To connect the backup heater kit to the outdoor unit
The wiring between the backup heater kit and the outdoor unit is as
follows:
A
X3M
1
2
3
4
5
B
X15M
6
7
8
9 10
X15M
HV
EKLBUHCB6W
A
Outdoor unit
B
Backup heater kit
HV
High voltage connections (backup heater thermal
protector + backup heater connection)
LV
Low voltage connection (backup heater thermistor)
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
1 On the backup heater kit, connect the LV and HV cables to the
appropriate terminals as shown in the illustration below.
F1B
X15M
1
2
7 6
9 8
10
LV
HV
2 On the outdoor unit, connect the HV cable to the appropriate
terminals as shown in the illustration below.
EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3
Daikin Altherma 3 M
4P685229-1D – 2022.10
K2M
K2M
1 3 5 13
2 4 6 14
X5M
1
2
1
2
LV
HV
6 7 8 9 10
X15M
EKLBUHCB6W
180°
3 On the outdoor unit, connect the LV cable to the appropriate
terminals as shown in the illustration below.
180°
4 Fix the cables with cable ties to the cable tie mountings.
Bypass valve kit necessity
For reversible systems (heating+cooling) in which an external
backup heater kit is installed, the installation of valve kit EKMBHBP1
is required if condensation is expected inside the backup heater.
6 Electrical installation
X3M
1 2 3 4 5
X3M
LV
1 2
X15M
EKLBUHCB6W
X5M
1 2