulation Resistance Test and Dielectric Strength Test All ATT series transmitters are subjected to insulation resistance and dielectric strength tests (at the factory) prior to shipment. Normally these tests are not required to be duplicated in the field.
Manual:111508-2100-OM01V7.X inside the terminal housing accessible by opening the rear cover. The ground ® AUTROL Series screw can be easily identified from its ground symbol marking. * External Ground Lug: This is located on the right side of housing and accessible from outside.
Page 14
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series aintenance and Repair Instrument modification or parts replacement by other than authorized factory representatives is prohibited and will void flameproof certification. 2.10.1 KOSHA Certification Caution for KOSHA Flameproof is following type. [Note1] Model APT3100 sealed for potentially explosive atmosphere: Type of Protection and Marking Code: Ex d ⅡC T6...
3.1 Overview This chapter includes instructions to facilitate pre-installation set up procedures for an AUTROL®ATT series SMART Temperature Transmitter. Tasks that can be performed on the bench prior to installation in the field are also explained in this chapter. 3.2 Safety Message Procedures and instructions in this chapter may require special precautions to ensure the safety of the personnel performing these operations.
3.4 Fail Mode Alarm Fail Mode Selection Jumper Switch of LCD Module The AUTROL® Smart Temperature Transmitter automatically performs real time self- diagnostic routines and displays error codes on its local LCD display (M1 option if ordered) that can be used for troubleshooting. In addition, the self-diagnostic routine is also designed to drive transmitter current output outside of the normal saturation values in case a fault mode is detected.
Page 17
[Table 3-2 Jumper/DIP settings for Fail Mode Selections] FAIL MODE UP – (place jumper to left) FAIL MODE DOWN- (place jumper to right) 3.4.2. <Fail Mode Selection DIP Switch on CPU Module > Operat ion Manual:111508-2100-OM01V7.X ® AUTROL Series Fail Mode Select Jumper Switch on LCD Module...
Page 18
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series Figure 3-1 Fail Mode Selection Jumper Switch on LCD Module CPU Module DIP Switch #: (1) EEPROM Write Selection (2) Fail Mode Selection Figure 3-2. Fail Mode Selection DIP Switch location on CPU Board Note: Use DIP switch (2) on right shown in Fig 3-4 for Fail Mode Selection.
(1)shownon right in Fig 3-4 is for Fail Mode Selection as explained in earlier Chapter 3.4. Operat ion Manual:111508-2100-OM01V7.X ® AUTROL Series DOWN DIP(1) = WR_EN (EEPROM Write Enable) DOWN : ENABLE CONFIGURATION CHANGES : DISABLE /LOCK CONFIGURATION CHANGES...
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series 3.5.1 Security To quickly summarize there are three options available to implement configuration security lock out within the ATT2100. These include: (1) DIP settings on CPU Board (2) Software enable/disable on Write function using HHT or HART® PC.
Page 21
Manual:111508-2100-OM01V7.X ② If Zero Procedure was incorrectly performed display will show “ZR-Er” error code* ® AUTROL Series indicating failure and possible LRL setting out of sensor range capabilities. Span (or URL) Calibration: Sets the process value for Upper Range Value (20 mA).
Page 22
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series 3.7.2: Advanced Configuration Via Push Buttons. The advanced “smart” functions which can be initiated using the Zero/Span buttons are shown below. This includes re-ranging of transmitters (set URL/LRL without an external temperature source). Recommended: read instructions below while scanning Appendix II “Menu Tree”...
Page 23
Operat ion Manual:111508-2100-OM01V7.X ® AUTROL Series For “22 U-RNG”, from NORmal mode press Zero/Span, “1 TRIM” shows. Zero to scroll down to “2 SETUP”. Span to enter Sub-Menu “21 UNIT”, Zero to scroll to “”22 U-RNG”. Span to enter Numeric Entry screen, Enter number as in 3.7.3 above, Span to “SAVE”, Span for “DONE”, display returns to “22 U-RNG”.
Page 24
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series 3.7.4 Entering Alphanumeric Values The following Sub-Menus have data entry fields that allow an Alphanumeric (symbols, numbers, and capital and small letters) entry. See Appendix II “Alphanumeric Data Entry” for a diagram. This procedure required for use in: “33 Engineering Mode”, Sub-Sub-Menu “333 Engineering Units”...
Page 25
PC configuration software) or Autrol® A-CONF321 (HART® based UMPC tablet configurator). In addition to Autrol® configuration software the ATT2100 transmitter can also be configured using external third party Hand Held Terminals such as Emerson 275, 375 to 475 HHC or Meriam 4100/4150...
Page 26
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series 3.10 Wiring Connections for External HHT/ Ammeters The ATT2100 Temperature Transmitter can also be commissioned using a HART® enabled HHT or any HART® DDL supported PC software either before or after installation. A complete commissioning consists of configuring and/or verifying transmitter configuration data, testing the transmitter, testing the loop, and zero adjustment.
◈ Avoid direct contact with the signal leads and terminals to avoid potential electrocution .◈Only qualfied & trained personnel should be allowed to operate this transmitter. Operat ion Manual:111508-2100-OM01V7.X ® AUTROL Series...
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series .4 Commissioning on the bench with Hand-Held Terminal Use of a HHT is possible before or after field installation. However, as a good engineering practice it is recommended to first familiarize with available functions by pre-commissioning done on the bench before installing the transmitters in field.
4.7. Wiring Operat ion Manual:111508-2100-OM01V7.X ® AUTROL Series 4.7.1Cautions during Wiring (1) Install signal cables away from electrical noise sources like capacitors, transformers, motors, and power supplies where possible. (2) Before wiring pull out the electrical lead connection cap included and replace with appropriate cable glands.
