Carrier 40QQ-036ABA3-0A0 Installation Instructions Manual page 21

Vrf rooftop heat recovery and heat pump
Table of Contents

Advertisement

Menu
Parameter
MAT SET
LOW T LOCK
DRYBULB SET
ENTH CURVE
DCV SET
MIN POS
VENTMAX With 2- speed
fan units VENTMAX L (low
speed fan) and VENTMAX H
(high speed fan) settings
are required
VENTMAX L
Setpoints
VENTMAX H
VENTMIN With 2- speed
fan units VENTMIN L (low
speed fan) and VENTMIN H
(high speed fan) set
VENTMIN L
VENTMIN H
ERV OAT SP
EXH1 SET With 2- speed
fan units Exh1 L (low speed
fan) and Exh1 H (high
speed fan) settings are
required
Exh1 L
Exh1 H
EXH2 SET With 2- speed
fan units Exh2 L (low speed
fan) and Exh2 H (high
speed fan) settings are
required
Exh2 L
Exh2 H
Table 8 - Menu Structure (Cont.)
Parameter
Parameter range and
Default
Increment
Value
°
38 to 65
F
°
53
F
Increment by 1
°
- 45 to 65
F
°
32
F
Increment by 1
°
48 to 80
F
°
63
F
Increment by 1
ES1, ES2, ES3, ES4, or
ES3
ES5
500 to 2000 ppm
1100 ppm
Increment by 1
4.4V
2 to 10 VDC
2 to 10 VDC
or
4.4V
100 to 9990 cfm
Increment by 10
6V
4.4V
2 to 10 VDC
or
2.8V
100 to 9990 cfm
Increment by 10
3.7V
2.8V
°
0 to 50
F
°
32
F
Increment by 1
°
0 to 100
F
50%
Increment by 1
65%
50%
°
0 to 100
F
75%
Increment by 1
80%
75%
21
a
b
Setpoint determines where the economizer will
modulate the OA damper to maintain the mixed air
temperature.
Setpoint determines outdoor temperature when the
mechanical cooling cannot be turned on. Commonly
referred to as the Compressor lockout.
Setpoint determines where the economizer will
assume outdoor air temperature is good for free
°
cooling; e.g.; at 63
F unit will economize at 62
below and not economize at 64
°
is a 2
F deadband.
Enthalpy boundary "curves" for economizing using
single enthalpy
Displays only if CO2 sensor is connected. Setpoint for
Demand Control Ventilation of space. Above the
setpoint, the OA dampers will modulate open to bring
in additional OA to maintain a space ppm level below
the setpoint.
Displays ONLY if a CO2 sensor is NOT connected.
Displays only if a CO2 sensor is connected. Used for
Vbz (ventilation max cfm) setpoint. Displays 2 to 10 V
if <3 sensors (RA,OA, and MA). In AUTO mode
dampers controlled by CFM.
Displays only if a CO2 sensor is connected. Used for
Ba (ventilation min cfm) setpoint. Displays 2 to 10 V if
<3 sensors (RA, OA, and MA). Va is only set if DCV is
used. This is the ventilation for less than maximum
occupancy of the space. In AUTO mode dampers
controlled by CFM.
Only when AUX1 O = ERV
Setpoint for OA damper position when exhaust fan 1
is powered by the economizer.
Setpoint for OA damper position when exhaust fan 2
is powered by the economizer. Only used when AUX
is set to EHX2.
Notes
°
F and
°
F and above. There