Daikin EBLA08E23V3 Installation Manual page 23

Hide thumbs Also See for EBLA08E23V3:
Table of Contents

Advertisement

Connecting the user interface cable to the outdoor unit
Wires: 4×(0.75~1.25 mm²)
Maximum length: 200 m
[2.9] Control
[1.6] Room sensor offset
1 Access the electrical connections. See
electrical wiring to the outdoor
2 Connect the user interface cable to the outdoor unit. Fix the
cable with cable ties to the cable tie mountings.
a
X5M.11
X5M.12
X5M.16
X5M.15
a
User interface: Required for operation. Delivered with the
unit as accessory.
180°
Installing the user interface, and connecting the user interface
cable to it
You need the following user interface accessories (delivered on top
of the unit):
EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3
Daikin Altherma 3 M
4P685229-1D – 2022.10
"6.3.1  To connect the
unit" [ 4  17].
X1B
4
P1P2
3
+
2
PSU
1
X5M
11 12 15 16
6 Electrical installation
a
b
c
×2
d
×2
a
Front plate
b
Rear plate
c
Screws
d
Wall plugs
1 Mount the rear plate to the wall.
▪ Use the 2 screws and wall plugs.
▪ Use any of the 6 holes. The holes are compatible with
standard electrical box extenders of 60 mm.
a
a
Holes
b
Electrical box extender (field supply)
2 Connect the user interface cable to the user interface.
▪ Choose one of the 4 possible wiring intakes (a, b, c or d).
▪ If you choose the left or right side, make a hole for the cable
in the part of the casing where the casing is thinner.
b
60 mm
Installation manual
23

Advertisement

Table of Contents
loading

Table of Contents