◈ Both transmitter covers must be fully engaged to meet explosion proof requirements 4.7.4 Loop Power Wiring A. Loop Configuration AUTROL® Series Transmitters uses a two-wire loop powered system for 4~20mA analog and digital HART® transmission. External DC Power Supply is required for operation of this transmitter loop.
Page 31
C O M M TEST TEST (3) Intrinsic Safety Type (IS Barrier in safe area only) Operat ion Manual:111508-2100-OM01V7.X ® AUTROL Series C O M M C O M M TEST TEST [Figure 4-3 Connection between Transmitter and Power Supply]...
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series B. Wiring Installation General- Purpose and intrinsically Safe Type Installations Use metallic conduit or waterproof cable glands. Apply a non-hardening Sealant to the conduit threads to ensure water tight sealing. [Figure 4-4a Typical Wiring using Flexible Metal Conduit] Explosion proof &Flameproof Type (see Figure 4-4b)
Page 33
There are ground terminal provided on the inside and outside of the terminal box. Either one of these terminals may be used for grounding the transmitters. d. Use PVC insulated wire (600V min rated) for grounding. TEST TEST COMM COMM Operat ion Manual:111508-2100-OM01V7.X ® AUTROL Series...
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series 4.7.6 Power Supply Voltage and Load Resistance When connecting an external load make sure load resistance is within the range noted in the figure below. Note: voltages specified must be measured at the transmitter signal terminal input and not at the source.
POWER (-) RTD 4 wire TC(+) TC(-) + - - + + - - + COMM TEST COMM TEST Operat ion Manual:111508-2100-OM01V7.X POWER (+) POWER (+) ® AUTROL Series POWER (-) POWER (-) Figure 3-1. ATT2100 Temperature Transmitter Sensor Connections...
M6 x 1, on corners of a square at 32.5 mm centers. These tapped holes match holes on Autrol mounting brackets BA (Angle type) and BF (Flat type). Two electrical entrances, each ½”-14 NPT, can be used for direct mounting of a sensor, if ambient and process temperatures allow.
Page 37
During installation provide transmitters with adequate support. In the case of severe vibration, we recommend mounting to a 2” pipe using appropriate mounting brackets available as an option. Autrol® offers two styles of mounting brackets in SS. This includes a BA (Angle type) and BF (Flat type).
Chapter 5 On-line Operation 5.1 Overview This chapter describes configuration functions of an Autrol® ATT series SMART Temperature Transmitter. Transmitter can be configured in either On-Line or Off-Line mode. In On-Line Configuration Mode, you must connect through an external HHT (Hand Held Terminal) or PC configuration tool supporting HART®...
Manual:111508-2100-OM01V7.X Set the URL and LRL for the 4~20mA analog output. As linearization information for the ® AUTROL Series sensor is stored and applied over the entire published range under 5.5.1 users can re-range within specified limits without requiring an external temperature source input.
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series 5.6.2 Set Damping Time Determine the appropriate damping setting based on the required response time, signal stability, and other requirements of the loop dynamics of your system. The default damping TEST value is 1.0 seconds, and can be reset to damping values between 0 and 60 seconds.
Manual:111508-2100-OM01V7.X In Engineering mode ( when enabled) users have the added flexibility of enabling Square ® AUTROL Series Root mode only for local display purposed on LCD and retain a linear 4/20mA current output for a remote DCS /PLC control system.
Autrol® Series Chapter 6 Maintenance 6.1 Overview This chapter describes diagnostic and maintenance functions for the ATT series transmitters. 6.2 Safety Message For safety of operator please pay specific attention to safety note identified under Warning symbol (▲). 6.2.1 Warning ▲...
Manual:111508-2100-OM01V7.X Sensor Element mode to identify an electronics mode failure. ® AUTROL Series Check the PV to see if it is out of range. Check for adequate voltage to the transmitter. The transmitter always requires 17.9 ~ 45 Vdc.
If you must return failed transmitters or parts, first obtain a Return Material Authorization# before sending units back to Autrol® America Inc. for inspection, repair, or replacement.
Vdc) Connector 커넥터 CPU & Operat ion Manual:111508-2100-OM01V7.X Power Module ® AUTROL Series Analog Connector 6.4.2.2 Fail Mode and Jumper Switch of EEPROM-write Fail-mode and jumper switch of EEPROM-write is located front of electronics module (Refer to Figure 2-2, 2-3)
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series 6.4.3 Assembling the Electronics Housing Re-assembling procedure is same as follows:- 1. Make sure that Fail-mode and Jumper Switch are set exactly as the MCU board being replaced. 2. Insert electronics module into housing Connect back the cable connectors of analog sensor board &...
Page 47
A-STOR Analog EEPROM Whole Write Write initiated Operat ion Manual:111508-2100-OM01V7.X A-FAIL Analog EEPROM Whole Write Failure Write fail ® AUTROL Series -AC- Analog EEPROM Whole Write Done Write completed S-FL Sensor Failure Check sensor input S-OP Sensor PV exceed MWP Check limits.
Page 48
® Operation Manual: 150414-2100-OM01V7.X AUTROL Series ATT2100 Appendix II ATT2100 Smart Temperature Transmitter Quick Push Button Menu guide (Menu Tree)
Page 50
ATT2100 Operation Manual: 111508-2100-OM01V7.X Autrol® Series Appendix II (Continued)
Page 51
HHC please make sure you have the most current DDL (or DOF) version installed on your hand held device. All Autrol® transmitters have been tested prior to release of official DDL and DOF files for third party use, hence please check your installation and/or contact the original...
Need help?
Do you have a question about the ATT Series and is the answer not in the manual?
Questions and answers