ELECTRIC HEATER CONTROL SETTING

The following is a start guide for electric heater control.
Follow these step- by- step procedures after installed electrical heater.
STEP1: Change of SW501 (Required setting activation for Electric heater control)
SW501_1
OFF
ON
STEP2: Change of DN code setting (Required setting activation for Electric heater control)
Set data of DN (DC)
0001 or more
Fig. 66 - Control Outline (TA)
Fig. 65 - SW501
Table 25 – SW501 Settings
Table 26 – DN Code Settings
0000
SW501_2
OFF
OFF
*DN(DC) determines the value of
0000
Set Data
ΔAS-H
0.0
(°F)
Set Data
ΔAS-H (°F)
TA : Temperature of room sensor
Ts : Temperature set point on Remote controller
TSA_H : Temperature set air high (= TS-
TSA_L : Temperature set air low
41
Comments
Factory Setting
Activate EHeater
Comments
Factory Setting
Activate EHeater
AS- H.
Δ
0001
0002
0003
0004
0.9
1.8
2.7
3.6
0006
0007
0008
0009
5.4
6.3
7.2
8.1
AS- H)
Δ
(= TSA_H-
0005
4.5
0010
9.0
AH- L )
Δ