Connect Panic Input/Panic Output - ETC Echo Relay Panel Feedthrough Installation Manual

Table of Contents

Advertisement

Connect Panic Input/Panic Output

The Echo Relay Panel Feedthrough offers a panic capability that
complies with the UL 924 standard. When the ERP Feedthrough is
properly connected and has a panic "look" stored, it will automatically
play the recorded look when it receives a signal over the panic contact
input.
Panic can be triggered by a maintained contact input that can be configured as normally open
or normally closed. In addition, the relay panel optionally offers a +24 VDC (maximum 25 mA)
panic output that provides a feed to a lamp or LED, which indicates emergency activity.
Connect Panic Input
1. Pull two 1.5 mm
previously installed. See
2. Strip 5 mm (3/16 in) of insulation from the ends of each wire.
3. Remove the two pin Panic Input connector from position J3 on the termination I/O board.
4. Loosen the terminal screws.
5. While maintaining the wire twist as close to the connection as possible, insert each wire
into the terminals on the connector.
6. Tighten the connector screws firmly onto the wires.
7. Replace the connector to the termination I/O board.
Determine Panic Switching
Slide the Panic switch, labeled "S2 Panic" on the termination I/O board, to set the Panic Input
contact closure type:
For a normally open closure, slide the switch to N/O.
To disable the Input, slide the switch to Off (center position).
For a normally closed closure, slide the switch to N/C.
Connect Panic Output (optional)
1. Pull two 1.5 mm
conduit previously installed. See
2. Strip 5 mm (3/16 in) of insulation from the ends of each wire.
3. Remove the two pin Panic Output connector from J2 (labeled Emergency Indicator) on the
termination I/O board.
4. Loosen the terminal screws.
5. Insert the negative wire into pin 1 and insert the positive wire (this carries 24 VDC,
maximum current draw of 25 mA, to the lamp) into pin 2 of the terminals on the connector.
6. Tighten the connector screws firmly onto the wires.
7. Replace the connector to the termination I/O board.
Installation Procedure
2
(16 AWG) wires from your emergency contact location to the conduit
Cable Routing and Conduit Access on page 13
2
(16 AWG) wires from your external emergency indication lamp to the
Cable Routing and Conduit Access on page 13
Panic Output
Panic Input
.
.
25